background image

42

Use the following procedure to change the automatically resettable 

High Limit Setpoint:
1.  Press the MENU key.

2.  Scroll the “>” with the DOWN key next to USER SETTING SCREEN.

3.  Press the SELECT key.

4.  Scroll the “>” with the DOWN key until it is pointing to HIGH 

LIMIT SETPOINT.

5.  Press the SELECT KEY.
6.  Use the UP and DOWN key to select the value you wish to 

enter.

7.  Press the SELECT key to accept and store the new value.

•  High Limit Differential:

  The outlet temperature must be below the automatic High Limit 

setpoint minus the High Limit Differential setpoint before  a call 

for heat can be generated.

HIGH LIMIT DIFFERENTIAL SETPOINT ADJUSTMENT 

PROCEDURE

The High Limit Differential Setpoint has a range of 1°F to 50°F for 

all models. Use the following procedure to change the High Limit 

Differential Setpoint:
1.  Press the MENU key.

2.  Scroll  the  “>”  with  the  down  key  next  to  USER  SETTING 

SCREEN.

3.  Press the SELECT key.

4.  Scroll the “>” with the DOWN key until it is pointing to HIGH 

LIMIT DIFFERENTIAL SETPOINT.

5.  Press the SELECT key.
6.  Use the UP or DOWN key to select the value you wish to enter.
7.  Press the SELECT key to accept and store the new value.

•  Operating  Differential  Setpoints:

  Each of the two stages has an independent Operating 

Differential setpoint.

• 

Temperature Units:

  Temperature can be displayed in either °F or °C units.

• 

Post Circulate Delay Time:

  The time circulation pump will stay on after the burner 

is turned off. The time in seconds is adjustable with the 

following values: 45, 90, 180 or continuous. If the continuous 

value is selected the pump will remain on at all times and 

the post circulate state time will be set at 45 seconds.

• 

Network Address:

  This is a unique number assigned to this boiler to differentiate 

it from other boilers or water heater on the same A. O. 

Smith proprietary network. A valid Network Address can be 

any number from 1 to 31. It is set by default to zero, which 

is an invalid address. The boiler will not communicate until 

it is changed to a valid and unique number. This prevents 

two units from trying to respond to the same request from 

the PC or supervisory network device.

• 

Configuration Settings Screen:

  Displays the status of the dipswitches installed on all 

boards as described earlier.

• 

Log & System Info Screen:

  Displays the following information:

  Elapsed hours of operation (Total time system has been powered up)
  Number of running minutes (Number of minutes system has 

been in the run mode)

  kBtu rating of the boiler (0 to 5750kBtu in 10kBtu increments)

  The software revision level of the MCB.

  Current Error Screen:

  Displays the last error that the system has detected plus a time 

stamp  of  when  the  error  occurred.  (The  time  stamp  is  based 

on the elapsed hours value at the time the error occurred.  It 

is displayed in hours and minutes. This error remain displayed 

as long as it is still valid. When cleared it is moved to the Error 

History Screen. The system will automatically jump to this screen 

when an error is detected. It will also go to this screen upon 

power-up if an error was still valid when power was turned off.

 

NOTE: Errors are cleared from this screen by pressing 

the “select” key.

•  Error  History  Screen:

  This  screen  displays  a  list  of  the  last  9  errors  (with  time 

stamps)  that  have  occurred.    The  last  error  to  occur 

is displayed first. If a new error occurs this screen is 

presented to display the error.

•  Reload  Defaults  Screen:

  From this screen the user can restore the factory default 

values for screen adjustable configurations by pressing 

the Select key. The values restored are as follows:

  VW Models

  Oper  Setpnt  (Operating  Setpoint)  -  145°  F  (63°  C)
  Hi  Limit  (High  Limit  Setpoint)  =  210°  F  (99°  C)
  Hi  Limit  Dif  (High  Limit  Differential)  =  20°  F  (11°  C)

  VB Models

  Oper Setpnt (Operating Setpoint) = 190° F (88° C)
  Hi Limit (High Limit Setpoint) = 230° F (110° C)
  Hi Limit Dif (High Limit Differential) = 20° F (11° C)

  Both Models

  Tempert Units (Temperature Units) = F
  Post Cir Secs (Post Circulation pump delay = 45 seconds
  Network Address (Network Address) =  (none)

UIM Touch Switches

Below the LCD display are five touch switches or keys, that the 

operator uses to operate the system.

