Actual signals and parameters in ACS800 Standard Application Program
35
PAR 22.08&09
Acceleration and deceleration times given by parameters 22.08 and 22.09
15
22.08 ACC PTR
Selects the source for 22.01
100 = 1 s
-255.255.31 …
+255.255.31 / C.-32768
… C.32767
Parameter pointer or constant value. See Parameter
22.09 DEC PTR
Selects the source for 22.01
100 = 1 s
-255.255.31 …
+255.255.31 / C.-32768
… C.32767
Parameter pointer or constant value. See Parameter
26
MOTOR CONTROL
Parameters through which the Adaptive Program can control the flux of the
drive.
26.06 FLUX REF PTR
Selects the source for the flux reference.
-255.255.31 …
+255.255.31 / C.-32768
… C.32767
Parameter pointer or constant value. See Parameter
40
PID CONTROL
Parameters through which the Adaptive Program can affect on the process
PID control.
40.07 ACTUAL1 INPUT SEL
PARAM 40.25
Source selected by parameter
6
40.25 ACTUAL1 PTR
Selects the source for
100 = 1%
-255.255.31 …
+255.255.31 / C.-32768
… C.32767
Parameter pointer or constant value. See Parameter
83
ADAPT PROG CTRL
Execution control of the Adaptive Program.
83.01 ADAPT PROG CMD
Selects the operation mode for the Adaptive Program.
STOP
Stop. The program cannot be edited.
START
Run. The program cannot be edited.
EDIT
Stop to edit mode. The program can be edited.
83.02 EDIT COMMAND
Selects the command for the block placed in the location defined by
parameter
. The program must be in edit mode. (See parameter
)
NO
Home value. The value automatically restores to NO after an editing
command has been executed.
PUSH
Shifts the block in the location defined by parameter
and the
subsequent blocks one location up. A new block can be placed in the emptied
location by programming the Block Parameter Set as usual.
Example:
A new block needs to be placed in between the current block
number four (parameters 84.20…84.25) and five (parameters 84.25…84.29).
In order to do this:
- Shift the program to the edit mode by parameter
.
- Select location number five as the desired location for the new block by
parameter
.
- Shift the block in location number 5 and all subsequent blocks one location
forward by parameter
(selection PUSH).
- Program the emptied location number 5 by parameters 84.25 to 84.29 as
usual.
DELETE
Deletes the block in the location defined by parameter
and shifts the
subsequent blocks one step down.
Index Parameter name /
value
Description
FbEq