AAON R90800 Technical Manual Download Page 9

Technical Guide

 

                     

Full Digital Module

9

Modes of Operation

 

NOTE:

  See Unit Con

fi

 gurations Chart on page 10 for more 

information about compressor staging.

Digital Stage 1 / Digital Stage 2

On units with two Digital Scroll Compressors, the 

fi

 rst compressor (A1) 

will be designated as Digital Stage 1 and the second compressor (A2) 
will be designated as Digital Stage 2.

On units with four Digital Scroll Compressors, there may be instances 
where compressor numbers on the module do not correlate with the 
mechanical compressors’ numbers. Therefore, Digital Stage 1 refers to 
the 

fi

 rst set of Digital Scroll Compressors (A1/B1) that will stage on 

together and Digital Stage 2 refers to the second set of Digital Scroll 
Compressors (A2/B2) that will stage on together. Please refer to AAON’s 
wiring diagram for speci

fi

 c wiring of the unit.

Off Mode

The Full Digital Module will be in the Off Mode when no signal is 
being received from the VCM-X Modular series controller to run the 
compressors.

Cooling Mode

When a Cool Signal is received, the Full Digital Module will go into 
Cooling Mode. At this point, Compressor A1 (and B1*) will energize and 
Digital Stage 1 Analog Output will modulate as necessary to maintain 
the Supply Air Temperature at the Active Supply Air Setpoint that is 
broadcast from the VCM-X Modular series controller. 

When Digital Stage 1 reaches 100%, a stage up timer is started. If Digital 
Stage 1 stays at 100% for the Stage Up timer, Compressor A2 (and B2*) 
will energize and both Digital Stage 1 and Digital Stage 2 outputs will 
go to 50% and begin to modulate together. 

If both systems are energized and they go below 30% and the Supply Air 
is below the Supply Air Setpoint by the Cooling Stage Window value, 
the stage down timer is started. If the systems remain below 30% for 
the duration of the stage down timer, Digital Stage 2 will deactivate and 
Digital Stage 1 will  go to 60%.  Digital Stage 1 will stage down if it is 
at 0% for the duration of the stage down timer.

* If con

fi

 gured for 4 modulating compressors.

Heat Pump Heating Mode (Air to Air)

Heating Mode works the same as Cooling Mode except the Reversing 
Valve is switched and the sequence is opposite. Compressors modulate 
up when below the Heating Supply Air Setpoint and modulate down 
when above the setpoint.

Dehumidi

fi

 cation Mode

In Dehumidi

fi

 cation Mode, compressors will be controlled to maintain 

the Suction Pressure Temperature Setpoint. Digital Stage 1—Com-
pressor A1 (and B1*) will modulate up to 100% before Digital Stage 
2—Compressor A2 (and B2*) can be energized.  When Digital Stage 2 
is energized, Digital Stage 1 will be locked at 100%.  

* If con

fi

 gured for 4 modulating compressors.

Defrost Mode

In Defrost Mode, if only Digital Stage 1 is energized, it will go to 100% 
and the reversing valve will deactivate. If both Digital Stage 1 & Digital 
Stage 2 are energized, they will both go to 100% and the reversing valve 
will be deactivated. The duration for Defrost Mode is determined by the 
VCM-X Modular series controller.

NOTE:  

Defrost Mode is only available if a One Condenser or 

Two Condenser Head Pressure Module is installed.

Staging Delays

Staging Delays minimum run times and minimum off times are sent 
from the VCM-X Modular series controller. 

Summary of Contents for R90800

Page 1: ...Full Digital Module Technical Guide Factory Packaged Controls Tulsa...

Page 2: ...0 PH 816 505 1100 FAX 816 505 1101 E mail mail wattmaster com Visit our web site at www orioncontrols com WattMaster Form AA FDM TGD 01G Copyright July 2016 WattMaster Controls Inc AAON Manual Part Nu...

Page 3: ...e Module OE370 23 HP1C is also installed Module Overview Figure 1 Full Digital Module The Full Digital Module is connected to the VCM X Modular Control ler using the E BUS Distribution Module OE365 23...

Page 4: ...standard I2 C modular cable to connect with the VCM X Modular Controller VCM X Expansion Module or 12 Relay Expansion Module The Full Digital Module can also be directly connected to the VCM X Modula...

Page 5: ...UT COM COM COM EXC EXC EXC P4 P4 P4 BK BK BK RD RD RD WH WH WH P2 P2 P2 P1 P1 P1 P3 P3 P3 P5 P5 P5 C1 C1 C1 C2 C2 C2 P6 P6 P6 SHLD OUT COM EXC P4 BK RD WH P2 P1 P3 P5 AO1 SIG 1 SIG 2 SIG 3 SIG 4 AO2 G...

Page 6: ...r lengths and 100 and 150 foot lengths Figure 4 VCM X Modular E BUS Controller to Full Digital Module Wiring Diagram Connect To Other WattMaster Approved E BUS Expansion Module s HSSC Cable HSSC Cable...

Page 7: ...mon Failure To Do So Will Result In Damage To The Controllers T to T R to R SHLD to SHLD Size Transformer For Correct Total Load VCM X Modular Controller 8 OE332 23E VCMX MOD A VCM X Modular E BUS Con...

Page 8: ...e to observe polarity could result in damage to the boards Table 1 Unit Configurations Chart UNIT CONFIGURATIONS PERMUTATION SYSTEM A SYSTEM B HARDWARE VCM X WSHP CONFIGURATION Comp A1 Comp A2 Comp B1...

Page 9: ...ital Stage 2 outputs will go to 50 and begin to modulate together If both systems are energized and they go below 30 and the SupplyAir is below the Supply Air Setpoint by the Cooling Stage Window valu...

Page 10: ...diagnostic blink code LED It will light up and blink out diagnostic codes See Table 2 for Diagnostic Blink Code descriptions The blink code descriptions are also located on the mod ule s front cover N...

Page 11: ...ctive R3 This LED will light up when Compressor B1 is enabled and will stay lit as long as Compressor B1 is active R4 This LED will light up when Compressor B2 is enabled and will stay lit as long as...

Page 12: ...If the COMM LED does not blink then communications have not been established Check the connection between the VCM X Modular Con troller the VCM X Modular E BUS Controller the E BUS Distribution Modul...

Page 13: ...e and Voltage Chart for R410A Refrigerant testing Table 4 The chart shows a temperature range from 20 F to 80 F For troubleshooting pur poses the DC Voltage readings are also listed with their corresp...

Page 14: ...Digital Room Sensor And Or Digital CO Sensor 2 Warning 24 VAC Must Be Connected So That All Ground Wires Remain Common Failure To Do So Will Result In Damage To The Controllers T to T R to R SHLD to...

Page 15: ...COMM GND VDC 485 DRV 24VAC GND PWR YS102308 REV 1 I2C TO COMM DIST BOARD OUTPUT Modular Cable Connect To VCM X Modular Controller HSSC Cable Connect To E BUS Distribution Module Connect To Other Watt...

Page 16: ...2425 So Yukon Ave Tulsa OK 74107 2728 Ph 918 583 2266 Fax 918 583 6094 AAON Manual Part No R84500 WattMaster Manual Form No AA FDM TGD 01G www aaon com...

Reviews: