background image

19

oPErAtIon

GEnErAL

Refer to the Features and Components section of this manual 

(pages 7 & 8) for the location of components mentioned in the 

instructions that follow.
NEVER turn on power to the water heater without being certain the 

water heater is filled with water and a temperature and pressure 

relief valve is installed in the relief valve opening.

do not tEst ELECtrICAL systEM BEforE hEAtEr Is 

fILLEd wIth wAtEr. foLLow fILLInG And stArt-uP 

InstruCtIons In oPErAtIon sECtIon.

fILLInG thE wAtEr hEAtEr

1.  Turn off the electrical disconnect switch.
2.  Close the water heater drain valve.
3.  Open a nearby hot water faucet to permit the air in the system 

to escape.

4.  Fully open the cold water inlet pipe valve allowing the heater and 

piping to be filled.

5.  Close the hot water faucet as water starts to flow. The heater is 

now ready for STARTUP and TEMPERATURE REGULATION.

InItIAL stArt uP

The following checks should be made by the installer when the heater 

is placed into operation for the first time.
1.  Turn off the electrical disconnect switch.
2.  Open the front panel, check all water and electrical connections 

for tightness. Also check connections on top and side of heater. 

Repair  water  leaks  and  tighten  electrical  connections  as 

necessary.

3.  Depress the red manual reset button on each Thermostat/ECO 

combination control (Surface Mount Control Models only).

4.  Turn on the electrical disconnect switch.
5.  Observe the operation of the electrical components during the first 

heating cycle. Use care as the electrical circuits are energized.

6.  Close the front panel.
Temperature control and contactor operation should be checked 

 

by  allowing  heater  to  come  up  to  temperature  and  shut  off 

automatically. 

use care as the electrical circuits are energized.

drAInInG thE wAtEr hEAtEr

It  is  recommended  that  the  water  heater  storage  tank  be 

drained  and  flushed  every  6  months  to  reduce  sediment 

buildup. The water heater should be drained if being shut down 

during freezing temperatures. See Features And Components 

in this manual for the location of the water heater components 

described below.

Burn harzard.

Hot water discharge.

Keep  hands   clear  of  drain

valve  discharge.

To drAIN ThE wATEr hEATEr STorAGE TANk:

1.  Turn  off  the  electrical  supply  to  the  water  heater  at  the 

breaker or disconnect switch.

2.  Ensure the cold water inlet valve is open.
3.  Open a nearby hot water faucet and let the water run until 

the water is no longer hot.

4.  Close the cold water inlet valve to the water heater.
5.  Connect a hose to the water heater drain valve and terminate 

it to an adequate drain.

6.  Open the water heater drain valve and allow all the water to 

drain from the storage tank.

7.  Close  the  water  heater  drain  valve  when  all  water  in  the 

storage tank has drained.

8.  Close the hot water faucet opened in Step 3.
9.  If the water heater is going to be shut down for an extended 

period, the drain valve should be left open.

Summary of Contents for DRE-52 Series

Page 1: ...e reference COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS DRE 52 80 120 SERIES 100 DVE 52 80 120 SERIES...

Page 2: ...testing or replacement of gas piping or b the connection installation testing repair or servicing of appliances and equipment that is experienced in such work that is familiar with all precautions req...

Page 3: ...y may also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must...

Page 4: ...sant Valley Road Cleveland OH 44131 3 If after reading this manual you have any questions or do not understand any portion of the instructions call the toll free number listed on the back cover of thi...

Page 5: ...221 184 158 138 123 111 101 92 85 79 30 102 390 410 307 246 205 176 154 137 123 112 102 95 88 36 122 868 492 369 295 246 211 184 164 148 134 123 113 105 40 5 138 226 554 418 3332 277 237 208 1185 166...

Page 6: ...tional Sanitation Foundation NSF 5 requirements LISTED 22U1 No OF WATTS PHASE VOLTS AC ELEMENTS EACH RATED MEASURED WATTS COMMERCIAL STORAGE TANK WATER HEATER MODEL NUMBER SERIAL NUMBER ITEM ID PART N...

Page 7: ...7 FEATURES AND COMPONENTS ELECTRONIC CONTROL MODELS Figure 2...

Page 8: ...8 FEATURES AND COMPONENTS SURFACE MOUNT CONTROL MODELS Figure 3...

Page 9: ...tank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure Close to the point of major hot water usage and the power supply Hot water piping a...

Page 10: ...hysically developmentally disabled If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a maximum water temperature at the hot water...

Page 11: ...the building Shall not have any valve or other obstruction between the relief valve and the drain The temperature pressure relief valve must be manually operated at least once a year Caution should be...

Page 12: ...protection and disconnect switch The water heater should be grounded in accordance with national and local codes Voltage applied to the heater should not vary more than 5 to 10 of the model and rating...

Page 13: ...element current sensors for monitoring the power circuits Refer to the control circuit label on the water heater for details The CCB is powered by a small 120V 24V transformer The control circuit oper...

Page 14: ...14 CCB CENTRAL CONTROL BOARD CONTROL CIRCUIT DIAGRAM ELECTRONIC CONTROL MODELS Figure 6 WIRING DIAGRAMS...

Page 15: ...the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C F...

Page 16: ...to terminal L1 with black wires 3 Reconnect all yellow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connect...

Page 17: ...page 8 The following describes the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or T...

Page 18: ...nect all red wires to terminal L2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service...

Page 19: ...Models only 4 Turn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are energized 6 Close the...

Page 20: ...94 C When the ECO switch contacts open activate the electronic control system locks out and displays a Fault message Voltage to the contactor coils and heating elements is terminated to prevent furthe...

Page 21: ...djustable 1 to 20 differential set points for each bank First bank on is the last bank off Helps reduce operating costs during low moderate loads CONTROL SYSTEM NAVIGATION The UIM User Interface Modul...

Page 22: ...control system has initiated heating operation Heating elements icon for a water heater equipped with 1 Bank of heating elements Each circle represents one heating element Each diagonal row of 3 elem...

Page 23: ...played in this menu Economy Mode Setup Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied or reduced demand periods Alarm Output Setup The co...

Page 24: ...g This can improve the precision of temperature control in the storage tank and at points of use This feature can also be used to compensate for building recirculation loops hot water returning to the...

Page 25: ...on off status of each Bank of heating elements Yes On No Off Alarm Condition Displays the status of the user definable Alarm Output function see Alarm Output Setup Menu Yes alarm condition has been m...

Page 26: ...tional Buttons on the display changes as you navigate through the various menus and screens Use the Up Down buttons to select highlight in black the Economy Mode Setup menu from the Main Menu Press th...

Page 27: ...ges to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm...

Page 28: ...Up Down and CHANGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change...

Page 29: ...n current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault co...

Page 30: ...sages in chronological order in this menu The most recent will be at the top of the list A time stamp is displayed below each listed Fault and Alert message showing when the Fault or Alert condition o...

Page 31: ...Restore Factory Defaults menu General Periodically the drain valve should be opened and the water allowed to run until it flows clean This will help to prevent sediment buildup in the tank bottom Peri...

Page 32: ...om water system Check for any leaks and immediately correct any if found 7 Restart the water heater as directed in this manual See the Repair Parts Illustration for anode rod location FLUSHING the Wat...

Page 33: ...not remove these types of scale which are occasionally encountered Call the toll free phone number on the back cover of this Instruction Manual to purchase UN LIME and heating element gaskets Other sc...

Page 34: ...are normal however the tank bottom and elements should be cleaned See the Maintenance section of this manual 2 Some of the electrical components of the water heater make sounds which are normal Conta...

Page 35: ...ters tank insert Q Tip or similar absorbent material between jacket opening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the t...

Page 36: ...any component in the system 3 Service valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELI...

Page 37: ...Control should be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature...

Page 38: ...re Control should be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperatur...

Page 39: ...the system 3 Service valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCUL...

Page 40: ...to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECT...

Page 41: ...ed to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELE...

Page 42: ...lves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 3 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERAT...

Page 43: ...between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH VERTICA...

Page 44: ...ump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH HORI...

Page 45: ...icing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 4 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL...

Page 46: ...er s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH VERTICAL STORAGE TANK LEGEND T...

Page 47: ...ater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH HORIZONTAL STORAGE TANK LEGE...

Page 48: ...Inlet and outlet size 1 1 2 THREE HEATERS Tank Capacity Gallons Part Number H W D A 52 9003430205 66 1 4 91 3 4 27 1 4 13 1 4 80 9003430205 70 1 2 95 1 4 31 1 4 9 3 4 120 9003430205 73 1 4 99 1 2 35...

Page 49: ...49 NOTES...

Page 50: ...50 NOTES...

Page 51: ...he owner is responsible for all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipp...

Page 52: ...52 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: