6-10 (16)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 6 - Electrical installation
6.6.2.2 Cable entry
Enter the cable through the entry plate and secure per national and local
code requirements.
Figure 6-7
Typical cable entry
6.6.2.3 Stress cones
Shielded power cables must be terminated with stress cones and two-hole
lugs. The lug holes need to accept M12 [0.5 in] bolts, and accommodate
standard IEC (50 mm) or NEMA [1.75 in] two-hole patterns.
6.6.2.4 Checking cable insulation
Check the insulation of each cable with a megger before connecting it and
verify that the results are within the specification of the cable
manufacturer.
Leave the cable conductors unconnected at both ends until the
commissioning engineer has given his permission.
Legend
1
Cable entry
2
Cable connector
Top view detail
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......