232 Parameters
Energy saved in MWh compared to direct-on-line motor
connection. This parameter is incremented when
rolls over.
When this parameter rolls over, parameter
is incremented.
This parameter is read-only (see parameter
).
-
0…999 MWh
Energy savings in MWh.
1 = 1 MWh
Energy saved in kWh compared to direct-on-line motor
connection.
If the internal brake chopper of the drive is enabled, all energy
fed by the motor to the drive is assumed to be converted into
heat, but the calculation still records savings made by
controlling the speed. If the chopper is disabled, then
regenerated energy from the motor is also recorded here.
When this parameter rolls over, parameter
is incremented.
This parameter is read-only (see parameter
).
-
0.0…999.9 kWh
Energy savings in kWh.
10 = 1 kWh
Energy saved in kWh compared to direct-on-line motor
connection.
If the internal brake chopper of the drive is enabled, all energy
fed by the motor to the drive is assumed to be converted into
heat.
This parameter is read-only (see parameter
).
-
0.0…214748364.0
kWh
Energy savings in kWh.
1 = 1 kWh
Monetary savings in thousands compared to direct-on-line
motor connection. This parameter is incremented when
rolls over.
If you have not set the currency during the first start-up, you
can specify it in
Main menu - Primary settings - Clock,
region display - Units - Currency
.
This parameter is read-only (see parameter
).
-
0…4294967295
thousands
Monetary savings in thousands of units.
1 = 1 unit
Monetary savings compared to direct-on-line motor
connection. This value is a calculated by multiplying the
saved energy in kWh by the currently active energy tariff
(
).
When this parameter rolls over, parameter
is incremented.
If you have not set the currency during the first start-up, you
can specify it in
Main menu - Primary settings - Clock,
region display - Units - Currency
.
This parameter is read-only (see parameter
).
-
0.00…999.99 units
Monetary savings.
1 = 1 unit
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...