Full Digital Module
Technical Guide
6
Installation and Wiring
VCM-X Modular E-BUS Controller to
Full Digital Module Wiring
The Full Digital Module directly connects to the VCM-X Modular E-
BUS Controller using a modular HSSC cable. The Full Digital Module
requires a 24 VAC power connection with an appropriate VA rating. See
Figure 4
below for wiring.
Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.
NOTE:
Contact Factory for the correct HSSC cable length for
your application. Cables are available in ½ and 3 meter
lengths and 100 and 150 foot lengths.
Figure 4: VCM-X Modular E-BUS Controller to Full Digital Module Wiring Diagram
Connect To Other
WattMaster-Approved
E-BUS Expansion Module(s)
HSSC Cable
HSSC Cable
Connect To VCM-X E-BUS Controller
OE370-23-FD-A
Full Digital Module
+5V
SIG 2
GND
OPTI
O
N
S
ALARM
ANALOG
STAT
+5V
COMM
GND
SIG 4
GND
BIN 2
R1
R2
GND
RELAYS
ADDRESS
SIG 3
+5V
GND
BIN 1
COM
+5V
SIG 1
R3
R4
Rc
AO1
AO2
PWM1-
PWM1+
PWM2-
PWM2+
PWR
24 VAC Transformer
3 VA Minimum
Line Voltage
24 V
A
C
GND
WARNING!!
Observe Polarity! All boards must be
wired with GND-to-GND and 24 VAC-
to-24 VAC. Failure to observe polarity
could result in damage to the boards.
This Dip Switch Is
Not Used For This
Application
If Using One Module,
Set Addresses To Off.
If Using Two Modules,
Set Addresses
Consecutively.