A.O. Smith Burkay HW-300 User Manual Download Page 7

7

THERMAL BALANCER

Figure 4 shows the internal wiring of the thermal balancer. The 

device  may  be  tested  after  disconnecting  the  four  leads  from 

their respective terminals on the unit.

1. 

Apply a test light to the yellow and red leads.
•  The lamp should light as the contact in this circuit is 

normally closed when the resistor is cool.

2. 

Apply a light to the black and yellow leads.
•  The lamp should not light as the contact in this circuit is 

normally open when the resistor is cool.

3. 

Remove the test light.

4. 

Apply 120 volts to the white and red leads which power the 

1900 ohm resistor. After a warming period the contacts of 

the thermal balancer should operate.

5. 

Remove the test light.

6. 

Apply the test light as described in steps 1 and 2.

While the resistor is still warm the lamp indications should be the 

opposite as described previously.

MANUAL RESET HIGH LIMIT

This  boiler  is  equipped  with  a  manual  reset  high  limit  switch, 

located  under  the  small  cover  on  the  side  of  the  jacket,  see 

Figure  5. This  device  provides  positive  shutdown  of  the  boiler 

in the event of boiler or system malfunction. Should the surface 

temperature of the copper tubing heat exchanger reach 250°F 

(120°C), the high limit switch will activate, the gas control valve 

will  close,  the  pilot  and  main  burners  will  be  extinguished.  If 

the  high  limit  switch  should  shut  off  unit,  check  the  following 

conditions:

•  No water in boiler.
•  Restricted water flow through the boiler.
•  Improper wiring (boiler firing without circulating pump 

operating).

•  Pump failure.

After  correcting  failure  condition  remove  the  protector  switch 

cover and push the reset button. The high limit switch may be 

reset  after  the  coil  surface  cools  to  6°F  (3.3°C)  below  the  trip 

setting.

AUTO RESET HIGH LIMIT

The high limit is a safety device wired in series with the ignition 

system. Set the high limit control to approximately 100°F above 

the maximum designed system temperature. If the boiler outlet 

water temperature should exceed the high limit setting, the main 

gas control valve will close but the circulating pump will continue 

to operate. Maximum adjustable setting is 115°C (239°F) cut-out 

with a 30°C (86°F) to 250°C (482°F) adjustable differential, see 

Figure 2.

INTERMITTENT IGNITION CONTROL MODULE

The  Honeywell  S-8600  control  module  contains  the  electronic 

components of the system and also serves as a control wiring 

system  for  the  controls  mounted  on  the  boiler.  The  control 

module performs the following functions:

1. 

Checks for safe-start by sensing for a false flame condition 

on start-up.

2. 

Generates a potential of 15,000 volts for spark ignition of the 

 

pilot burner.

3. 

Opens the pilot valve.

4. 

Discontinues  ignition  spark  when  the  pilot  flame  is 

established.  The  S-8600  control  used  on  propane 

gas  models  provides  safety  lockout  if  the  pilot 

fails  to  ignite  within  the  pilot  flame  establishing 

period.  The  S-8600  control  used  on  natural  gas 

models  continues  trial  for  ignition  until  pilot  flame 

 

is established.

5. 

After proof of pilot flame, opens then main valve.

6. 

On  a  power  loss,  shuts  the  boiler  down.  When  power  is 

restored it will begin a new ignition cycle.

7. 

On a loss of flame, shuts off main gas and starts trial for pilot 

ignition.

Please refer to Troubleshooting section for more information. 

FIGURE 2.  AUTO RESET HIGH LIMIT

FIGURE 3.  S-8600 INTERMITTENT IGNITION CONTROL 

MODULE (IID)

FIGURE 4.  THERMAL BALANCER

FIGURE 5.  HIGH LIMIT SWITCH

Summary of Contents for Burkay HW-300

Page 1: ...exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applian...

Page 2: ...OMPONENTS 6 BOILER START UP AND OPERATIONS 10 Filling the system 10 Precautions 10 Pilot and main burner 10 Checking and adjusting input 12 TROUBLESHOOTING 16 MAINTENANCE PROCEDURES 24 Manual reset hi...

Page 3: ...y hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...l Code CSA C22 1 ABBREVIATIONS USED Abbreviations found in this Instruction Manual include ANSI American National Standards Institute ASME American Society of Mechanical Engineers NEC National Electri...

Page 6: ...6 Figure 1 COMPONENT LOCATIONS CONTROL COMPONENTS...

Page 7: ...push the reset button The high limit switch may be reset after the coil surface cools to 6 F 3 3 C below the trip setting AUTO RESET HIGH LIMIT The high limit is a safety device wired in series with t...

Page 8: ...h ASME code Properly sized Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death Water Damage Hazard Press...

Page 9: ...lower water temperatures be used to avoid the risk of scalding It is further recommended in all cases that the water temperature be set for the lowest temperature which satisfies the user s hot water...

Page 10: ...iators or convectors PRECAUTIONS If the unit is exposed to the following do not operate boiler until all corrective steps have been made by a qualified service technician Flooding to level of burner o...

Page 11: ...ee Figure 7 Check for good terminal connection at the sensing probe at the pilot burner assembly if pilot does not light Check for electrical power to the valve If electrical power and gas are present...

Page 12: ...this formula to clock the meter Be sure that other gas consuming appliances are not ON during this interval 3600 x H Btuh T Btuh The approximate actual input rate T Time in seconds to burn one cubic f...

Page 13: ...M After 15 sec ignition shut down 5 minute time delay before re try S 8600H After 15 sec ignition system locks out must be manually reset FLAME CURRENT SENSED Spark generator off Second valve operator...

Page 14: ...14 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE FOR HW300 HW399...

Page 15: ...15 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE WITH I I D FOR HW420 UP...

Page 16: ...ff delay of approximately 2 minutes Pump and burner remain on Tank temperature control thermostat defective Replace System wiring is incorrect Correct wiring Circulating pump on Pump wired for continu...

Page 17: ...ceramic insulator surrounding the electrode cracked or broken Replace pilot burner assembly Replace ignition module Turn on gas supply Turn on power supply Securely connect cable and or ground wire Ca...

Page 18: ...ttached to pilot assembly and GND terminal on module Are ignition cable and ground wire in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor ro...

Page 19: ...sensor rod in good condition not broken or cracked Is the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the inst...

Page 20: ...lot ground wire firmly attached to the pilot assembly and GND terminal on module Are high voltage cable and ground wire in good condition not brittle burnt or cracked Make sure pilot flame spreader ho...

Page 21: ...below minimum threshold for system operation not applicable A Flash Code Descriptions Heartbeat Constant 1 2 second bright 1 2 second dim cycles The flash code number signifies that the LED flashes X...

Page 22: ...ontrol remains in wait mode When the fault corrects control resumes normal operation after a one minute delay Check transformer and AC line for proper input voltage to the control Check with full syst...

Page 23: ...r proper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout Remain in lockout until Call for Heat is cycled Check gas supply...

Page 24: ...r bad leads With leads attached depress the switch button If the meter does not read zero the switch is defective and must be replaced PRESSURE RELIEF VALVE TEST Burn hazard Hot water discharge Keep c...

Page 25: ...w boiler parts and vent to cool before disassembly 2 Remove the boiler draft diverter and vent pipe running to the chimney Check parts and chimney for obstructions and clean as necessary 3 Remove burn...

Page 26: ...26 NOTES...

Page 27: ...te or provincial law are limited to one 1 year dura tion for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limita...

Page 28: ...28 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: