background image

7

REPLACEMENT INSTRUCTIONS 

 | 

 

ACH580-01 BXR UL TYPE 1 & 12, R1/R2

Step

Instruction

Diagram

14 

Connect the input wires (from fuse block) to the Input Terminals of 
the drive. 

Yellow  U1   to L1

Black V1  to L2

Red W1 to L3

R1 Frame: 

Using PZ2 bit, torque terminals to 5 in-lb (0.5 Nm).

R2 Frame: 

Using a PZ2 bit, torque terminals to 14 in-lb (1.5 Nm). 

15 

Connect the motor wires (from 1M contactor) to Motor Terminals of 
the drive. 

Yellow U2 to T1/U

Black V2 to T2/V

Red W2 to T3/W

R1 Frame: 

Using PZ2 bit, torque terminals to 5 in-lb (0.5 Nm).

R2 Frame: 

Using a PZ2 bit, torque terminals to 14 in-lb (1.5 Nm). 

16 

Re-install the CDPI 

A

 into control unit and secure with two  

zip ties 

B

Reconnect the RS485 terminal block 

C

  to EFB on control unit and 

secure with two zip ties 

D

 .

Reconnect any control wiring removed in steps 3 and 4.

WARNING! 

This configuration does not support Safe Torque Off (STO) 

functionality in bypass mode.

17 

Close the door and rotate latches counterclockwise.

B

A

C

D

Summary of Contents for ACH580-01 Series

Page 1: ...nclosure Disconnect all wiring Remove flange plate Remove drive Prepare replacement drive Remove conduit assembly Install in reverse order Check connections Power drive Reprogram and test Notes and ca...

Page 2: ...disconnecting power Turn off source power and wait 5 minutes for the DC bus capacitors to discharge Turn handle to the off position 2 Rotate latches clockwise and open the enclosure door 3 Perform vol...

Page 3: ...ve by pulling out the terminal block NOTE Remove any additional drive I O wiring 5 Using a PZ2 bit loosen and remove wires from the Input Terminals of the drive Using a PZ2 bit loosen and remove wires...

Page 4: ...lift the drive off the screws Carefully push the drive up lift the drive off of the screws and out of enclosure 9 Unpack the replacement drive UL Type 12 UL Type 12 drives require a UL Type 12 replace...

Page 5: ...ng a T20 bit loosen and remove two 2 M4x8 screws Remove conduit assembly Recycle the conduit assembly and hardware 11 CAUTION Use two people to install the drive Slide the drive mounting holes over th...

Page 6: ...ep Instruction Diagram 12 Place collar around drive Using a T20 bit secure the drive using the six 6 M4x20 screws that were removed earlier Using a T20 bit torque to 14 in lb 1 5 Nm 13 Secure the grou...

Page 7: ...o Motor Terminals of the drive Yellow U2 to T1 U Black V2 to T2 V Red W2 to T3 W R1 Frame Using PZ2 bit torque terminals to 5 in lb 0 5 Nm R2 Frame Using a PZ2 bit torque terminals to 14 in lb 1 5 Nm...

Page 8: ...80 01 BXR UL TYPE 1 12 R1 R2 Step Instruction Diagram 18 Power and reprogram the drive 19 Test and verify drive operation and motor direction 20 Back up and save parameters to the keypad prior to putt...