TERMINAL STRIP CONNECTIONS:
Earth
N
Neutral
L
Live input of controller
L
1
Live input for 3-way mixing valve (warm water supply of water heater)
L
2
Live input for 3-way mixing valve (return water of plate heat exchanger)
L
3
Live input for solar heating system modulating pump (PWM)
L
5
Live input for heating pump
L
6
Live input for DHW pump
L
7
Live output of Switched Live room thermostat
PWM + PWM+ signal of solar heating system pump (modulating)
PWM - PWM- signal of solar heating system pump (modulating)
COMPONENTENS:
AA
Controller of solar heating system (SHM 3.0)
BB
3-way mixing valve (230 V
AC
)
CC
Heating pump (230 V
AC
)
DD
DHW pump (230 V
AC
)
EE
Temperature sensor (S
5
- heating system)
FF
Room thermostat (24 V
AC
- ON/OFF)
GG
Room thermostat (230 V
AC
- Switched Live)
HH
Communication between the water heater controller and the solar heating
system controller
JJ
[VAC]
Solar heating system pump (modulating) (230 V
AC
)
JJ
[PWM]
Solar heating system pump (modulating) (PWM-signal)
KK
Temperature sensor (S
1
-solar collector) (20
kΩ NTC)
LL
Temperature sensor (S
2
- tank)
(12 kΩ NTC)
MM
Combined Q/T sensor incl. temperature sensor
(S
4
- solar collector return)
(12 kΩ NTC)
NN
Temperature sensor (S
3
- top of storage tank)
(12 kΩ NTC)
K
Double-pole isolator
CONTROLLER CONNECTIONS:
J3
Connection of room thermostat (ON/OFF)
J12
Connection combined Q/T sensor (1-2-3-4)
J13
Connection of temperature sensor S
5
(1-3) and temperature sensor S
1
(2-4)
J14
Connection of temperature sensor S
2
(2-4) and temperature sensor S
3
(1-3)
J16
Connection of BUS-link communication
J18
Connection of PWM-signal solar heating system pump
F2
Fuse (T 3,15 A - 250 V)
Summary of Contents for Theta T Series
Page 4: ...Theta Dual Service Module 2 0 4...
Page 6: ...Installatie Gebruikers en Service handleiding 6...
Page 16: ...Installatie Gebruikers en Service handleiding 16...
Page 28: ...Installatie Gebruikers en Service handleiding 28...
Page 30: ...Installatie Gebruikers en Service handleiding 30...
Page 32: ...Installatie Gebruikers en Service handleiding 32...
Page 38: ...Installatie Gebruikers en Service handleiding 38...
Page 44: ...Installatie Gebruikers en Service handleiding 44...
Page 46: ...Installatie Gebruikers en Service handleiding 46...
Page 58: ...Installation User and Service Manual 58...
Page 68: ...Installation User and Service Manual 68...
Page 80: ...Installation User and Service Manual 80...
Page 82: ...Installation User and Service Manual 82...
Page 84: ...Installation User and Service Manual 84...
Page 90: ...Installation User and Service Manual 90...
Page 96: ...Installation User and Service Manual 96...
Page 98: ...Installation User and Service Manual 98...
Page 108: ...Installation User and Service Manual 108 11 5 Configuration 3 way mixing valve IMD 1124 R0 0...
Page 109: ...Installation User and Service Manual 109 0311 686 R0 0 NL EN...