Panel Programming ( ESL, ESX, Elite S & S- Lite only)
You will need to tell the panel what zone the smoke detector is connected to.
I n Program mode press
< PROGRAM> < 123>
< ENTER>
then put in the zone (1-8)
that the smoke is on
< 1- 8> < ENTER>
now turn On option
< 5>
< ENTER> .
With this feature turned On, when the smoke detector is triggered the Alarm will activate
even if the system is disarmed. Also the sirens will pulse On and Off making a different
sound to a normal burglar alarm. The user will have to clear the alarm with their normal
alarm code.
i.e.
P 123 E 8 E 5 E
(zone 8 is now a 24 Hour Fire zone)
+ 12V
-0V
C
Z 1-8
+ 12V
-0V
C
Z 1-8
Multiple Detectors in Parallel Connection (using N/ O Contacts)
* Diagram B
+ 12V
-0V
C
Z 1-8
Multiple Detectors in Series Connection (using N/ C Contacts) Daisy-chain wiring
* Diagram C
Multiple Detectors in Series Connection (using N/ C Contacts) I ndividual wiring
* Diagram D
EOL Fitted in last Detector
EOL
EOL
Connection Diagram
E
O
L
EOL
EOL
Built- in 2K2 EOL
The HM-MI NI -12V has a built-in 2K2 EOL resistor
This allows you to easily wire one detector,
directly to a Zone I nput on an Elite series control
panel.
(see diagram A)
I f you are using a different control panel or wish
to wire multiple HM-MI NI -12V’s to the same
zone
(see diagram B, C & D)
you will need to
remove the 2K2 EOL Jumper.
Remove
Jumper
for No
2K2 EOL
N/ O
Contacts
N/ C
Contacts
Wire Colour
Connection
Red
+ 9 to 16 VDC
Black
-0 VDC
Yellow
Normally Open
Blue
Common
White
Normally Closed
=
=
=
=
=
* Remove 2K2 EOL Jumper for this wiring
* Remove 2K2 EOL Jumper for this wiring
* Remove 2K2 EOL Jumper for this wiring
+
1
2
V
-0
V
C
Z
1
-8
P
o
w
e
r
T
e
rm
.
Z
o
n
e
T
e
rm
.
Alarm Panel
Termination
Simple Wiring
for Elite Systems
Using Built-in 2K2 EOL
* Diagram A
Drill a 10-13mm hole in the Wall/
Ceiling for cabling.
Note. Wires must leave the detector
through the rubber grommet.
The Detector must be sealed from
Wall/ Ceiling cavity.
Onboard Circuit Diagram