Start Up and Commissioning

General

In order to have a trouble free start-up, it is important to follow a few 
simple procedures. Before applying power for the 

fi

 rst time, it is very 

important to run through a few simple checks.

One of the most important checks to make before powering up the system 
for the 

fi

 rst time is to make sure that the VCM-X Modular or VCM-X 

Modular E-BUS Controller is con

fi

 gured properly for your application. 

Refer to the 

VCM-X Controller Technical Guide

 or 

VCM-X Modular 

E-BUS Controller Technical Guide 

for more information. A handheld 

Modular Service Tool, Modular System Manager, or System Manager 
Touch Screen connected to the VCM-X Modular or VCM-X Modular 
E-BUS Controller  will allow you to con

fi

 gure your application. Refer to 

the 

VCM-X / RNE Operator’s Interfaces SD Technical Guide

 or 

System 

Manager TS II Technical Guide

 for more information.

Check all wiring leads at the terminal block for tightness. Be sure that 
wire strands do not stick out and touch adjacent terminals. Con

fi

 rm 

that all sensors required for your system are mounted in the appropriate 
location and wired into the correct terminals.

WARNING:

    Observe polarity! All boards must be wired 

 

GND-to-GND and 24 VAC-to-VAC. Failure to 

 

observe polarity could result in damage to the 

 boards.

 

Table 1:  Unit Con

fi

 gurations Chart

UNIT CONFIGURATIONS

PERMUTATION

SYSTEM A

SYSTEM B

HARDWARE

VCM-X WSHP 

CONFIGURATION

Comp A1

Comp A2 Comp B1

Comp B2

Relay 1

Relay 2

Relay 3

Relay 4

1

On/Off

On/Off

Use VCM-X Modular 

Series Controller Only

2 Compressors

2

Digital

On/Off

Use VCM-X Modular 

Series Controller Only

2 Compressors
Digital Compressor

3

Digital

Digital

Use VCM-X Modular 

Series Controller and 

Full Digital Module

2 Compressors
Full Digital

4

On/Off

On/Off

On/Off

On/Off

Use VCM-X Modular 

Series Controller Only

4 Compressors

5

Digital

On/Off

On/Off

On/Off

Not Available

Not Available

6

Digital

On/Off

Digital

On/Off

Use VCM-X Modular 

Series Controller Only

4 Compressors
Digital Compressor

7

Digital

Digital

Digital

Digital

Use VCM-X Modular 

Series Controller and 

Full Digital Module

4 Compressors
Full Digital

In the 

Cooling Mode

, the Compressors will stage in the following order:

Permutations 1, 2 & 3:

  Compressor A1 -> Compressor A2

Permutations 4:

  Compressor A1 -> Compressor A2 -> Compressor B1 -> Compressor B2

Permutations 6: 

 Compressor A1 & Compressor A2 -> Compressor B1 -> Compressor B2

Permutations 7:

  Compressor A1 & Compressor A2 -> Compressor B1 & Compressor B2

In the 

Dehumidi

fi

 cation Mode

, the Compressors will stage in the following order:

Permutation 4: 

 Compressor A1 & Compressor A2 -> Compressor B1 -> Compressor B2

All other permutations in the Dehumidi

fi

 cation Mode stage as described in the Cooling Mode.

Summary of Contents for R90800

Page 1: ...Full Digital Module Technical Guide Factory Packaged Controls Tulsa...

Page 2: ...0 PH 816 505 1100 FAX 816 505 1101 E mail mail wattmaster com Visit our web site at www orioncontrols com WattMaster Form AA FDM TGD 01G Copyright July 2016 WattMaster Controls Inc AAON Manual Part Nu...

Page 3: ...e Module OE370 23 HP1C is also installed Module Overview Figure 1 Full Digital Module The Full Digital Module is connected to the VCM X Modular Control ler using the E BUS Distribution Module OE365 23...

Page 4: ...standard I2 C modular cable to connect with the VCM X Modular Controller VCM X Expansion Module or 12 Relay Expansion Module The Full Digital Module can also be directly connected to the VCM X Modula...

Page 5: ...UT COM COM COM EXC EXC EXC P4 P4 P4 BK BK BK RD RD RD WH WH WH P2 P2 P2 P1 P1 P1 P3 P3 P3 P5 P5 P5 C1 C1 C1 C2 C2 C2 P6 P6 P6 SHLD OUT COM EXC P4 BK RD WH P2 P1 P3 P5 AO1 SIG 1 SIG 2 SIG 3 SIG 4 AO2 G...

Page 6: ...r lengths and 100 and 150 foot lengths Figure 4 VCM X Modular E BUS Controller to Full Digital Module Wiring Diagram Connect To Other WattMaster Approved E BUS Expansion Module s HSSC Cable HSSC Cable...

Page 7: ...mon Failure To Do So Will Result In Damage To The Controllers T to T R to R SHLD to SHLD Size Transformer For Correct Total Load VCM X Modular Controller 8 OE332 23E VCMX MOD A VCM X Modular E BUS Con...

Page 8: ...e to observe polarity could result in damage to the boards Table 1 Unit Configurations Chart UNIT CONFIGURATIONS PERMUTATION SYSTEM A SYSTEM B HARDWARE VCM X WSHP CONFIGURATION Comp A1 Comp A2 Comp B1...

Page 9: ...ital Stage 2 outputs will go to 50 and begin to modulate together If both systems are energized and they go below 30 and the SupplyAir is below the Supply Air Setpoint by the Cooling Stage Window valu...

Page 10: ...diagnostic blink code LED It will light up and blink out diagnostic codes See Table 2 for Diagnostic Blink Code descriptions The blink code descriptions are also located on the mod ule s front cover N...

Page 11: ...ctive R3 This LED will light up when Compressor B1 is enabled and will stay lit as long as Compressor B1 is active R4 This LED will light up when Compressor B2 is enabled and will stay lit as long as...

Page 12: ...If the COMM LED does not blink then communications have not been established Check the connection between the VCM X Modular Con troller the VCM X Modular E BUS Controller the E BUS Distribution Modul...

Page 13: ...e and Voltage Chart for R410A Refrigerant testing Table 4 The chart shows a temperature range from 20 F to 80 F For troubleshooting pur poses the DC Voltage readings are also listed with their corresp...

Page 14: ...Digital Room Sensor And Or Digital CO Sensor 2 Warning 24 VAC Must Be Connected So That All Ground Wires Remain Common Failure To Do So Will Result In Damage To The Controllers T to T R to R SHLD to...

Page 15: ...COMM GND VDC 485 DRV 24VAC GND PWR YS102308 REV 1 I2C TO COMM DIST BOARD OUTPUT Modular Cable Connect To VCM X Modular Controller HSSC Cable Connect To E BUS Distribution Module Connect To Other Watt...

Page 16: ...2425 So Yukon Ave Tulsa OK 74107 2728 Ph 918 583 2266 Fax 918 583 6094 AAON Manual Part No R84500 WattMaster Manual Form No AA FDM TGD 01G www aaon com...

Reviews: