4
HEAT EXCHANGER PERFORMANCE
Heat exchanger temperature differentials (Delta T) are shown
for reference only. Actual values can be calculated by:
Delta T = Btuh/500/gpm
This will determine the difference between the heat exchanger’s
inlet and outlet water temperatures (Delta T).