266CRH / 266CRT, 266CSH / 266CST
MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
75
Application of the Diagnosis Main and Main 2 Registers
The
266CRH / 266CRT, 266CSH /
266CST has two ‘Diagnosis’
(Diagnosis Main and Main 2). The Diagnosis Main register
(Address 411, 412) each containing 16 bits.
The Diagnosis Main 2 register (Address 413) containing 16 bits.
Each bit represents an error.
The registers are structured as follows:
M11191
411
412
414
= true (1)
= false (0)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Figure 3: Diagnosis Main Register (Example, 16-bit Register)
The bit position is assigned to the errors in accordance with the
’Bit’ column in the table
Diagnosis codes
.
The following assignment applies to the example in
Figure 3
:
Register / Bit
Fault message
411
Bit 3
Process temperature out of range
411
Bit 5
Differential pressure sensor out of range
414
Bit 2
Multivariable input out of range
Diagnosis codes
Register
Address
Bit Error
411 0 –
1 –
2
Fourth sensor out of range
3
Process temperature out of range
4
Static pressure sensor out of range
5
Differential pressure sensor out of range
6 –
7 –
8
Process temperature out of limits
9
Sensor temperature out of limit
10
Static pressure sensor out of limits
11
Differential pressure sensor out of limits
12
Process temperature sensor fail
13
Sensor
temperature
fail
14
Static pressure sensor fail
15
Differential pressure sensor fail
Diagnosis codes
Register
Address
Bit Error
412
0
Maximum working pressure exceeded
1 Input
simulation
active
2 –
3 –
4 –
5 Non-Volatile
checking
active
6 Non-Volatile
storage
active
7
Non-Volatile memory burn error
8 Memory
failure
9 –
10
–
11
Electronic Interface communication error
12
Electronic
Interface
error
13
Non-Volatile memory burn error
14
Sensor memory fail
15
Sensor
invalid
414 0 Wrong
flow
direction
1 Multivariable
input
invalid
2
Multivariable input out of range
3 –
4
Multivariable calculation out of range
5 Replace
info
6 Electronic
temperature
error
7 Electronic
diagnosis
alarm
8
Changed operating conditions
9 PILD
output
10
Configuration
error
11
Electronic
diagnosis
warning
12
–
13
–
14
–
15
Pressure
overrange