A.O. Smith VF VB 500 Instruction Manual Download Page 44

44

TROUBLESHOOTING IGNITION SYSTEM

Fault  Messages and Lockout Status (* = stage number: 1, 2, 3, or 4)

FAULT DISPLAYED 

 

DESCRIPTION 

RED LED 

LOCKOUT

“Display Fail” 

Communications with UIM interrupted 

Continuous 

Auto Reset

 

 

Check communication cable to UIM.  Try moving to other Internal Communications connector on MCB. Also check the 

connectors where the cable is plugged in for best connecting wires.

“Comm. Fail Stg.*” 

Communications with FCB interrupted 

Continuous 

Auto Reset

 

 

Same as above.  Also try swapping FCB and UIM communications cables.

“Low AC Voltage” 

Line voltage less than 90 vac 

Continuous 

Auto Reset

 

 

Check incoming power line for loss of voltage.  May also be caused by a power line brown-out (momentary loss of voltage)

“Low 24VAC” 

Voltage from transformer less than 18 vac 

Continuous 

Auto Reset

 

 

Check transformer output.  Should be over 24vac.  May be caused by excessive current drain or a faulty transformer

“Brown Out Reset” 

Indicates a brown out reset occurred 

- - - - 

None

 

 

Caused by a momentary dip in voltage on the MCB +5vdc power bus.  Contact factory.  (Not considered a serious problem 

if it only occurs on very rare occasions.)

“Timeout Reset” 

Indicates a watchdog reset occurred 

- - - - 

None

 

 

Caused when the micro executes the software in an improper way. Contact factory. (Not considered a serious problem if it 

only occurs on very rare occasions.)

“FCB Comm Timeout” 

FCB did not receive command from MCB 

Continuous 

SOFT

 

 

Caused when communications between the MCB and the FCB are interrupted.  May occur when a surge of power on a 

nearby device (i.e. arc welder) creates an EMI burst.  Not a serious problem if it occurs rarely.

“No Flow”  

Water is not flowing 

Continuous 

SOFT

 

 

Caused by the flow switch being open when it should be closed.  Check water lines, pump, flow switch contacts, wiring.

“Blower Prov Stg*  

Blower pressure is too low it they should have been closed.   

Continuous 

SOFT

 

 

Check blower, switch contact, wiring, and for air leaks. 

“Blocked Flue” 

Flue is Blocked 

 

Continuous 

SOFT

 

 

Caused by the blocked flue switch contacts being open when they should have been closed.  Check for flue blockage, switch 

contacts, wiring.

“Blocked Inlet” 

Air Inlet is blocked

 

 

Check inlet terminal, venturi screen and burner tube for debris. If inlet is clear check blocked inlet flue switch for continuity. 

Inspect hose to switch to ensure it is connected and not cracked or spilt.

“High Limit” 

Outlet temp. exceeded high limit setpoint 

Continuous 

Auto Reset

 

 

Caused when the temperature of the outlet probe exceeds the high limit setpoint. This is an internal “software” limit switch and 

not an actual device. Check that the over temperature is not being caused by improper setup or operation of the boiler.

“MRHL”   

Outlet temp is too high 

Flashing 

HARD

 

 

Caused when the MRHL (a thermostat) contacts in the Outlet probe are open when they should be closed. Fault may be due 

to high outlet temperature, bad switch contacts in the probe, or disconnected wiring. Note: The MRHL can be checked by 

disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connector at the 

end of the probe cable. The value should be approximately  0 ohms when the temperature of the probe is less than 220°F.

“Low Water” 

Water level is too low 

Flashing 

HARD

 

 

Caused by the Low Water Cut Out device not closing its feedback switch contacts when it should. Check water line, switch 

contacts, wiring, LWCO.

“Low Gas” 

Gas pressure is too low 

Flashing 

HARD

 

 

Caused by the Low Gas switch being open when it should be closed. Check gas line, switch contacts, wiring. 

“Powered Accessory” 

Power vent not running 

Flashing 

HARD

 

 

Caused by the Powered Vent device not closing its feedback switch contacts when it should.  Could also be caused by a 

problem with the relay output on the MCB. Check output to powered vent, switch contacts, wiring.

“High Gas Stg*” 

Gas pressure too high 

Flashing 

HARD

 

 

Caused by the High Gas switch being open when it should be closed. Check gas line, switch contacts, wiring.

“Inlet Probe” 

Inlet probe shorted or open 

Flashing 

HARD

 

 

Caused when the thermistor in the probe or the wiring to the probe is shorted or disconnected. Check the probe. Note: The 

thermistor and wiring can be checked by disconnecting the probe from the MCB and reading the resistance across the two 

active pins on the connector at the end of the probe cable. The value should be approximately 10K ohms (value will change 

slightly with changes in temperature).

“Outlet Probe:” 

Outlet probe shorted or open 

Flashing 

HARD

 

 

Caused when the thermistor in the probe or the wiring is shorted or disconnected. Check the probe. Note: the thermistor and 

wiring can be checked by disconnecting the probe from the MCB and reading the   resistance across the two active pins on 

the connector at the end of the probe cable. The value should be approximately 10K ohms (value will change slightly with 

changes in temperature).

“Tank Probe” 

 Tank (Remote) probe shorted or open 

Flashing 

HARD

 

 

Caused when the thermistor in the probe or the wiring is shorted or disconnected. Check the probe. Note: the thermistor and 

wiring can be checked by disconnecting the probe from the MCB and reading the   resistance across the two active pins on 

the connector at the end of the probe cable. The value should be approximately 10K ohms| (value will change slightly with 

changes in temperature).

“Igniter Stg*” 

Igniter current is too low 

Flashing 

HARD 

 

 

Caused by a low current draw problem with the igniter. This may occur if the igniter is old, damaged, or disconnected and 

no longer draws the proper level of current. This condition will affect the ability of the igniterto get hot enough to fire the gas 

properly. Check the igniter and its associated wiring.

“Igniter Pwr Stg*” 

Improper power applied to the igniter circuit 

Flashing 

HARD

 

 

Caused by improper line power being applied to the igniter circuitry. Check line connections. Paying particular attention to 

the earth ground connection. Also check that line voltage does not exceed 132 VAC RMS.

“Igniter Hdwr Stg*” 

Hardware problems with igniter circuit 

Flashing 

HARD

Summary of Contents for VF VB 500

Page 1: ...ilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be...

Page 2: ...known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical know...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...al Power 120v 60hz and 30 amps Models VB VW 500 VB VW 750 VB VW 1000 Dimensions inches mm inches mm inches mm Flue Outlet Diameter 6 152 6 152 6 152 Air Intake Diameter 4 102 4 102 4 102 Water Inlet 2...

Page 5: ...9 42 159 2 1 0 6 32 121 1 8 0 5 110 416 4 3 1 3 12 7 32 121 1 8 0 5 40 22 VB 1000 85 322 3 9 1 2 56 212 2 8 0 9 42 159 2 3 0 7 120 454 4 9 1 5 14 8 42 159 2 3 0 7 40 22 Model No Input Rating Btu hr Ou...

Page 6: ...d Ability 10 Location 10 Panels and Covers 10 Chemical Vapor Corrosion 11 Installtion Clearances 11 Leveling 11 Air Requirements 11 Unconfined Space 11 Confined Space 11 Fresh Air Openings for Confine...

Page 7: ...N EXPOSED TO FLOODING IT MUST BE REPLACED Liquefied Petroleum Gas Models Boilers for propane or liquefied petroleum gas LPG are different from natural gas models A natural gas boiler will not function...

Page 8: ...S is a normally closed pressure switch that opens when the air intake is blocked If the BIS is activated check and clear the intake of any obstructions The blocked flue pressure switch BFS activated w...

Page 9: ...emperature Probe allows a boiler to sense the actual water temperature inside the storage tank or hydronic heating loop The boiler will modulate its firing rate in response to the actual system temper...

Page 10: ...g cartridge or linkage T P relief valve should have a temperature rating of 210 F 99 C a pressure rating not exceeding lowest rated working pressure of any system compo nent and a discharge capacity e...

Page 11: ...sure adequate air supply Unusually Tight Construction In unconfined spaces in buildings infiltration may be adequate to provide air for combustion ventilation and dilution of flue gases However in bui...

Page 12: ...ThroughTwoHorizontalDucts FIGURE 9C The confined space should be provided with two permanent horizontal ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300...

Page 13: ...osure See Figure 9E Each opening should communicate directly with an additional room s of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space Each op...

Page 14: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 3...

Page 15: ...let into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30...

Page 16: ...sing TWT to exhaust flue prod ucts and PVC piping to bring combus tion air to the boiler from the outside see Figures 12 and 12C 4 Vertical Direct Vent using a vertical vent termination to exhaust flu...

Page 17: ...direct vent installations Standard minimum vertical vent lengthis7feet 2 1m plusBoot Tee SeeFigures11 12A 12B and 12C for differences between standard and direct vent installations 3 An AL 29 C Vent V...

Page 18: ...r parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation FIGURE 11 VERTICAL TERMINATION FIGURE 11A HORIZONTAL THROUGH THE WALL TERMIN...

Page 19: ...d carbon monoxide detector with an alarm shall be installed APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA...

Page 20: ...nt terminal NOTES If the exhaust vent terminal is within 10 3 0m of a wall or parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation...

Page 21: ...OR PARAPET ON SIDEWALL VENT INSTALLATION REFER TO FIGURE 9F FOR SPACING SPECIFICATIONS FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS CLEARANCES SUPPORT ETC REFER TO FIGURES 12 AND 12A VERTICAL AIR IN...

Page 22: ...red by the warranty 2 EXPANSION TANK If the system is of the closed type install an expansion tank as shown in Figure 13 The sizing of the expansion tank for a closed system is very important and is d...

Page 23: ...ra tion Pipe joint compounds soldering paste grease on tubing and pipe all tend to contaminate a system Failure to flush contaminants from a system can cause solids to form on the inside of boiler exc...

Page 24: ...a suitable main manual shut off valve must be installed in a location complying with those codes Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or for...

Page 25: ...REQUIRED INSTALL IN PLACE OF THE DRAIN VALVE SHOWN DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTE...

Page 26: ...ES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES SEE TABLE 8 ONE VF MODEL VW HOT WATER SUPPLY BOILER WITH VERTICAL TANK FIGURE 14 INSTALL I...

Page 27: ...AFE USE TEMPERATURE AT FIXTURES IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES SEE TABLE 8 FIGURE 15 INSTALL...

Page 28: ...3 GREEN GROUND 4 2 TANK PROBE OR 2 ENABLE DISABLE Enable disable can also be used with a 24 volt thermostat Do not use tank probe when using thermostat These connections shall be made at the rear of...

Page 29: ...132 000 13 728 000 12 636 000 11 700 000 11 232 000 10 452 000 9 360 000 8 580 000 7 800 000 7 176 000 kW 10 508 7 219 5 848 4 980 4 432 4 021 3 701 3 427 3 290 3 061 2 741 2 513 2 284 2 102 TABLE 6...

Page 30: ...30 Wiring Diagram FIGURE 17 CONNECTION DIAGRAM...

Page 31: ...31...

Page 32: ...32 FIGURE 18 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Page 33: ...desired system pressure Close bypass valve and permit pressure to be established by the pressure reducing valve 2 Vent all high points in system to purge system of air Provisions should be made to per...

Page 34: ...further adjustments on the outlet and bypass valves until the desired inlet and outlet water temperatures are reached MANIFOLD PRESSURE CONNECTIONS Take the manifold pressure refer to Table 1 by remo...

Page 35: ...ure On Yes Off No Switch 8 Modulation On NOTE If the unit powers up with the number of stages selected by dip switches exceeding the number of FCBs the MCB will detect this condition and go into a har...

Page 36: ...36 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Page 37: ...e cap on the gas regulator using a slotted screwdriver This will expose the offset adjustment screw Using a TORX T40 or a 5mm hex wrench carefully adjust the low fire gas setting to achieve the CO2 le...

Page 38: ...is missing or shorted the flame will not be detected OUTPUTS FROM MCB Relay Contact Output Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an audio device...

Page 39: ...splayed 4 The system then compares the temperature read from the controlling probe inlet or tank to the setpoint temperature If the temperature is less than the operating setpoint minus the differenti...

Page 40: ...The MCB has 5 possible states and the FCB have 9 The normal MCB states sequence is to move from Idle to Pre Circulate when a call for heat is initiated Once heat has been satisfied or the Thermostat i...

Page 41: ...ch error has occurred The system waits in this state until the MCB sends a command to clear the error and the system returns to the idle state Cold Purge State Cold purge occurs when the MCB micro com...

Page 42: ...fo Screen Displays the following information Elapsedhoursofoperation Totaltimesystemhasbeenpoweredup Number of running minutes Number of minutes system has been in the run mode kBtu rating of the boil...

Page 43: ...es that a fault has been detected and the system has stopped running It is on continuously for soft faults and flashes for hard faults The Yellow LED indicates that the boiler is in a ready mode waiti...

Page 44: ...ote The MRHL can be checked by disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connector at the end of the probe cable The value should be appr...

Page 45: ...tion of the servo pressure regulator Replace the valve and add a gas filter in front of the new valve preventative maintenance This is a pre mix burner system The flame is not supposed to be directly...

Page 46: ...er adapter by first removing the four 4 bolts and subsequently the blower gas kets The blower should be free to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber...

Page 47: ...ystemssolidsexist Asthewaterisheated these tendtodropoutdepositingasscaleorlime Thisscalemustberemoved before the heat exchanger tubes become blocked Deliming The amount of calcium carbonate lime rele...

Page 48: ...48 notes...

Page 49: ...49 notes...

Page 50: ...50 notes...

Page 51: ...is boiler under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts s...

Page 52: ...52 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 433 2545 www hotwater com E Mail parts hotwater com...

Reviews: