1MAC050144-MB C
Section 8
Measurement functions
615 series ANSI
557
Technical Manual
8.6.2
Function block
Figure 300:
Function block
8.6.3
Signals
Table 467: V1, V2, V0 Input signals
8.6.4
Settings
Table 468: V1, V2, V0 Non group settings
Name
Type
Default
Description
V
0
SIGNAL
0
Zero sequence voltage
V
1
SIGNAL
0
Positive phase sequence voltage
V
2
SIGNAL
0
Negative phase sequence voltage
Parameter
Values (Range) Unit
Step Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Off / On
Ps Seq V Hi high Lim
0.00...4.00
xVn
1.40
High alarm voltage limit for positive sequence voltage
Ps Seq V high limit
0.00...4.00
xVn
1.20
High warning voltage limit for positive sequence voltage
Ps Seq V low limit
0.00...4.00
xVn
0.00
Low warning voltage limit for positive sequence voltage
Ps Seq V low low Lim
0.00...4.00
xVn
0.00
Low alarm voltage limit for positive sequence voltage
Ps Seq V deadband
100...100000
10000
Deadband configuration value for positive sequence voltage for
integral calculation. (percentage of difference between min and max as
0,001 % s)
Ng Seq V Hi high Lim
0.00...4.00
xVn
0.20
High alarm voltage limit for negative sequence voltage
Ng Seq V High limit
0.00...4.00
xVn
0.05
High warning voltage limit for negative sequence voltage
Ng Seq V low limit
0.00...4.00
xVn
0.00
Low warning voltage limit for negative sequence voltage
Ng Seq V low low Lim
0.00...4.00
xVn
0.00
Low alarm voltage limit for negative sequence voltage
Ng Seq V deadband
100...100000
10000
Deadband configuration value for negative sequence voltage for
integral calculation. (percentage of difference between min and max as
0,001 % s)
Zro V Hi high Lim
0.00...4.00
xVn
0.20
High alarm voltage limit for zero sequence voltage
Zro V High limit
0.00...4.00
xVn
0.05
High warning voltage limit for zero sequence voltage
Zro V low limit
0.00...4.00
xVn
0.00
Low warning voltage limit for zero sequence voltage
Zro V low low Lim
0.00...4.00
xVn
0.00
Low alarm voltage limit for zero sequence voltage
Zro V deadband
100...100000
10000
Deadband configuration value for zero sequence voltage for integral
calculation. (percentage of difference between min and max as 0,001
% s)
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......