is
Instruction manual BFC
75
Air pressure switch fails
to close during pre-
purge.
Air pressure switch
leads
1. Check the wiring between the air pressure switch and the
controller. Rectify any defect:
-
if any wires are damaged, replace the wiring harness
-
properly connect loose or detached hoses
2. Reset appliance controller
Loose air pressure
switch hoses
1. Check hoses between air pressure switch and burner/fan.
Rectify any defect:
-
if any wires are damaged, replace the wiring harness
-
properly connect loose or detached hoses
2. Reset appliance controller
Heat exchanger and/or
chimney flue is blocked
3. Measure the pressure differential across the air pressure switch
4. Check the values
(2.4.5 "Pressure switch")
5. Check heat exchanger, condensation drainage and/or chimney
flue for blockages
6. Clear any blockage that may be present.
7. Reset appliance controller
Defective controller
1. Check that the controller is receiving power
2. Check that the controller is correctly connected
3. If there is no electrical power, check the power supply to the
terminal block, or replace the controller.
4. Rectify any incorrect connections.
5. Reset appliance controller
Code + Description
Cause
Solution
Remark
Summary of Contents for Cyclone BFC - 30
Page 2: ...www aosmithinternational com your installer...
Page 4: ...4 Instruction manual BFC gis...
Page 8: ...Table of contents 8 Instruction manual BFC...
Page 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Page 42: ...Conversion to a different gas category 42 Instruction manual BFC 4 is...
Page 48: ...Draining 48 Instruction manual BFC 6 gis...
Page 54: ...Status of the appliance 54 Instruction manual BFC 8 gis...
Page 58: ...Shutting down 58 Instruction manual BFC 10 gis...
Page 82: ...is Instruction manual BFC 82...
Page 84: ...Maintenance frequency 84 Instruction manual BFC 14 is...
Page 94: ...Appendices 94 Instruction manual BFC 17 is...
Page 96: ...Instruction manual BFC 96...