70 Electrical installation
Connecting the control cables: JCU control unit
Notes
:
*Total maximum current: 200 mA
The wiring shown is for
demonstrative purposes only.
Further information of the usage of
the connectors and jumpers are
given in the text; more details are
available in the chapter
Wire sizes and tightening torques:
X2: 0.5 … 2.5 mm
2
(24…12 AWG).
Torque: 0.5 N·m (5 lbf·in)
X3, X4, X5, X6:
0.5 … 1.5 mm
2
(28…14 AWG).
Torque: 0.3 N·m (3 lbf·in)
X1
External power input
24 V DC, 1.6 A
+24VI
1
GND
2
X2
Relay output: Brake command
open/close
250 V AC / 30 V DC, 2 A
NO
1
COM
2
NC
3
X3
+24 V DC*
+24VD
1
Digital I/O ground
DGND
2
Digital input 1: Start up (par
)
DI1
3
Digital input 2: Start down (par
DI2
4
+24 V DC*
+24VD
5
Digital I/O ground
DGND
6
Digital input 3
DI3
7
Digital input 4: Speed ref sel1 (par
DI4
8
+24 V DC*
+24VD
9
Digital I/O ground
DGND
10
Digital input 5: Speed ref sel2 (par
DI5
11
Digital input 6: Speed ref sel3 (par
DI6
12
+24 V DC*
+24VD
13
Digital I/O ground
DGND
14
Digital input/output 1: Fault reset (par
) DIO1
15
Digital input/output 2: Drive ready (par.
bit 0)
DIO2
16
+24 V DC*
+24VD
17
Digital I/O ground
DGND
18
Digital input/output 3: Drive fault (par.
bit 10)
DIO3
19
X4
Reference voltage (+)
+VREF
1
Reference voltage (–)
-VREF
2
Ground
AGND
3
Analogue input 1 (Current or voltage,
selectable by jumper J1)
AI1+
4
AI1-
5
Analogue input 2 (Current or voltage,
selectable by jumper J2)
AI2+
6
AI2-
7
AI1 current/voltage selection
J1
AI2 current/voltage selection
J2
Thermistor input
TH
8
Ground
AGND
9
Analogue output 1 (current)
AO1 (I)
10
Analogue output 2 (voltage)
AO2 (U)
11
Ground
AGND
12
X5
Drive-to-drive link termination
J3
Drive-to-drive link. See separate section
below.
B
1
A
2
BGND
3
X6
Safe Torque Off. Both circuits must be closed
for the drive to start. See separate section
below.
OUT1
1
OUT2
2
IN1
3
IN2
4
Control panel connection
Memory unit connection
X3
(4 × 4-pole,
1 × 3-pole)
X2
(3-pole)
X1
(2-pole)
X4
(1 × 7-pole,
1 × 2-pole,
1 × 3-pole)
J1
J3
J2
Order of terminal headers and
jumpers
T
X5
(3-pole)
X6
(4-pole),
orange)
Summary of Contents for ACL30
Page 1: ...ABB high performance elevator drives User s manual ACL30 elevator drive ...
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 34: ...34 Operation principle and hardware description ...
Page 42: ...42 Planning the cabinet installation ...
Page 60: ...60 Planning the electrical installation ...
Page 126: ...126 Using the control panel ...
Page 318: ...318 Maintenance ...
Page 334: ...334 The Safe torque off function ...
Page 338: ...338 Mains chokes ...
Page 342: ...342 EMC filters ...
Page 348: ...Dimension drawings 348 Frame size B D1 D2 W H1 H2 ...
Page 349: ...Dimension drawings 349 ...
Page 350: ...Dimension drawings 350 Frame size C D1 D2 H2 H1 W ...
Page 351: ...Dimension drawings 351 ...
Page 352: ...Dimension drawings 352 Frame size D ...
Page 354: ...354 Dimension drawings EMC filters JFI 0x ...
Page 356: ...356 Dimension drawings Brake resistors JBR xx ...
Page 358: ...358 Dimension drawings ...