background image

Residential Gas Water Heater Use and Care Guide • 27

TROUBLESHOOTING

Plumbing Leak.

 Even a small leak 

in the hot water side of the home’s 

plumbing system can make it appear 

that the water heater is producing 

little to no hot water. In this case, the 

burner will be on all or almost all the 

time, yet you will have very little hot 

water. Locate and repair the leak.

Sediment or Lime in Tank.

 With an 

existing water heater, if you have 

some hot water but not as much 

as you are used to, there may be a 

build up of sediment or lime on the 

bottom of the tank. Sediment or lime 

buildup can reduce the efficiency of 

your water heater. Heavy deposits 

can damage the water heater. See 

the Maintenance section for steps 

on draining and flushing the water 

heater.

Temperature Too High

Adjust the gas control valve/

thermostat on the water heater 

to a lower setting. Install or adjust 

Thermostatic Mixing Valves at 

each point-of-use (see the valve 

manufacturer’s instructions).

Low Water Pressure

Check both the cold and hot water 

at a sink to determine if the lower 

pressure is only on the hot water side. 

If both hot and cold faucets have low 

pressure, call your local water utility. 

If the low pressure is only on the hot 

water side, the primary causes are:

• Melted heat traps or dip tube. Sol-

dering copper pipes while they are 

connected to the water heater can 

melt the heat traps inside the hot 

and cold water connections or the 

dip tube (cold water side). Melted 

heat traps or a melted dip tube can 

restrict the flow of hot water. If that 

is the case, replace the heat traps or 

dip tube.

• 

Partially closed supply valve. Open 

the water heater’s supply valve fully.

Drips from T&P Relief 

Valve Discharge Pipe

A small amount of water dripping 

from the Temperature and Pressure 

(T&P) Relief Valve usually means the 

home’s water pressure is too high 

and/or you need a Thermal Expansion 

Tank. See Step 1 in the Installation 

section of this manual for more 

information.

A large amount of hot water coming 

from the T&P discharge pipe may be 

due to the tank overheating. If the 

T&P Relief Valve is discharging large 

amounts of very hot water, turn the 

gas supply valve off and call a qualified 

person.

 WARNING! Do not cap or plug 

the T&P Relief Valve or discharge 

pipe, and do not operate the water 

heater without a functioning T&P 

Relief Valve — this could cause an 

explosion.

Water Pressure Too High.

 High 

water pressure can cause the T&P 

Relief Valve to drip. Install a Pressure 

Reducing Valve (PRV) on the main cold 

water supply line. Adjust the PRV to 

between 50 and 60 psi.

Thermal Expansion Tank.

 Install a 

Thermal Expansion Tank. If a Thermal 

Expansion Tank is already installed 

and the T&P Relief Valve discharge 

pipe drips, the home’s water pressure 

may be too high or the Thermal 

Expansion Tank may be defective. 

Refer to the instructions that came 

with the Thermal Expansion Tank for 

more information.

Debris.

 In rare cases, debris can stick 

inside the T&P Relief Valve preventing 

the valve from seating fully. In that 

case, the T&P Relief Valve discharge 

pipe will drip. You may be able to clear 

debris from the T&P Relief Valve by 

manually operating the valve, allowing 

small quantities of water to flush out 

the debris. Refer to the T&P Relief 

Valve Maintenance section of this 

manual.

 WARNING! When manually 

operating the Temperature Pressure 

Relief Valve, make sure that no one 

is in front of or around the discharge 

outlet. The water may be extremely 

hot and could cause severe burns. 

Also ensure that the water discharge 

will not cause property damage.

If the water pressure is between 50 

and 60 psi, a Thermal Expansion Tank 

is installed and properly pressurized, 

and the valve has been cleared of any 

debris, and it still drips, the valve may 

be broken — have a qualified person 

replace the T&P Relief Valve.

Water Odor

Harmless bacteria normally present 

in tap water can multiply in water 

heaters and give off a “rotten egg” 

smell. Although eliminating the 

bacteria that causes “smelly water” 

is the only sure treatment, in some 

cases, the standard anode rod that 

came with your water heater can be 

replaced with a special zinc anode rod 

which may help reduce or eliminate 

the odor. Contact a qualified person.

NOTICE:

 To protect the tank, an anode 

rod must be installed in the water 

heater at all times or the warranty is 

void.

In cases where the “rotten egg” smell 

is very strong, you could increase the 

tank temperature to 140°F in order 

to reduce the bacterial growth in the 

tank.

 WARNING! Because higher 

temperatures increase the risk of 

scalding, if you set the thermostat(s) 

higher than 120°F, Thermostatic 

Mixing Valves at each point-of-use 

are particularly important.

TR

OUBLE

SHOO

TING

Summary of Contents for G6-PVT4050NV

Page 1: ...on operation or service can damage the water heater your house and other property and present risks including fire scalding electric shock and explosion causing serious injury or death Residential Gas...

Page 2: ...Inlet Water Shut off Valve Inlet Water Shut off Valve Temperature and Pressure Relief Valve Combo Heating System Supply Outlet Optional Discharge Pipe Combo Heating System Supply Return Inlet Optiona...

Page 3: ...a fuel gas and carbon monoxide detector This product is certified to comply with a maximum weighted average of 0 25 lead content as required in some areas DANGER indicates a hazardous situation that i...

Page 4: ...lves tem perature limiting valves at each point of use These valves automati cally mix hot and cold water to limit the temperature at the tap Mixing valves are available at your local plumbing supplie...

Page 5: ...ident will show a discoloration on the flame arrestor and require replacement of the entire water heater Improper installation or an inadequate air supply can also cause the FVIR system to disable the...

Page 6: ...burning of fuels such as coal wood charcoal oil kerosene propane and natural gas Breathing excessive and abnormal amounts of carbon monoxide can cause carbon monoxide poisoning resulting in serious i...

Page 7: ...er pipes you may purchase a Gas Water Heater Hook Up Kit available at your local plumbing supplier with compres sion fittings that do not require soldering This kit includes two 12 flex water lines an...

Page 8: ...gated end of the vent piping connects to the top of the water heater and the opposite end connects to the vent termination hood which will be mounted on the exterior wall see Figure 4 Figure 4 shows t...

Page 9: ...t Cut a clearance hole approximately 7 in diameter through the exterior wall for the vent assembly The recommended height is 64 for 40 gallon models or 73 for 50 gallon models as measured from the hol...

Page 10: ...en secure the vent terminal to the exterior wall with 4 screw anchors included appropriate for the type of wall construction Caulk the junction of the vent terminal base plate and the exterior wall wi...

Page 11: ...and secure with the gear clamp Pull the free end of the corrugated pipe past the gear clamp and secure with one sheet metal screw see Figure 13 Smooth Easy Curve Apply silicone to Airbox before attac...

Page 12: ...to determine if your new water heater can be retrofitted to an existing vent termination hood Vent Termination Hood Application A 11 13 16 7 Figure 19 American Vent Termination Hood A A current Ameri...

Page 13: ...Piping 1 Install a readily accessible manual shut off valve in the gas supply line as recommended by the local utility Know the location of this valve and how to turn off the gas to this unit 2 Instal...

Page 14: ...t outlet connections for use with space heating applications If this water heater is to be used to supply both space heating and domestic potable drinking water the instructions listed below must be f...

Page 15: ...ming cold water supply line and adjust the water pressure control to between 50 and 60 psi If your home does not have a Pressure Reducing Valve install a PRV on the home s main water supply line and s...

Page 16: ...l plumbing supplier under the water heater to catch conden sation or leaks from the piping connections or tank Most codes require and we recommend install ing the water heater in a metal drain pan tha...

Page 17: ...lding codes NOTICE The state of California requires bracing anchoring or strapping the water heater to avoid its moving during an earthquake Contact local utilities for code requirements in your area...

Page 18: ...ischarge pipe but do not reuse the old T P Relief Valve A new T P Relief Valve comes with your new water heater Figure 34 Removing the T P Relief Valve discharge pipe 10 Allow the vent pipe and draft...

Page 19: ...tions or tank The drain pan must be at least two inches wider than the diameter of the water heater Install the drain pan so the water level is limited to a maximum depth of 1 4 Verify the water heate...

Page 20: ...Pressure Relief Valve Discharge Pipe Do not place any valve or other re striction between the tank and T P Relief Valve Do not cap block plug or insert any valve between the T P Relief Valve and the e...

Page 21: ...in your home Most homes use copper water pipes but some use CPVC or cross linked polyethylene PEX Use fittings appropriate for the type of pipe in your home Do not use iron or PVC pipe they are not su...

Page 22: ...Install Vent Pipe 1 Install the new vent pipe on top of the water heater Do not reuse the vent pipe from the old water heater but rather use the new one that came with your new water heater Follow Ven...

Page 23: ...stricter plate installed on heater flue outlet as applicable Inside pipe 3 and outside pipe 6 securely fastened to water heater with silicone and gear clamps Not obstructed in any way Vent Termination...

Page 24: ...utes 6 Repeat lighting steps 2 through 5 at least two additional times or until the Status Light starts flashing once every three seconds Wait 10 minutes between lighting attempts 7 A solid Status Lig...

Page 25: ...heat from sources such as solar collectors ambient air and the pilot light can result in temperatures higher than the thermostat set point WARNING Higher temperatures increase the risk of scalding but...

Page 26: ...wer control check other faucets in the house for hot water Water heater s capacity too small or usage too high Reversed plumbing connections or melted dip tube usually found soon after new installatio...

Page 27: ...harge pipe and do not operate the water heater without a functioning T P Relief Valve this could cause an explosion Water Pressure Too High High water pressure can cause the T P Relief Valve to drip I...

Page 28: ...to relight Pilot by following the lighting instructions on the water heater s label NOTE This gas control valve thermostat has built in circuitry that requires waiting 10 minutes between lighting att...

Page 29: ...ermostat knob is set to OFF Wait one minute Remove the outer door Look through the sight glass for a pilot flame If a pilot flame is observed with the gas control valve thermostat knob set to the OFF...

Page 30: ...e hose in a drain outside or in buckets Note that sediment in the bottom of the tank may clog the valve and prevent it from draining If you cannot get the tank to drain contact a qualified person 5 Tu...

Page 31: ...ove any flammable corrosive or combustible materials near the water heater If you lack the necessary skills required to properly perform this visual inspection or if the burner needs to be cleaned get...

Page 32: ...let and use it to turn the gas control valve thermostat counterclockwise Do not use pipe wrench or equivalent to grip body Damage may result causing leaks Do not insert any sharp objects into the inle...

Page 33: ...mbly behind outer door 13 Floor Drain 14 Metal Drain Pan 15 Flexible Manifold Tube 16 Sediment Trap 17 Ground Joint Union 18 Manual Gas Shut off Valve 19 Gas Supply 20 Baffle Assembly 21 Rating Plate...

Page 34: ...34 Residential Gas Water Heater Use and Care Guide 37 33 35 36 34 30 38 32 31 39 REPAIR PARTS REPAIR PARTS...

Page 35: ...Residential Gas Water Heater Use and Care Guide 35 NOTES NOTES...

Page 36: ...Copyright 2023 All Rights Reserved...

Reviews: