background image

18

PLANNING THE VENT SYSTEM

Plan the route of the vent system from the discharge of the blower to
the planned location of the vent terminal.

1. Layout total vent system to use a minimum of vent pipe and elbows.

2. This water heater is capable of venting  flue gases equivalent to 25'

(7.6 m) of 2" pipe, 65' (19.8 m) of 3" pipe, or 128' (39.0 m) of 4" pipe
as listed in Table 1.

TABLE 1

Number of

2" Maximum

3" Maximum

4" Maximum

90° Elbows

Pipe - ft. (m)

Pipe - ft. (m)

Pipe - ft. (m)

1

20 (6.1)

60 (18.3)

120 (36.6)

2

15 (4.6)

55 (16.8)

112 (34.1)

3

10 (3.0)

50 (15.2)

104 (31.7)

4

--

45 (13.7)

96 (29.3)

5

--

40 (12.2)

88 (26.8)

6

--

35 (10.7)

80 (24.3)

The minimum vent lengths for each of the pipe sizes is one 90° on top of
the unit plus 2' (61 cm) of straight pipe and the appropriate termination.

NOTE:  The equivalent feet (m) of pipe listed above are exclusive of
the  termination. That is, the termination, with an installed screen, is
assumed to be in the system and the remainder of the system must
not exceed the lengths discussed above.

3. The blower discharge adapter is made to accept only straight

sections of 2"  pipe.  To start, a minimum of 2 inches (5.1 cm) of 2"
pipe must be attached to the blower discharge, see Figure 17.

If using 2" inch vent pipe:
A minimum of 2 inches (5.1 cm) must be attached to the blower
before the first elbow. After the first elbow add the additional
venting required for the installation. The total system cannot
exceed the lengths discussed above, where each elbow is
equal to 5 feet (1.5 m) of straight pipe.

If using 3" or 4" inch vent pipe:
Two inches (5.1 cm) of pipe must be attached to the blower discharge
before adding a reducer to acquire the desired pipe diameter. An
appropriately sized 45 degree elbow (supplied locally-a schedule 40
DWV) vent terminal must be obtained with an equivalent screen (supplied
in vent kit). The total system cannot exceed the equivalent pipe lengths
discussed above where each elbow is equal to 5 feet (1.5 m) of straight
pipe (3" vent pipe) or 8 feet (2.4 m) of straight pipe (4" vent pipe).

U.S. Installations
NOTE: 
This unit can be vented with PVC pipe materials (Cellular Core
ASTM-F891; DWV ASTM-D2665 or CSA B181.2; Schedule 40, 80, 120
ASTM-D1785 or CSA B137.3; or SDR Series ASTM-D2241 or CSA B137.3),
CPVC pipe materials (CPVC41 ASTM-D2846 or CSA B137.6; Schedule
40, 80 ASTM-F441 or CSA B137.6; or SDR Series ASTM-F442), ABS pipe
materials (Schedule 40 DWV ASTM-D2661 or CSA B181.1 or Schedule
40 DWV Cellular Core ASTM-F628). The fittings, other than the TERMINATION
should be equivalent to PVC-DWV fittings meeting ASTM D-2665 (Use
CPVC fittings, ASTM F-438 for CPVC pipe and ABS fittings, ASTM D-2661/
3311 for ABS pipe). If CPVC or ABS pipe and fittings are used, then the
proper cement must be used for all joints, including joining the pipe to the
Termination (PVC Material). If local codes do not allow the use of the PVC
termination when a material other than PVC is used for venting, then an
equivalent fitting of that material may be substituted if the screen in the PVC
terminal is removed and inserted into the new fitting.

PVC Materials should use ASTM D-2564 Grade Cement; CPVC Materials
should use ASTM F-493 Grade Cement and ABS Materials should use
ASTM D-2235 Grade Cement.

Canadian Installation of this water heater must comply with CAN/CSA
B149.1 - Natural Gas and Propane Installation Code which requires
the vent system components be certified to ULC S636.

This water heater has been design certified to be vented with PVC
pipe certified and marked as complying with ULC S636. This water
heater is supplied with a 2 inch 22.5 degree termination elbow that is

a special fitting that must be used with this appliance. Any outlet
piping, fittings and glue used to vent this appliance that is not supplied
by the manufacturer must comply with the ULC S636 requirements.

If the water heater is being installed as a replacement for an existing power
vented heater in pre-existing venting, a thorough inspection of the existing
venting system must be performed prior to any installation work. Verify that
the correct material as detailed above has been used, and that the minimum
or maximum vent lengths and terminal location as detailed in this manual
have been met. Carefully inspect the entire venting system for any signs of
cracks or fractures, particularly at the joints between elbows and other
fittings and the straight runs of vent pipe. Check the system for signs of
sagging or other stresses in the joints as a result of misalignment of any
components in the system. If any of these conditions are found, they must
be corrected in accordance with the venting instructions in this manual
before completing the installation and putting the water heater into service.

NOTE: A. For water heaters in locations with high ambient temperatures
(above 100°F) it is recommended that CPVC or ABS pipe and fittings be used.
B. A 22.5 degree elbow (2" vent pipe) or a 45 degree elbow (3" and 4" vent
pipe) with an installed screen VENT TERMINAL must be used in all cases.

