MHGRV-X Field Technical Guide
APPENDIX A
19
SAT Options Jumper Settings
Refer to
Tables 8 & 9
to determine the SAT Option Jumper settings.
See
Figures 2 & 3 on pages 5 & 6
for jumper locations.
STAND-ALONE MODE
SAT OPTIONS JUMPER SETTINGS*
CONDITION
SETTING
MHGRV-X Only
Normal
MHGRV-X with
MODGAS-X**
MODGAS-X
MHGRV-X with
MODGAS II***
MODGAS
* For SAT Sensor testing, use
Table 5
for
Normal & MODGAS-X jumper setting and use
Table 6
for MODGAS jumper setting.
** In this situation, also set MODGAS-X SAT
Option to Jumper Setting 1. See the
MODGAS-X
Technical Guide
for more information.
*** The MODGAS II must have PU1 resistor
installed.
Table 8: Stand Alone Mode SAT OPTIONS Jumper
Settings
COMMUNICATIONS MODE
SAT OPTIONS JUMPER SETTINGS*
CONDITION
SETTING
VCM / VCM-X / SA/ RNE *
Normal
MUA, VAV/CAV**
Normal
VCCX2, VCB-X*
Normal
* For SAT Sensor testing, use
Table 5
for Normal
jumper setting. SAT should be connected to the
Main Controller.
** For SAT Sensor testing, use
Table 5
for Normal
jumper setting. SAT should be connected to the
MHGRV-X Controller.
Table 9: Communications Mode SAT OPTIONS
Jumper Settings
SAT Wiring Conditions
MODGAS-X ONLY
MHGRV-X ONLY
MODGAS-X & MHGRV-X
STAND-
ALONE
Install Supply Air
Sensor in MODGAS-X.
Install Supply Air
Sensor in MHGRV-X.
Set “SAT Options”
Jumpers to “Normal”.
Install Sensor in MODGAS-X and daisy-chain it
to the MHGRV-X. Set “SAT Options” Jumpers to
“MODGAS X”. If connected to a MODGAS II
Retrofi t, Set “SAT Options” Jumpers to “MODGAS”.
VCCX2
VCB-X
Install Supply Air Sensor
in VCCX2 or VCB-X.
Connect to VCCX2 or
VCB-X using E-BUS
cable.
Install Supply Air
Sensor in VCCX2 or VCB-
X. Connect to VCCX2
or VCB-X using E-BUS
cable.
Install Supply Air Sensor in VCCX2 or VCB-X.
Connect to VCCX2 or VCB-X using E-BUS cable.
VCM-X,
SA, RNE
Install Supply Air Sensor
in Main Controller.
Connect to Main
Controller using I
2
C
cable.
Install Supply Air
Sensor in Main Controller.
Connect to Main
Controller using I
2
C cable.
Install Supply Air Sensor in Main Controller.
Connect to Main Controller using I
2
C cable.
VCM,
VAV/CAV,
MUA,
MUA II,
MUA IID
Install Supply Air Sensor
in MODGAS-X.
Connect to Main
Controller using I
2
C
cable.
Install Supply Air
Sensor in MHGRV-X.
Connect to Main
Controller using I
2
C cable.
Install Supply Air Sensor in MODGAS-X.
Connect to Main Controller using I
2
C cable.
Table 7: SAT Wiring Conditions