Repeat the process of prefilter installation until all housings are filled
with latched prefilters as shown below.

3.8 Pressure Gauge: It is recommended that a pressure gauge be
installed across the filter bank to indicate when the prefilter needs to
be replaced. The pressure gauge will register the pressure differential
across the bank. As the prefilter loads with dirt the resistance to the
airflow, and consequently, the pressure across the filter will increase.
The pressure across the gas phase chemical filter will remain
constant since this filter collects gas molecules and not particulate. If
a pressure gauge has not been included in the customer s purchase
order, discuss the pressure gauge options with your AAF representative.
If a pressure gauge has been included in the order, refer to the
specific installation instructions supplied with the gauge.

3.9 After-filters: Some gas phase chemical filter media may
discharge a small plume of dust on fan start-up when the filter system
is first operated. This may result in dust being deposited on the
downstream side of the filter bank. There are generally two ways to
deal with this:

— In industrial applications that are not particularly sensitive to small
amounts of dust, this initial plume is allowed to blow off and the
deposited dust is swept up or vacuumed.
— In applications that are sensitive to dust, it is recommended that
an after-filter similar to the prefilter discussed above be supplied on
the downstream side of the filter bank. This will require an
additional frame bank to be mounted in the duct on the downstream
side of the gas phase chemical filters. In addition to the MERV 7
after-filter a higher rated air filter may also be installed to provide a
significantly improved level of air cleanliness in the space to be
ventilated. Many options are available up to HEPA and ULPA filter
systems. If an after-filter or higher efficiency final filter with
appropriate support frames have not been included in the
customer s purchase order, discuss the additional filter options with
your AAF representative. If any of these items have been included
in the order, refer to the specific installation instructions supplied
with those items.

4.0 Start-up Instructions

When the fan system is started up, ensure that the airflow volume is
controlled so that the actual airflow velocity across the filter bank does
not exceed the rated face velocity shown on the AAF submittal
drawing. If there is any doubt about the required face velocity the
default maximum velocities shall be as follows:

— MD and CG cassettes: 500 feet per minute
— HD cassettes: 250 feet per minute

Immediately on start-up examine the filter system for any apparent air
leaks or other anomalies. Air leaks may be detected by noise or by
use of a synthetic smoke puffing device at the internal and perimeter
joints and seams of the filter bank installation. Correct or repair any
discrepancies, as necessary. Repeat this examination after 24 hours
of operation and again after one week of operation. 
Monitor the pressure drop across the filter bank to ensure that the
filters are operating within the pressure range expected and to ensure
that the pressure drop is not too high. Consult the AAF drawing for the
expected clean filter pressure differentials.

5.0 Maintenance

5.1 Prefilter: If a prefilter has been included as part of the system,
record the pressure drop weekly to obtain the status of the particulate
filter. A normal particulate prefilter can be expected to last for between
2 and 3 months before reaching its final recommended pressure drop
(see the AAF drawings for details). However, under heavier or lighter
dust loading conditions this may vary. At an airflow velocity of 500 feet
per minute the 2  deep AAF PerfectPleat filter can be expected to
have an initial pressure drop in the range of 0.35  water gauge. The
recommended final pressure drop is 1.0  water gauge. This means
that when a pressure drop increase of 0.65  water gauge has been
recorded it is time to change the prefilter.

13

Summary of Contents for FAH-102-2P-HD

Page 1: ... federal government codes laws and policies Table of Contents 1 0 Introduction 1 1 About this document 1 2 Packaging and shipping receiving and inspection handling and storage 1 3 Product descriptions 1 4 Product model designations 1 5 Product drawings 1 6 Assembly general comments 1 7 Related system equipment 2 0 Principles of Operation 3 0 Installation Instructions 3 1 Space requirements 3 2 Fou...

Page 2: ... shall be handled with great care The components shall be retained and stored in their protective packaging until immediately prior to installation Care shall be taken to ensure that the packages are not dropped or subjected to any impact loads At all times the equipment shall be protected from exposure to weather The equipment shall be stored in a clean dry temperature controlled environment All ...

Page 3: ...ips in two halves 24 high x 12 wide x 12 deep Type CG cassette ships in one piece The three 3 types of gas phase chemical filter cassettes that can be supplied are as follows 1 3 3 Particulate filters Particulate filters will typically be AAF PerfectPleat pleated filters Depending on the size of the filter frame ordered 24 high x 24 wide x 2 deep full size filters 24 high x 12 wide x 2 deep or 12 ...

Page 4: ...ing individual components with a maximum weight of approximately 55 pounds 25 kg riveting or screwing components together and caulking Completion of the following preparations and provision of the following items will be the responsibility of the installer or others Site preparation Stainless steel rivets as required Caulk as required Sheet metal or other duct as required Sheet metal perimeter bla...

Page 5: ...ia in a V bank configuration of media beds that maximizes the media exposed to the air stream reduces the air stream velocity through the media bed maximizes energy efficiency and maximizes the removal of contaminants and the life of the product The method of contaminant removal is through a combination of the physical property of adsorption and the chemical process of oxidation AAF offers a varie...

Page 6: ...2 2P HD FAH 202 2P CG Cassette support angle Pre filter latch in closed position Cassette sealing and locking channel Filter sealing locking handle Filter face sealing gasket Locking handle support tab Rivet hole 4 each side and top and bottom The entering air face of an FAH 202 2P MD housing is shown 3 3 Typical FAH Details 6 ...

Page 7: ...igures 1 and 3 Locate the lines of caulk as shown and as follows Two 2 unbroken transverse lines between horizontal and vertical rows across the entire width of the filter bank at each level beginning at the support surface One orthogonal line of caulk across the full depth of the frame at any point where the side panel of the FAH joins to the top or bottom of the housing forming a corner that con...

Page 8: ...aulking around the perimeter to achieve a complete seal Detailed caulking instructions are provided in paragraph 3 4 2 Use Sheet Metal Panels to Seal Top and Sides of Frame Bank as Necessary Suggested Ductwork Connection Detail Figure 3 Caulk Seal Typ caulk Supplied by Others Hardware Supplied by Others 3 5 Preparation for Filter Installation At this time a filter bank similar to that shown lower ...

Page 9: ...nd plastic bag You may notice that each cassette or half cassette is accompanied by a plastic bag containing loose gaskets see right These are supplied for use when the cassette is being installed into an AAF Side Access Housing SAH and are not required for installation into the FAH frame bank DISCARD THESE GASKETS 3 6 4 Handling of the Cassette The AAF SAAF Cassette is designed to be sturdy and t...

Page 10: ...r panels of the FAH as shown in the illustration below Adjacent housings will share a set of tabs Note that the locking handle support tabs are shipped installed on MD and most HD housings 3 6 7 Sealing and Locking the Cassettes in Place The patent pending AAF SAAF Seal system ensures that the gas phase chemical filter cassettes are properly sealed into position against the face gasket to prevent ...

Page 11: ...ates upwards Step 5 Making sure that the locking handle is hooked behind the front flange of the locking handle support tab and cannot slip off rotate the locking handle downwards so that the face of the handle engages the web of the channel forcing it against the cassettes and pushing them into the housing to compress the face gasket Step 7 Now repeat the process on the right hand side of the cen...

Page 12: ...prefilters as shown in the sequence at right Each individual FAH can accommodate one prefilter A standard 24 x 24 ASHRAE style filter will fit into the size 202 housing and a standard 24 x 12 ASHRAE style filter will fit into the size 201 and 102 housings The Front Access Housings are designed to accept a 2 deep pre filter only For best results AAF recommends the use of the MERV 7 rated PerfectPle...

Page 13: ...filter with appropriate support frames have not been included in the customer s purchase order discuss the additional filter options with your AAF representative If any of these items have been included in the order refer to the specific installation instructions supplied with those items 4 0 Start up Instructions When the fan system is started up ensure that the airflow volume is controlled so th...

Page 14: ... seal between the gas phase chemical filter cassette and the FAH on the air leaving face of the housings whenever new SAAF Cassettes are installed 5 7 General System Maintenance Ducts filter support frames access doors and other system infrastructure should be checked at least every 6 months Examine all components for the following 5 7 1 Cleanliness Sweep and vacuum all standing dust or dirt in th...

Page 15: ...3 2 Check for missing or damaged filters and system leaks Replace filters and re seal as necessary 7 0 Spare Parts List It is recommended that the following spare parts be stored at the installation site for routine maintenance purposes The quantities required will depend on the size of the system Consult with your AAF representative to determine actual quantities required Minimum recommended quan...

Page 16: ...ations without notice 10300 Ormsby Park Place Suite 600 Louisville Kentucky 40223 6169 www aafintl com Customer Service 800 477 1214 Fax 800 254 3019 ISO Certified 9001 2000 2006 AAF International GPF 3 115 NOV 06 QG 2M SAAF Front Access Housings with SAAF Cassette Gas Phase Chemical Filters Installation Operation and Maintenance Instructions ...

Reviews: