10
266CRH / 266CRT, 266CSH / 266CST
MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
… 2 Use in potentially explosive atmospheres
Ex Explosion protection aspects (United States and Canada)
According to Factory Mutual standards for the assurance of
fundamental safety requirements in the United States of
America. Ratings are with or without integrated digital display.
• FM
3600:
ಫ
Approval Standard for Electrical Equipment for use
in Hazardous (Classified) Locations, General Requirements
ಬ
.
• FM
3611:
ಫ
Approval Standard for Non-Incendive Electrical
Equipment for Use in Class I and II, Division 2 and Class III
Division 1 and 2 Hazardous (Classified) Locations
ಬ
.
• FM
3615:
ಫ
Approval Standard for Explosion-proof Electrical
Equipment General Requirements
ಬ
.
• FM
3810:
ಫ
Approval Standard for Electrical Equipment for
Measurement, Control and Laboratory Use
ಬ
.
• NEMA
250:
ಫ
Enclosures for Electrical Equipment (1000 Volts
Maximum)
ಬ
.
According to CSA standards for the assurance of fundamental
safety requirements in Canada. Ratings are with or without
integrated digital display.
• C22.2 No 142-M1987:
ಫ
Process Control Equipment Industrial
Products.
• C22.2 No 213-M1987:
ಫ
Non-incendive Electrical Equipment for
Use in Class I, Division 2 Hazardous Locations Industrial
Products
ಬ
.
• C22.2 No 30:
ಫ
Explosion-Proof Enclosures for Use in Class I
Hazardous Locations Industrial Products
ಬ
.
• C22.2 No 25:
ಫ
Enclosures for Use in Class II Groups E, F and G
Hazardous Locations
ಬ
.
• CSA-C22.2 No 94-M91: ‘Special Purpose Enclosures Industrial
Products
ಬ
.
• ANSI/ISA 12.27.01: ‘Requirements for Process Sealing
Between Electrical Systems and Flammable or Combustible
measuring medium’.
Type of protection:
ಫ
Explosion-proof
ಬ
Certification
(Code ET)
The 266 transmitters have FM certification for the following
hazardous location protections:
Code ET ratings
Explosionproof (US)
Class I, Division 1, Groups ABCD,
T5 for Ta =
Æ
50 °C to +85 °C
Flame-proof (US)
Class I, Zone 1, AEx d, IIC,
T4 for Ta =
Æ
50 °C to +85 °C
Explosionproof (Canada):
Class I, Division 1, Groups BCD,
T5 for Ta =
Æ
50 °C to +85 °C
Flame-proof (Canada)
Class I, Zone 1, Ex d, IIC,
T4 for Ta =
Æ
50 °C to +85 °C
Dust Ignition Proof
(US and Canada)
Class II, III Division 1, Groups EFG,
T5 for Ta =
Æ
50 °C to +85 °C
FM Approvals Certificate
USA:
FM16US0066X
Canada:
FM16CA0036X