QUICK START GUIDE
Page 6
Version 1.0
© 2021 ABB. All rights reserved.
Step 1
-
Mount the shelf
1.
Position the Combiner Shelf System mounting ears with the
mounting frame. If necessary, mounting ears can be reversed to
better align with other equipment in the frame.
2.
Attach shelf to the frame using four screws on each side (two
on each side)
-
12
-
24 (provided/Not provided).
3.
Torque to 40 in
-
lb (4.5Nm)
-
5/16”
socket.
4.
Provide 2 inch minimum clearance at back of shelf for converter
airflow.
Information
-
Tools Required
•
Wire cutters and strippers
•
Philips Screw Driver
-
#0
•
Cable crimpers
•
Flat Screw Drivers
-
1/8”
and
1/16”
•
Torque wrench (0
-
40 in
-
lb)
•
Sockets
-
7/16” & 5/16”
Step 2
-
Connect Chassis Ground
1.
Minimum 6 AWG wire is recommended.
2.
Lug
-
double
-
hole
1/4”
on
5/8”
centers (Lugs not provided).
3.
Secure lug with screws
-
10
-
32 (provided)
4.
Torque to 10
-
32 screws to 30 in
-
lb (3.4Nm)
-
5/16”
socket.
Some applications may rely on frame mounting screws for shelf ground omitting the need for this
shelf ground cable.
Figure 2 : Chassis Ground Connection
Chassis Ground
Figure 1 : Mounting shelf
NOTE: It is recommended that wire ferrules are used on all power and ground connections.
Slot For
Wire Dressing