Operation & Testing 

Pressing the Test  Button will activate test mode, trig-
gering both the Relay and the Buzzer. The HM-MI NI -
12V smoke detector should be tested every month. 

 

The smoke detector sounder will automatically reset, 
when all the smoke has cleared. 

 

The alarm system sounders may need to be  
deactivated from the control keypad. 

 

Hush feature. 

When the smoke detector has been 

activated, pressing the test button for 1 second, will 
silence that smoke detectors sounder. 

This will not 

hush the controllers, sounders or other smoke detec-
tors connected. 

 

When using any aerosol smoke detector tester, please 
follow all instructions provided on the can. 
I mproper use may result in degraded detector 
performance. 

ARROWHEAD ALARM PRODUCTS Ltd. 
344b Rosedale Rd, 
Albany,  
Auckland. 
Ph. 09 414 0085 
Fax. 09 414 0088 
www.aap.co.nz 
 
v1.04 

HM-MI NI -12V 

AUTO RESETTI NG SMOKE DETECTOR 

 
Specifications 

Detection Type   

Photoelectric Chamber 

Power Source   

9-16 Volts DC 

Standby Current 

5mA 

Alarm Current   

25mA 

Buzzer Output   

85db @ 3 meters 

Output Relay 

 

N/ O and N/ C Contacts 

 

 

 

 

50mA max 

(2K2 EOL fitted)

 

Dimensions 

 

51mm x 

Ø

45mm 

(smoke)

 

 

 

 

 

Ø

64mm 

(base)

 

Standards:                  

GB4715-2005, EN14604, UL217

 

Suggested Mounting Locations  

Smoke alarms must be located in escape routes on 
all levels within the household unit.  
On levels containing sleeping spaces, they must be 
installed within the sleeping space, or within  
3 metres of every sleeping space door and they must 
be audible through closed doors. 

 

Always Refer to NZS 4514: 2009 or the latest  
standard for full installation recommendations. 

=  MOUNTI NG AREA 

=  DON’T FI T AREA 
  (DEAD AI R SPACE) 

M
a

x

. 3

0

0

m

m

 

CEI LI NG 

W

A

L

L

 

BEST  

LOCATI ON 

ACCEPTABLE 

LOCATI ON 

Note. Smoke Detectors should be 
mounted a minimum of 400mm away 
from Air Con. or forced air vents. 

 

Test at least once a month.  

 

 

Min.  

100mm 

Min.  

200mm 

900mm  

or less 

Beams, joists and 
exposed rafters 
deeper than 
460mm are 
treated as walls 

Min.  

200mm 

Always Refer to NZS 4514: 2009 or the latest  
standard for full installation recommendations. 