A.O. Smith Burkay HW-300 User Manual Download Page 24

24

MAINTENANCE PROCEDURES

These boilers are designed to give many years of efficient and 

satisfactory  service  when  properly  operated  and  maintained.

To  assure  continued  good  performance,  the  following 

recommendations are made.
The area around the boiler should be kept clean and free from 

lint and debris. Sweeping the floor around the boiler should be 

done carefully. This will reduce the dust and dirt which may enter 

the burner and pilot air passages, causing improper combustion 

and sooting.
The flow of combustion and ventilation air to the boiler must not 

be obstructed. The boiler area must be kept clear and free from 

combustible  materials,  gasoline,  and  other  flammable  vapors 

and liquids.
Any safety devices including low water cutoffs used in conjunction 

with  this  boiler  should  receive  periodic  (every  six  months) 

inspection to assure proper operation. A low water cutoff device 

of the float type should be flushed every six months. All pressure 

relief  valves  should  be  inspected  and  manually  operated  at 

least twice a year. More frequent inspections may be necessary 

depending on water conditions.
Periodic checks, at least twice a year, should be made for water 

and/or gas leaks.
The  boiler  mounted  gas  and  electrical  controls  have  been 

designed  to  give  both  dependable  service  and  long  life. 

However, malfunction can occur, as with any piece of equipment. 

It  is  therefore  recommended  that  all  components  be  checked 

periodically by a qualified service technician for proper operation.

MANUAL RESET HIGH LIMIT SWITCH CONTINUITY 

TEST

Do not depress the switch reset button prior to testing. With the 

boiler being cold, disconnect the leads from the switch. With a 

multimeter place a probe on each side of the switch. If the meter 

reads zero the switch is good. If you receive an infinite or OL 

signal, the reason could be:

1. 

Switch contacts open.
•  Depress reset button on switch (switch cannot be reset 

until water temperature in the boiler coils drop below 

200°F). Meter should read zero.

2. 

Defective switch or bad leads.
•  With leads attached, depress the switch button. If the 

meter does not read zero, the switch is defective and 

must be replaced.

PRESSURE RELIEF VALVE TEST

Burn hazard.

Hot water discharge.

Keep clear of Pressure

Relief Valve discharge outlet.

If after manually operating the valve, it fails to completely reset 

and  continues  to  release  water,  turn  off  power  to  the  boiler  at 

the main disconnect switch or breaker. Close the cold water inlet 

to the boiler and follow the draining instructions in this manual 

to drain the boiler. Should the pressure relief valve need to be 

replaced, call the toll free phone number listed on the back of this 

manual for further technical assistance.

CLEANING AND FLUSHING INSTRUCTIONS
INTERNAL CONTAMINANTS

The  hydronic  system  must  be  internally  cleaned  and  flushed 

after a new or replacement boiler has been installed to remove 

contaminants  that  may  have  accumulated  during  installation. 

This is doubly important when a replacement boiler is installed 

into an existing system where stop leak or other boiler additives 

have been used.
Failure  to  clean  and  flush  the  system  can  produce  acid 

concentrations  that  become  corrosive,  cause  gases  to  form 

that block water circulation or lead to formation of deposits on 

the boiler surfaces, any of which could result in damage to the 

system and circulating pump.
All hot water heating systems should be completely flushed with 

a grease removing solution to assure trouble-tree operation.
Pipe  joint  compounds,  soldering  paste,  grease  on  tubing  and 

pipe all tend to contaminate a system.
Failure to flush contaminates from a system can cause solids to 

form on the inside of boiler heat exchangers, create excessive 

amounts of air and other gases to block circulation, foul various 

system accessories and even deteriorate circulation seals and 

impellers.
It is recommended that after installation, the boiler and system 

when  filled  should  include  the  proper  percentage  of  cleaning 

solution related to approximate water volume of the system. Fire 

and circulate for about one hour and then flush clean with fresh 

water. Commercial grease removing solutions are available from 

your distributor.

