262
ACQ550-U1 User’s Manual
Maintenance
4. Reinstall the cooling fan.
5. Restore power.
Main fan replacement
The drive’s main cooling fan has a life span of about 60 000 operating hours at
maximum rated operating temperature and drive load. The expected life span
doubles for each 10 °C (18 °F) drop in the fan temperature (fan temperature is a
function of ambient temperatures and drive loads).
Fan failure can be predicted by the increasing noise from fan bearings and the
gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is
operated in a critical part of a process, fan replacement is recommended once these
symptoms start appearing. Replacement fans are available from ABB. Do not use
other than ABB specified spare parts.
Frame sizes R1
…
R4
To replace the fan:
1. Remove power from the drive.
2. Remove drive cover.
3. For frame size:
•
R1, R2: Press together the retaining clips on the fan
cover sides, and lift.
•
R3, R4: Press in on the lever located on the left side
of the fan mount, and rotate the fan up and out.
4. Disconnect the fan cable.
5. Reinstall the fan in reverse order.
6. Restore power.
Frame size R5
To replace the fan:
1. Remove power from drive.
2. Remove the screws attaching the fan.
3. Remove the fan: Swing the fan out on its hinges.
4. Disconnect the fan cable.
5. Reinstall the fan in reverse order.
6. Restore power.
Arrows in the fan show the directions of the rotation and air flow.
X0021
3
4
2
2
3
X5023
Bottom view
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...