5  Safety instructions
•  When using the vacuum pump set regard all local regulations concerning safety on work and those  

regulations of the operator of the installation. 

•  Do not install the vacuum pump on high exposed GIS parts. This may cause hazards. The spiral hose  

has sufficient length to operate the vacuum pump on the floor or an occasional working table. 

•  There is a risk of stumbling and slipping. Block the working place to prevent stumbling over the  

associated parts.

•  Only personnel which has been trained on hydromechanical operating mechanisms and switching  

apparatus shall operate the vacuum pump set.

•  Wear safety glasses, oil-resistant gloves and safety shoes during work.
•  Do not release hydraulic oil of the operating mechanism or lubricating oil of the vacuum pump to the  

environment. Dispose oil-soaked clothes environmentally compatible. Hydraulic and lubricating oil is 
harmful to the environment. 

•  Avoid direct contact to hydraulic or lubricant oil. Direct contact may cause irritations. Clean affected  

sites with abundant amount of water. 

•  Do not breathing or swallowing hydraulic or lubricant vapor, mist and oil. Breathing high concentration  

levels or swallowing may cause damages to health or death. 

•  Do not put defective or damaged parts into operation. Replace damaged parts and parts which recom-

mended period of use is exceeded by new parts. The device shall only be repaired by the manufacturer. 

•  For following switching operations of the operating mechanism on the coupled breaker, it has to be  

secured that the switching device is filled with SF6 gas at appropriate operating pressure. The mnimal  
oil level at fully charged operating mechanism should not be lower than the oil level given in the oil level 
charts of the technical description of the oil handling kit 1HDS680617P0001.

6  Standards and directives
The vacuum pump set is in conformance with the machine directive 2006/42/EG.
Additional directives do not apply.
 
7  Shipping and storage
Transport and store the vacuum pump set only in the supplied transportation case to prevent damage and 
protect especially the spiral hose and the expansion tank from sunlight. 
Store only in dry and dust-free areas. Storage temperature: +5°C … +40°C

8 Commissioning
Check all parts of the vacuum pump set for damages before commissioning:
1.  Check the vacuum pump for damages. If the vacuum pump is damaged do not put it into operation!
2.  Check the expansion tank for damages. If the expansion tank is damaged it has to be replaced by a  
  new one before commissioning! 
3.  Check the spiral and the hydraulic hose as well as the pipe connections for damages. If the spiral and  
  the hydraulic hose or the pipe connections are damaged they have to be replaced by a new one before  
 commissioning!
4.  Check the period of use of the spiral and hydraulic hose. We recommend to replace the spiral and the 
  hydraulic hose by a new one at least five years after purchase to prevent leakages and malfunctions. 

Summary of Contents for 1HDS112160R0001

Page 1: ...ydromechanical operating mechanisms Product manual 1HDS680632 REV A The vacuum pump set 1HDS112160R0001 is designed to evacuate hydromechanical operating mechanisms of type AHMA and HMB in mounted discharged condition before commissioning 01 Vacuum pump set ...

Page 2: ...iated documents 3 4 Scope of delivery 3 5 Safety instructions 4 6 Standards and directives 4 7 Shipping and storage 4 8 Commissioning 4 9 Technical information 5 10 Operating instructions 5 11 Maintenance 6 12 Troubleshooting 6 13 Disposal 6 14 Technical data 6 15 Manufacturer information 6 Declaration of conformity ...

Page 3: ...anual 2 Abbreviations AHMA Hydromechanical operating mechanism type A CO Close Open COV Change over valve HMB Hydromechanical operating mechanism type B SF6 Sulphur hexafluoride 3 Associated documents Technical description of oil handling kit 1HDS680617P0001 Instruction for operation and maintenance 1HDH118041 or comparable 4 Scope of delivery The vacuum pump set will be delivered in a transportat...

Page 4: ... new parts The device shall only be repaired by the manufacturer For following switching operations of the operating mechanism on the coupled breaker it has to be secured that the switching device is filled with SF6 gas at appropriate operating pressure The mnimal oil level at fully charged operating mechanism should not be lower than the oil level given in the oil level charts of the technical de...

Page 5: ...witching characteristics e g simultaneity The mentioned pressure ranges are absolute pressure values e g 50 mbar absolute The provided pressure gauge has a relative pressure sensor display Consequently a conversion of absolute to relative pressure values with regard to the ambient atmospheric pressure is necessary 10 Operating instructions 1 Open the tank connection of the low pressure tank 2 Conn...

Page 6: ...460 x 580 mm Total weight 21 kg 15 Manufacturer information ABB AG High Voltage Products Brown Boveri Strasse 30 63457 Hanau Germany For any assistance support or service we recommend to contact directly our local representatives first They have extensive knowledge of the specific customer needs the individual circumstances and the possibilities of the whole ABB group and are consequently able to ...

Page 7: ......

Page 8: ...to purchase orders the agreed particulars shall prevail ABB AG does not accept any responsibility whatsoever for poten tial errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without p...