192 Actual signals and parameters
1502 AO1
CONTENT MIN
Defines the minimum value for the signal selected with
AO minimum and maximum correspond to the
settings as
follows:
-
x…x
Setting range depends on the parameter
setting.
-
1503 AO1
CONTENT
MAX
Defines the maximum value for the signal selected with
. See the figure for
-
x…x
Setting range depends on the parameter
setting.
-
1504 MINIMUM AO1 Defines the minimum value for the analog output signal AO.
See the figure for parameter
0.0 mA
0.0…20.0 mA
Minimum value
1 =
0.1 mA
1505 MAXIMUM
AO1
Defines the maximum value for the analog output signal AO.
20.0 mA
0.0…20.0 mA
Maximum value
1 =
0.1 mA
1506 FILTER AO1
Defines the filter time constant for analog output AO, ie the
time within which 63% of a step change is reached. See the
figure for parameter
.
0.1 s
0.0…10.0 s
Filter time constant
1 = 0.1 s
16 SYSTEM
CONTROLS
Parameter view, Run enable, parameter lock etc.
1601 RUN ENABLE
Selects a source for the external Run enable signal.
NOT SEL
Allows the drive to start without an external Run enable
signal.
0
DI1
External signal required through digital input DI1. 1 = Run
enable. If Run enable signal is switched off, the drive does
not start or coasts to stop if it is running.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
All parameters
No.
Name/Value
Description
Def/FbEq
AO
content
AO
(mA)
AO
(mA)
AO
content