FIGURE 10.  PRESSURE RELIEF VALVE TEST

Summary of Contents for Burkay HW-300

Page 1: ...exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applian...

Page 2: ...OMPONENTS 6 BOILER START UP AND OPERATIONS 10 Filling the system 10 Precautions 10 Pilot and main burner 10 Checking and adjusting input 12 TROUBLESHOOTING 16 MAINTENANCE PROCEDURES 24 Manual reset hi...

Page 3: ...y hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...l Code CSA C22 1 ABBREVIATIONS USED Abbreviations found in this Instruction Manual include ANSI American National Standards Institute ASME American Society of Mechanical Engineers NEC National Electri...

Page 6: ...6 Figure 1 COMPONENT LOCATIONS CONTROL COMPONENTS...

Page 7: ...push the reset button The high limit switch may be reset after the coil surface cools to 6 F 3 3 C below the trip setting AUTO RESET HIGH LIMIT The high limit is a safety device wired in series with t...

Page 8: ...h ASME code Properly sized Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death Water Damage Hazard Press...

Page 9: ...lower water temperatures be used to avoid the risk of scalding It is further recommended in all cases that the water temperature be set for the lowest temperature which satisfies the user s hot water...

Page 10: ...iators or convectors PRECAUTIONS If the unit is exposed to the following do not operate boiler until all corrective steps have been made by a qualified service technician Flooding to level of burner o...

Page 11: ...ee Figure 7 Check for good terminal connection at the sensing probe at the pilot burner assembly if pilot does not light Check for electrical power to the valve If electrical power and gas are present...

Page 12: ...this formula to clock the meter Be sure that other gas consuming appliances are not ON during this interval 3600 x H Btuh T Btuh The approximate actual input rate T Time in seconds to burn one cubic f...

Page 13: ...M After 15 sec ignition shut down 5 minute time delay before re try S 8600H After 15 sec ignition system locks out must be manually reset FLAME CURRENT SENSED Spark generator off Second valve operator...

Page 14: ...14 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE FOR HW300 HW399...

Page 15: ...15 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE WITH I I D FOR HW420 UP...

Page 16: ...ff delay of approximately 2 minutes Pump and burner remain on Tank temperature control thermostat defective Replace System wiring is incorrect Correct wiring Circulating pump on Pump wired for continu...

Page 17: ...ceramic insulator surrounding the electrode cracked or broken Replace pilot burner assembly Replace ignition module Turn on gas supply Turn on power supply Securely connect cable and or ground wire Ca...

Page 18: ...ttached to pilot assembly and GND terminal on module Are ignition cable and ground wire in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor ro...

Page 19: ...sensor rod in good condition not broken or cracked Is the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the inst...

Page 20: ...lot ground wire firmly attached to the pilot assembly and GND terminal on module Are high voltage cable and ground wire in good condition not brittle burnt or cracked Make sure pilot flame spreader ho...

Page 21: ...below minimum threshold for system operation not applicable A Flash Code Descriptions Heartbeat Constant 1 2 second bright 1 2 second dim cycles The flash code number signifies that the LED flashes X...

Page 22: ...ontrol remains in wait mode When the fault corrects control resumes normal operation after a one minute delay Check transformer and AC line for proper input voltage to the control Check with full syst...

Page 23: ...r proper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout Remain in lockout until Call for Heat is cycled Check gas supply...

Page 24: ...r bad leads With leads attached depress the switch button If the meter does not read zero the switch is defective and must be replaced PRESSURE RELIEF VALVE TEST Burn hazard Hot water discharge Keep c...

Page 25: ...w boiler parts and vent to cool before disassembly 2 Remove the boiler draft diverter and vent pipe running to the chimney Check parts and chimney for obstructions and clean as necessary 3 Remove burn...

Page 26: ...26 NOTES...

Page 27: ...te or provincial law are limited to one 1 year dura tion for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limita...

Page 28: ...28 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: