Actual signals and parameters 23
SMOOTH
START
Smooth start ramp time will be effect in ramp time according
to settings of parameter 2621...2624.
11
DI1(INV)
Inverted digital input DI1. 0 = ramp pair 2, 1 = ramp pair 1.
-1
DI2(INV)
See selection
.
-2
DI3(INV)
See selection
.
-3
DI4(INV)
See selection
.
-4
DI5(INV)
See selection
.
-5
25 CRITICAL
SPEEDS
Speed bands within which the drive is not allowed to
operate.
2502 CRIT SPEED 1
LO
Defines the minimum limit for critical speed/frequency range
1.
0.0 Hz /
1 rpm
0.0…1400.0 Hz
/ 0…32000 rpm
Limit in rpm. Limit in Hz if parameter 9904 MOTOR CTRL
MODE setting is SCALAR: FREQ. The value cannot be
above the maximum (parameter
1 = 0.1 Hz
/ 1 rpm
2503 CRIT SPEED 1
HI
Defines the maximum limit for critical speed/frequency
range 1.
0.0 Hz /
1 rpm
0.0…1400.0 Hz
/ 0…32000 rpm
Limit in rpm. Limit in Hz if parameter 9904 MOTOR CTRL
MODE setting is SCALAR: FREQ. The value cannot be
below the minimum (parameter
).
1 = 0.1 Hz
/ 1 rpm
2504 CRIT SPEED 2
LO
See parameter
.
0.0 Hz /
1 rpm
0.0…1400.0 Hz
/ 0…32000 rpm
See parameter
1 = 0.1 Hz
/ 1 rpm
2505 CRIT SPEED 2
HI
See parameter
.
0.0 Hz /
1 rpm
0.0…1400.0 Hz
/ 0…32000 rpm
See parameter
1 = 0.1 Hz
/ 1 rpm
2506 CRIT SPEED 3
LO
See parameter
.
0.0 Hz /
1 rpm
0.0…1400.0 Hz
/ 0…32000 rpm
See parameter
1 = 0.1 Hz
/ 1 rpm
2507 CRIT SPEED 3
HI
See parameter
.
0.0 Hz /
1 rpm
0.0…1400.0 Hz
/ 0…32000 rpm
See parameter
1 = 0.1 Hz
/ 1 rpm
26 MOTOR
CONTROL
Motor control variables
2611 USER
DEFINED F1
Defines the first frequency point of the custom U/f curve.
10.0 Hz
0.0…1400.0 Hz Frequency
1 = 0.1 Hz
2613 USER
DEFINED F2
Defines the second frequency point of the custom U/f curve. 20.0 Hz