8.3 Troubleshooting table for displayed errors
Indication
Cause
Measure
Remark
C05 (blocking error)
Error message from the
(Theta dual service/solar)
controller.
Incorrect reference voltage
from the AD-converter.
EEPROM error
1. Reset controller.
2. Check that the frequency of the power supply is compliant
with 50 Hz ± 1 Hz. If not, contact your installation engineer
3. If the frequency is correct but the error persists, replace the
dual service/solar heating controller.
-
If the error persists, consult you installation
engineer.
-
To replace the necessary parts, you must contact
your installation engineer.
F18 (blocking error)
Communication error.
No supply voltage present on
(dual service/solar) control.
Check whether there is power to the controller. The measured
voltage must be 230 V
AC
(-15%, +10%).
-
See electrical diagram (see Installation- User- and
Service manual of the water heater, 17
“Appen-
dices
” or 11 “Appendices” of this manual).
-
If the error persists, consult you installation
engineer.
-
To replace the necessary parts, you must contact
your installation engineer.
No communication cable
(correctly) connected or
damaged.
1. Check whether there is a (communication) cable between
the controller of the water heater and the controller of the
dual service module/solar heating system.
2. In case of no cable, a (communication) cable must be
connected.
3. In case of damage, the (communication) cable must be
replaced.
Short circuit Q/T-sensor.
Check whether the Q/T-sensor is connected correctly to the
controller.
1. Disconnect the Q/T-sensor.
2. In case of no cable, a cable must be connected.
3. In case of damage, the cable must be replaced.
F20 (blocking error)
(1/2)
Temperature of heating
system is to high.
DHW-pump not functioning.
1. Check whether the (DHW) pump is correctly (electrical)
connected to the controller.
2. Check whether the (DHW) pump is correctly connected
hydraulically.
-
See electrical diagram (11
“Appendices”).
-
To replace the necessary parts, you must contact
your installation engineer.
Heating pump not functioning. 1. Check whether the (heating) pump is correctly (electrical)
connected to the controller.
2. Check whether the (heating) pump is correctly connected
hydraulically.
Table continues on next page.
Summary of Contents for Theta T Series
Page 4: ...Theta Dual Service Module 2 0 4...
Page 6: ...Installatie Gebruikers en Service handleiding 6...
Page 16: ...Installatie Gebruikers en Service handleiding 16...
Page 28: ...Installatie Gebruikers en Service handleiding 28...
Page 30: ...Installatie Gebruikers en Service handleiding 30...
Page 32: ...Installatie Gebruikers en Service handleiding 32...
Page 38: ...Installatie Gebruikers en Service handleiding 38...
Page 44: ...Installatie Gebruikers en Service handleiding 44...
Page 46: ...Installatie Gebruikers en Service handleiding 46...
Page 58: ...Installation User and Service Manual 58...
Page 68: ...Installation User and Service Manual 68...
Page 80: ...Installation User and Service Manual 80...
Page 82: ...Installation User and Service Manual 82...
Page 84: ...Installation User and Service Manual 84...
Page 90: ...Installation User and Service Manual 90...
Page 96: ...Installation User and Service Manual 96...
Page 98: ...Installation User and Service Manual 98...
Page 108: ...Installation User and Service Manual 108 11 5 Configuration 3 way mixing valve IMD 1124 R0 0...
Page 109: ...Installation User and Service Manual 109 0311 686 R0 0 NL EN...