4. There will be some installations where condensate will be formed in

the horizontal runs of the vent system. This condensate will run into
the condensate boot attached to the blower and out the fitting. The
water heater is shipped with condensate hose that attaches to the
fitting on the condensate boot. No other Tee or fitting is required. See
Figures 17, 20 and 21.

CONDENSATE

This water heater is a condensing unit and requires a drain to be located
in close proximity to allow the condensate to drain safely. The condensate
drains from the unit at the exhaust tee located at the bottom of the unit
(see figure 16) and from two places on the blower assembly (see figure
17). Condensate from this water heater is mildly acidic. Please note that
some local codes require that condensate is treated by using a pH
neutralizing filter prior to disposal.

NOTE: It is important that the condensate hose on the bottom of the unit is
not installed elevated above the clamp that is secured to the side of the
jacket, see figure 16. This must be true for the entire length of the hose
from the clamp to the exit into an appropriate drain. If these instructions are
not followed or if the condensate hose is blocked, water will spill from the
condensate trap. As with every water heater installation, a drain pan
should be used to prevent water damage to the surrounding area. If
necessary, a condensate pump with an incorporated reservoir may be
used to pump the water to an appropriate drain. To avoid condensate
spillage, select a pump with an overflow switch.

Caution must be used to ensure that the drain is free and clear of
debris and will not allow backflow through the condensate hose. Consideration
must be given to avoid freezing of the condensate lines which could result in
excessive build up of condensate inside the water heater. Waterproof heat
tape may be required to prevent freezing of the condensate lines. Please
ensure that the outlet of the condensate drain does not create a slippery
condition which could lead to personal injury.

Summary of Contents for W/HOT

Page 1: ...LS W HOT SURFACE IGNITION ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTE...

Page 2: ...onal Fuel Gas Code as it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features of water heaters and have a thorough understandin...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...ortion of the instructions call the local gas utility or the manufacturer whose name appears on the rating plate 5 Carefully plan the place where you are going to put the water heater Correct combusti...

Page 6: ...D Plastic Top E E On Off Switch F F Exhaust Tee G G Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve...

Page 7: ...so must be primed by filling half of the loop with water prior to operating the water heater Carefully plan the location of the loops and straight sections of hose prior to cutting hoses If necessary...

Page 8: ...s All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynamic...

Page 9: ...an others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water from this heater fits into one of these groups or if there is a local code or state...

Page 10: ...stalled Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or...

Page 11: ...or exceeds the Energy Policy Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulation blanket to this he...

Page 12: ...pening shall have a minimum free area of 1 square inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 7 FIGURE7 2 When communicating with the outd...

Page 13: ...hemicals calcium and sodium chloride water softener salt waxes and process chemicals are typical compounds which are potentially corrosive Do not store products of this sort near the heater Also air w...

Page 14: ...y into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm above or at any distanc...

Page 15: ...he water heater Use a soapy water solution not a match or open flame Rinse off soapy solution and wipe dry This heater is approved for operation up to 5 300 feet 1 615 m without alteration Highaltitud...

Page 16: ...llow water to run until a constant flow is obtained This will let air out of the water heater and the piping 4 Check all water piping and connections for leaks Repair as needed VENT PIPE ASSEMBLY Ther...

Page 17: ...e CAN CSA B149 1 Instructions on proper installation through a sidewall are provided in Figure 15 Plan the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pip...

Page 18: ...ter heater has been design certified to be vented with PVC pipe certified and marked as complying with ULC S636 This water heater is supplied with a 2 inch 22 5 degree termination elbow that is a spec...

Page 19: ...blower housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the ou...

Page 20: ...one quarter inch 0 64 cm outside of the line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on ins...

Page 21: ...l piping and fittings must be joined by the proper procedures as described under VENT PIPE PREPARATION INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe wh...

Page 22: ...o prevent any combustion gases escaping into the room If the plug is not securely tightened remove and reinstall using Teflon tape on the threads Once installed along with the rest of the vent configu...

Page 23: ...r leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical V...

Page 24: ...nd above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning...

Page 25: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristlebrush Thisprocesssoftensandprepares...

Page 26: ...nd HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off...

Page 27: ...a is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressingthe COOLER buttondecreasestemperatureandpr...

Page 28: ...anode rod is one of a rotten egg smell in the hot water The smell is a result of four factors which must all be present for the odor to develop a A concentration of sulfate in the supply water b Litt...

Page 29: ...Contact a qualified installer or service agency to replace a flooded water heater Do not attempt to repair the unit It must be replaced At least once a year a visual inspection should be made of the...

Page 30: ...the temperature pressure relief valve discharge line and 2 that the water discharge will not cause any property damage as the water may be extremely hot see Figure 28 If after manually operating the...

Page 31: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Page 32: ...ed wiring If the control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condi...

Page 33: ...ot within 11 5 and 18 8 ohms at room temperature 8 Ensure the correct size of vent pipe 2 3 4 was used per installation manual for vent length Using larger pipe than required may cause excessive air t...

Page 34: ...34 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Page 35: ...nless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE...

Page 36: ...36...

Reviews: