266CRH / 266CRT, 266CSH / 266CST
MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
73
Optional text on display
An optional text will be shown automatically on the display with sending data to the registers 1001 to 1008. It allows displaying
strings in two lines written via MODBUS. The first text line is filed from register 1001 to 1004, the second text line is filed from
register 1005 to 1008.
It is possible to write all 8 registers in an access with the function WriteMultipleRegister (16).
The optional text lines can be disabled with the display menu an option ‘USER TEXT’.
Address
Parameter
Data type
Function code
32 bit
16 bit
Read
Write (32 bit)
Write (16 bit)
–
1001
User Text Line 1 Sign 1 & 2
Usign16
03
–
06, 16
–
1002
User Text Line 1 Sign 3 & 4
Usign16
03
–
06, 16
–
1003
User Text Line 1 Sign 5 & 6
Usign16
03
–
06, 16
–
1004
User Text Line 1 Sign 7
Usign16
03
–
06, 16
–
1005
User Text Line 2 Sign 1 & 2
Usign16
03
–
06, 16
–
1006
User Text Line 2 Sign 3 & 4
Usign16
03
–
06, 16
–
1007
User Text Line 2 Sign 5 & 6
Usign16
03
–
06, 16
–
1008
User Text Line 2 Sign 7
Usign16
03
–
06, 16