Step 4: Login as Admin
From the Settings screen log in by pressing the Login Button (All Caps Username: ADMIN; Default Password: ADMIN)
Step 5: Update settings
Once logged in as the Admin user the following settings can be updated:
•
Ethernet IP Address, Subnet Mask
•
Modbus Node Type for one or each of the 5 drives can be entered in the corresponding Drop-down lists.
•
The reconnection pause in seconds (default is 1s). This setting controls how often the VFD-Gateway will check for a
loss of connection with a Node/drive on the Modbus RTU network. Example, if the value is programmed to 3
seconds and node/drive is powered down, the gateway will check every 3 seconds for this node/drive. A lower
setting will decrease the update speed of the VFD-Gateway when there is a problem with the Modbus RTU network.
•
The Ethernet IP Address, Subnet Mask, and the Gateway information can be entered into the corresponding white
boxes
•
The Modbus Node Type for one or each of the 5 drives can be entered in the corresponding Drop-down lists.
(ACS380, ACS580, ACH580, ACQ580, ACS880, DCS880, ACH580 E-Clipse, and ACS355)
Example: Selecting ACH580
from drop-down as Node 1