26
Startup
General
ONLY
QUALIFIED,
AUTHORIZED
PERSONNEL SHOULD POWER ON, OR
STARTUP THIS EQUIPMENT.
Before starting up the equipment, building
construction should be complete, and start-
up personnel should:
Have a working knowledge of general
HVAC and mechanical commissioning
procedures and practices.
Be familiar with unit functions, features,
optional unit accessories, and all control
sequences.
Have appropriate literature on hand for
consultation.
Before the structure is occupied, the
installation, and/or startup personnel must
take three essential steps:
1. Check-Out
2. Start-Up
3. Commissioning
Check-Out
Equipment should be thoroughly checked
for loose wiring, a free spinning blower
wheel and well fitting access panels. Air
handling units should not be operated
without proper ductwork and access panels
installed, except as required during start-up
and air balancing.
1.
Check all electrical connections to be
sure they are tight.
2.
Open all access panels, and remove all
shipping screws, or restraints.
3.
Clean out any debris that may be
present.
4.
Check wheel alignment, and tightness of
fan drives.
5.
Check
bearing
locking
collars
if
provided and fan wheel set screws for
tightness.
6.
Turn fan wheels to assure free rotation.
7.
Ensure electrical supply matches the unit
nameplate.
8.
Ensure condensate lines are correctly
connected.
9.
Check local codes for any special
provisions.
10.
Replace and/or close all access panels.
Procedures
Note:
Failure to adhere to the following
start-up
procedures
will
void
all
manufacturer warranties.
Install gauges, voltmeter and ammeter
before
start-up.
Observe
refrigerant
pressures during initial operation. Note, and
determine the cause of any excessive sound
or vibration. Follow start-up procedures
outlined below to start each piece of
equipment.
Note:
Completed factory test sheets are in
the equipment literature packet shipped
inside the unit. Factory run-test readings
recorded on the test sheets may be helpful to
reference during start-up.
Equipment
operation
during
construction is not recommended.
Construction site pollution can affect
unit operation, and seriously degrade
performance.
Operation
during
construction
will
void
all
manufacturers’ warranties.
CAUTION
Summary of Contents for F1-024
Page 31: ...31 ...
Page 36: ...36 Figure 8 Heat Pump Piping Diagram with Indoor Unit above Outdoor Unit ...
Page 37: ...37 Figure 9 Heat Pump Piping Diagram with Outdoor Unit above Indoor Unit ...
Page 40: ...40 Thermostat Installation and Wiring Figure 12 2 Stage Cooling with Electric Heat ...
Page 41: ...41 Figure 13 2 Stage Cooling with Heat Pump and Electric Heat ...
Page 42: ...42 Figure 14 2 Stage Cooling and Electric Heat with Hot Gas Reheat and Humidistat ...
Page 43: ...43 Figure 15 Main Control Board for Units Equipped with Modulating Hot Gas Reheat ...
Page 45: ...45 Figure 17 5kW Electric Heat ...
Page 46: ...46 Figure 18 10 kW Electric Heat ...
Page 47: ...47 Figure 19 15 kW Electric Heat ...
Page 48: ...48 Figure 20 20 kW Electric Heat ...
Page 49: ...49 Figure 21 25 kW Electric Heat ...
Page 55: ...55 ...