•  Menu Key:

  Pressing this key activates the menu screen where the other 

screens can be accessed.

•  Select Key:

  This key performs several functions.  Screens can be selected 

from the menu screen by pressing this key when the “>” appears 

next to the screen desired.

  On the User Settings screen items that appear next to a “>” 

symbol can be selected with this key.  If a setpoint configuration 

item is selected, the “>” will then flash slowly to indicate that 

the item has been selected.  The Up and Down keys are then 

used to change its value.

  From the Current Error Screen this key is used to reset the 

system from an error:

Summary of Contents for VF VB 500

Page 1: ...ilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be...

Page 2: ...known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical know...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...al Power 120v 60hz and 30 amps Models VB VW 500 VB VW 750 VB VW 1000 Dimensions inches mm inches mm inches mm Flue Outlet Diameter 6 152 6 152 6 152 Air Intake Diameter 4 102 4 102 4 102 Water Inlet 2...

Page 5: ...9 42 159 2 1 0 6 32 121 1 8 0 5 110 416 4 3 1 3 12 7 32 121 1 8 0 5 40 22 VB 1000 85 322 3 9 1 2 56 212 2 8 0 9 42 159 2 3 0 7 120 454 4 9 1 5 14 8 42 159 2 3 0 7 40 22 Model No Input Rating Btu hr Ou...

Page 6: ...d Ability 10 Location 10 Panels and Covers 10 Chemical Vapor Corrosion 11 Installtion Clearances 11 Leveling 11 Air Requirements 11 Unconfined Space 11 Confined Space 11 Fresh Air Openings for Confine...

Page 7: ...N EXPOSED TO FLOODING IT MUST BE REPLACED Liquefied Petroleum Gas Models Boilers for propane or liquefied petroleum gas LPG are different from natural gas models A natural gas boiler will not function...

Page 8: ...S is a normally closed pressure switch that opens when the air intake is blocked If the BIS is activated check and clear the intake of any obstructions The blocked flue pressure switch BFS activated w...

Page 9: ...emperature Probe allows a boiler to sense the actual water temperature inside the storage tank or hydronic heating loop The boiler will modulate its firing rate in response to the actual system temper...

Page 10: ...g cartridge or linkage T P relief valve should have a temperature rating of 210 F 99 C a pressure rating not exceeding lowest rated working pressure of any system compo nent and a discharge capacity e...

Page 11: ...sure adequate air supply Unusually Tight Construction In unconfined spaces in buildings infiltration may be adequate to provide air for combustion ventilation and dilution of flue gases However in bui...

Page 12: ...ThroughTwoHorizontalDucts FIGURE 9C The confined space should be provided with two permanent horizontal ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300...

Page 13: ...osure See Figure 9E Each opening should communicate directly with an additional room s of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space Each op...

Page 14: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 3...

Page 15: ...let into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30...

Page 16: ...sing TWT to exhaust flue prod ucts and PVC piping to bring combus tion air to the boiler from the outside see Figures 12 and 12C 4 Vertical Direct Vent using a vertical vent termination to exhaust flu...

Page 17: ...direct vent installations Standard minimum vertical vent lengthis7feet 2 1m plusBoot Tee SeeFigures11 12A 12B and 12C for differences between standard and direct vent installations 3 An AL 29 C Vent V...

Page 18: ...r parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation FIGURE 11 VERTICAL TERMINATION FIGURE 11A HORIZONTAL THROUGH THE WALL TERMIN...

Page 19: ...d carbon monoxide detector with an alarm shall be installed APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA...

Page 20: ...nt terminal NOTES If the exhaust vent terminal is within 10 3 0m of a wall or parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation...

Page 21: ...OR PARAPET ON SIDEWALL VENT INSTALLATION REFER TO FIGURE 9F FOR SPACING SPECIFICATIONS FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS CLEARANCES SUPPORT ETC REFER TO FIGURES 12 AND 12A VERTICAL AIR IN...

Page 22: ...red by the warranty 2 EXPANSION TANK If the system is of the closed type install an expansion tank as shown in Figure 13 The sizing of the expansion tank for a closed system is very important and is d...

