Actual signals and parameters
196
35.06
MOT 2 TEMP FLT L
Defines the fault trip limit for the motor 2 temperature measurement function.
The fault indication is given when the limit is exceeded.
-10 … 5000 ohm/°C
(PTC/Pt100)
See
-10 … 5000
35.07
MOT MOD
COMPENSAT
Selects whether measured motor 1 temperature is used in the motor model
compensation.
NO
The function is inactive.
1
YES
The temperature is used in the motor model compensation.
Note:
Selection is possible only when Pt 100 sensor(s) are used.
2
42 BRAKE CONTROL
Control of a mechanical brake. The function operates on a 20 ms time level.
For the function description, see section
on
page
.
42.01
BRAKE CTRL
Activates the brake control function.
OFF
Inactive
1
ON
Active
2
42.02
BRAKE
ACKNOWLEDGE
Activates the external brake on/off supervision and selects the source for the
signal. The use of the external on/off supervision signal is optional.
OFF
Inactive
1
DI11
Active. Digital input DI11 is the signal source.
DI11 = 1: Brake is open.
DI11 = 0: Brake is closed.
2
DI12
Digital input DI11 is the signal source. See selection DI11
3
PAR 42.15
Signal source selected using Par.
DI11.
4
42.03
BRAKE OPEN DELAY Defines the brake open delay (= the delay between the internal Open brake
command and the release of the motor speed control). The delay counter
starts when the drive has magnetised the motor and risen the motor torque to
the level required at the brake release (parameters
and
Simultaneously with the counter start, the brake function energises the relay
output controlling the brake and the brake starts opening.
Note:
If DI is used for brake acknowledge, the speed control is released on the
DI activation and does not wait for the complete time delay.
0.0 … 5.0 s
Delay time. Set the delay time to the same value as the mechanical opening
delay of the brake specified by the brake manufacturer.
0 … 500
42.04
BRAKE CLOSE
DELAY
Defines the brake close delay. The delay counter starts when the motor actual
speed has fallen below the set level (parameter
) after the drive has
received the Stop command. Simultaneously with the counter start, the brake
control function de-energises the relay output controlling the brake, and the
brake starts closing. During the delay, the brake function keeps the motor live
preventing the motor speed from falling below zero.
Note:
POS HYSTERISIS.
0.0 … 60.0 s
Delay time. Set the delay time to the same value as the mechanical make-up
time of the brake (= operating delay when closing) specified by the brake
manufacturer.
0 … 6000
42.05
ABS BRAKE CLS
SPD
Defines the brake close speed. See parameter
.
Note:
POS HYSTERISIS.
0 … 1000 rpm
Speed (an absolute value)
0 …10000
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...