T-D2-IN / T-D2-OS Service Manual
Ver. 1.00
67
CONFIDENTIAL
To sum it up in a chart:
Case 5 minutes have elapsed
since prior operation?
Inlet
thermistor
temperature
Output thermistor
temperature
Will
automatic
firing be activated?
1
No
Any
Any
NO
2
Yes
Above 37°F
Any
NO
3
Yes
Any
Above 50°F
NO
4
Yes
37°F and below
50°F and below
YES
5
Yes
Any
37°F and below
YES
T-D2-OS installation:
After 25 minutes have elapsed since the T-D2-IN or T-D2-OS’s previous firing operation, the computer
will continually check the temperatures of the inlet and output thermistors. The automatic firing
system will not activate at all unless these 25 minutes have elapsed.
When the computer checks for these temperatures, the freeze protection firing system will activate if:
T
in
<
37°F and T
out
<
50°F OR T
out
<
37°F
where T
in
is the temperature of inlet thermistor and T
out
is the temperature of the output thermistor.
To sum it up in a chart:
Case 25 minutes have elapsed
since prior operation?
Inlet
thermistor
temperature
Output
thermistor
temperature
Will
automatic
firing be activated?
1
No
Any
Any
NO
2
Yes
Above 37°F
Any
NO
3
Yes
Any
Above 50°F
NO
4
Yes
37°F and below
50°F and below
YES
5
Yes
Any
37°F and below
YES