Page 23: ...ra tion Pipe joint compounds soldering paste grease on tubing and pipe all tend to contaminate a system Failure to flush contaminants from a system can cause solids to form on the inside of boiler exc...

Page 24: ...a suitable main manual shut off valve must be installed in a location complying with those codes Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or for...

Page 25: ...REQUIRED INSTALL IN PLACE OF THE DRAIN VALVE SHOWN DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTE...

Page 26: ...ES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES SEE TABLE 8 ONE VF MODEL VW HOT WATER SUPPLY BOILER WITH VERTICAL TANK FIGURE 14 INSTALL I...

Page 27: ...AFE USE TEMPERATURE AT FIXTURES IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES SEE TABLE 8 FIGURE 15 INSTALL...

Page 28: ...3 GREEN GROUND 4 2 TANK PROBE OR 2 ENABLE DISABLE Enable disable can also be used with a 24 volt thermostat Do not use tank probe when using thermostat These connections shall be made at the rear of...

Page 29: ...132 000 13 728 000 12 636 000 11 700 000 11 232 000 10 452 000 9 360 000 8 580 000 7 800 000 7 176 000 kW 10 508 7 219 5 848 4 980 4 432 4 021 3 701 3 427 3 290 3 061 2 741 2 513 2 284 2 102 TABLE 6...

Page 30: ...30 Wiring Diagram FIGURE 17 CONNECTION DIAGRAM...

Page 31: ...31...

Page 32: ...32 FIGURE 18 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Page 33: ...desired system pressure Close bypass valve and permit pressure to be established by the pressure reducing valve 2 Vent all high points in system to purge system of air Provisions should be made to per...

Page 34: ...further adjustments on the outlet and bypass valves until the desired inlet and outlet water temperatures are reached MANIFOLD PRESSURE CONNECTIONS Take the manifold pressure refer to Table 1 by remo...

Page 35: ...ure On Yes Off No Switch 8 Modulation On NOTE If the unit powers up with the number of stages selected by dip switches exceeding the number of FCBs the MCB will detect this condition and go into a har...

Page 36: ...36 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Page 37: ...e cap on the gas regulator using a slotted screwdriver This will expose the offset adjustment screw Using a TORX T40 or a 5mm hex wrench carefully adjust the low fire gas setting to achieve the CO2 le...

Page 38: ...is missing or shorted the flame will not be detected OUTPUTS FROM MCB Relay Contact Output Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an audio device...

Page 39: ...splayed 4 The system then compares the temperature read from the controlling probe inlet or tank to the setpoint temperature If the temperature is less than the operating setpoint minus the differenti...

Page 40: ...The MCB has 5 possible states and the FCB have 9 The normal MCB states sequence is to move from Idle to Pre Circulate when a call for heat is initiated Once heat has been satisfied or the Thermostat i...

Page 41: ...ch error has occurred The system waits in this state until the MCB sends a command to clear the error and the system returns to the idle state Cold Purge State Cold purge occurs when the MCB micro com...

Page 42: ...fo Screen Displays the following information Elapsedhoursofoperation Totaltimesystemhasbeenpoweredup Number of running minutes Number of minutes system has been in the run mode kBtu rating of the boil...

Page 43: ...es that a fault has been detected and the system has stopped running It is on continuously for soft faults and flashes for hard faults The Yellow LED indicates that the boiler is in a ready mode waiti...

Page 44: ...ote The MRHL can be checked by disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connector at the end of the probe cable The value should be appr...

Page 45: ...tion of the servo pressure regulator Replace the valve and add a gas filter in front of the new valve preventative maintenance This is a pre mix burner system The flame is not supposed to be directly...

Page 46: ...er adapter by first removing the four 4 bolts and subsequently the blower gas kets The blower should be free to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber...

Page 47: ...ystemssolidsexist Asthewaterisheated these tendtodropoutdepositingasscaleorlime Thisscalemustberemoved before the heat exchanger tubes become blocked Deliming The amount of calcium carbonate lime rele...

Page 48: ...48 notes...

Page 49: ...49 notes...

Page 50: ...50 notes...

Page 51: ...is boiler under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts s...

Page 52: ...52 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 433 2545 www hotwater com E Mail parts hotwater com...

Reviews: