background image

47

START UP CONDITIONS

SMOKE/ODOR

It is not uncommon to experience a small amount of smoke and odor 

during the initial start-up. This is due to burning off of oil from metal 

parts, and will disappear in a short while.

THERMAL EXPANSION

Water  supply  systems  may,  because  of  such  events  as  high

 

line  pressure,  frequent  cut-offs,  the  effects  of  water  hammer 

among  others,  have  installed  devices  such  as  pressure

 

reducing  valves,  check  valves,  back  flow  preventers,  etc.

 

to  control  these  types  of  problems.  When  these  devices

 

are  not  equipped  with  an  internal  by  pass,  and  no  other

 

measures  are  taken,  the  devices  cause  the  water  system

 

to be closed. As water is heated, it expands (thermal expansion)

 

and  closed  systems  do  not  allow  for  the  expansion  of

 

heated water.

The  water  within  the  water  tank  expands  as  it  is  heated

 

and  increases  the  pressure  of  the  water  system.  If  the

 

relieving  point  of  the  water  heater’s  temperature-pressure

 

relief valve is reached, the valve will release excess pressure. The 

temperature-pressure relief valve is not intended for the constant 

relief of thermal expansion. This is an unacceptable condition and

 

must  be  corrected.  It  is  recommended  that  any  devices

 

installed  which  could  create  a  closed  system  have  a

 

by-pass  and/or  the  system  have  an  expansion  tank 

or  device  to  relieve  the  pressure  built  by  thermal

 

expansion  in  the  water  system.  Expansion  tanks  are

 

a v a i l a b l e   f o r   o r d e r i n g   t h r o u g h   a   l o c a l   p l u m b i n g

 

contractor.  Contact  the  local  water  heater  supplier

 

or  qualified  service  agency  for  assistance  in  controlling  these 

situations.

OPERATIONAL CONDITIONS

SMELLY WATER

In each water heater there is installed at least one anode rod (see 

“Figure 1B: 50 GALLON UNIT” “Figure 1C: 75 GALLON UNIT” 

for  corrosion  protection  of  the  tank.  Certain  water  conditions  will 

cause a reaction between this rod and the water. The most common 

complaint associated with the anode rod is one of a rotten egg smell 

in the hot water. The smell is a result of four factors which must all 

be present for the odor to develop:

a.  A concentration of sulfate in the supply water.

b.  Little or no dissolved oxygen in the water.

c.  A sulfate reducing bacteria which has accumulated within the 

water heater (this harmless bacteria is nontoxic to humans).

d.  An excess of active hydrogen in the tank. This is caused by the 

corrosion protective action of the anode rod.

Smelly water may be eliminated or reduced in some water heater 

models by replacing the anode rod(s) with one of less active material, 

and then chlorinating the water heater tank and all water lines. Contact 

the local water heater supplier or a qualified service agency for further 

information  concerning  an Anode  Rod  Replacement  Kit  and  this 

chlorination treatment.

If  the  smelly  water  persists  after  the  anode  rod  replacement  and 

chlorination treatment, we can only suggest that chlorination or aeration 

of the water supply be considered to eliminate the water problem.

Do not remove the anode rod leaving the tank unprotected. By 

doing so, all warranty on the water heater tank is voided.

AIR IN HOT WATER FAUCETS

HYDROGEN GAS: Hydrogen gas can be produced in a hot water 

system that has not been used for a long period of time (generally 

two  weeks  or  more).  Hydrogen  gas  is  extremely  flammable  and 

explosive. To prevent the possibility of injury under these conditions, 

we  recommend  the  hot  water  faucet,  located  farthest  away,  be 

opened  for  several  minutes  before  any  electrical  appliances 

which are connected to the hot water system are used (such as a 

dishwasher or washing machine). If hydrogen gas is present, there 

will probably be an unusual sound similar to air escaping through the 

pipe as the hot water faucet is opened. There must be no smoking 

or open flame near the faucet at the time it is open.

FOR YOUR INFORMATION

Summary of Contents for BTXL-100

Page 1: ...131 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WA...

Page 2: ...Piping 23 High Altitude Installations 23 Filling The Water Heater 23 INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS 24 VENTING INSTALLATION 25 Vent Installation Considerations 25 U S...

Page 3: ...irth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth...

Page 4: ...sing any electrical appliance connected to the hot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE S...

Page 5: ...5 GENERAL SAFETY INFORMATION...

Page 6: ...ad and understand instruction manual Breathing Hazard Carbon Monoxide Gas Property Damage Hazard All water heaters eventually leak Do not install without adequate drainage CAUTION Fire and Explosion H...

Page 7: ...installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installe...

Page 8: ...T Table 1 ROUGH IN DIMENSIONS Units A B C D E F G H I 50G Inches 66 75 49 25 22 00 15 75 3 00 8 00 8 00 62 00 65 00 cm 169 5 125 09 55 88 40 00 7 62 20 32 20 32 157 48 165 1 75G Inches 64 71 45 64 27...

Page 9: ...ply Pressure for Natural Gas 3 50 87kPa Minimum Supply Pressure for Propane Gas 8 00 1 99kPa Minimum pressure must be maintained under both load and no load dynamic and static conditions Table 3 RECOV...

Page 10: ...CODES 50 GALLON UNIT FEATURES AND COMPONENTS 24 18 35 31 9 4 2 3 19 29 20 22 23 21 1 12 16 25 11 17 33 13 26 27 34 SEE ACCESS PANEL CAUTION 28 30 32 21 18 5 14 15 Caution Thisaccesspanelcovers a 2 NPT...

Page 11: ...stallation of Vent System and Condensate Piping for more information VACUUM RELIEF VALVE INSTALL PER LOCAL CODES 75 GALLON UNIT FEATURES AND COMPONENTS CONT 24 18 35 31 9 4 2 3 19 22 23 21 1 12 17 25...

Page 12: ...Board 12 Top Plastic Enclosure 13 Display Enclosure 14 Exhaust Elbow Assembly 15 Condensate Tubing 16 Off On Switch 17 Display Label 18 Hot Water Outlet 19 Gas Supply 20 Main Manual Gas Shutoff Valve...

Page 13: ...d to flow freely from the exhaust elbow and for obstructions in the exhaust venting and exhaust vent terminal Also verify that the vent length does not exceed the maximum allowed as shown in the Vent...

Page 14: ...er where an adequate supply of fresh air for combustion and ventilation can be obtained See Combustion Air and Ventilation on Page 15 9 Locate the water heater where the vent and intake air piping whe...

Page 15: ...proper combustion potentially resulting in fire asphyxiation serious personal injury or death Do not apply insulation to the top of the water heater as this will interfere with safe operation of the b...

Page 16: ...ngs to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized openings will cause air to be drawn into the room through the...

Page 17: ...the bottom of the enclosure The horizontal ducts shall communicate directly with the outdoors See Figure 7 Each duct opening shall have a minimum free area of 1 square inch per 2 000 Btu hr 1100 mm2...

Page 18: ...manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read theTemperature Regulation section in this manual This water heater shall not be co...

Page 19: ...pain threshold 116 46 7 35 minutes 45 minutes 122 50 1 minute 5 minutes 131 55 5 seconds 25 seconds 140 60 2 seconds 5 seconds 149 65 1 second 2 seconds 154 67 8 instantaneous 1 second U S Government...

Page 20: ...lock up gas pressure regulator s should be installed no closer than 3 feet 1 meter and no farther than 8 feet 2 4 meters from the water heater s inlet gas connection 3 After installing the positive lo...

Page 21: ...h as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system THERMAL EXPANSION As water is heated it expands thermal expansion...

Page 22: ...quipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 and the code requirements of ASME If replaced the new T P valve must meet the requi...

Page 23: ...copper tubing iron or steel pipe for the condensate drain line Condensate drain lines should be installed in conditioned areas only Drain lines installed in areas that are subject to freezing temperat...

Page 24: ...he horizontally vented gas fueled heating appliance or equipment The sign should read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPEC...

Page 25: ...proper cement must be used for all joints including joining the pipe to Termination PVC Material If Polypropylene pipe and fittings are used the metal joint connector rings available from the Polyprop...

Page 26: ...lations Table 5 M G Duravent PolyPro Nominal Pipe Diameter Flue Outlet Adapter Adapter Connector Ring Connector 90 Degree Elbow Vent Material Terminal s 2 2PPS AD PPS PAC 2PPS LB 2PPS E90 2PPS 2PPS 2P...

Page 27: ...ON The first step is to determine where the vent pipe will terminate See Figures 13 Figure 14A and Figure 15 The vent may terminate through a sidewall as shown in Figure 13 and Figure 15 or through th...

Page 28: ...ow be positioned on the outside wall using the drilled holes as a centering point for the template A MASONRY SIDE WALLS Chisel an opening approximately 1 2 1 3 cm larger than the marked circle B WOODE...

Page 29: ...ir supply inlet into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 00...

Page 30: ...l air supply inlet into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100...

Page 31: ...ing 3 The air intake termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the air intake termination and the center line of the exhaust vent terminati...

Page 32: ...E HIGHEST ANTICIPATED SNOW LEVEL 12 MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL 24 MINIMUM SEPARATION EXHAUST MUST BE AT SAME LEVEL OR ABOVE INTAKE TERMINAL Figure 21 Figure 23 Figure 24 Fi...

Page 33: ...ration INSTALLATION VERTICAL ROOF TERMINATION 1 Determine best location for termination kit NOTE Roof termination is preferred since it is less susceptible to damage has reduced chances to intake cont...

Page 34: ...ioned where the vent vapors will not damage plants shrubs or air conditioning equipment Termination kit positioned so it will not be affected by wind eddy that may allow recirculation of combustion pr...

Page 35: ...re than 60 1 5 m See Figure 25 Do not use field supplied couplings to extend pipes Airflow restriction will occur and the heater pressure switch may cause intermittent operation 7 Cement heater combus...

Page 36: ...or hole using the base as a template 4 Screw the Cap to the Base using the supplied screws 5 Once the vent termination and pipes are secured the wall penetrations will need to be sealed from the inter...

Page 37: ...37 LIGHTING AND OPERATION LABELS...

Page 38: ...ply to the water heater must be turned off and on again to reset the control system Contact your dealer or servicer if continued high limit switch operation occurs It is recommended that lower water t...

Page 39: ...ressure switches and Temperature Probe is monitored by the control system The Combustion Blower Igniter and the 24 Volt Gas Control Valve are all energized by the control system The main components of...

Page 40: ...tion Blower is being energized The Blower Prover pressure switch contacts have closed The check mark icon is visual confirmation of contact closure The Igniter is being energized GAS OFF O N The 24 Vo...

Page 41: ...on that caused the Fault has not been corrected Heating Disabled The heating is disabled by the Enable Disable On Off switch in front of the unit CONTROL SYSTEM MENUS From the Desktop screen pressing...

Page 42: ...description of control system menus Use the Up and Down Buttons to view all control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen press...

Page 43: ...he hot water supply temperature varies greatly from the Operating Set Point setting These settings are adjusted in the same way described for the Operating Set Point and Differential Adjustment Operat...

Page 44: ...mulated time the control system has been in the heating operating state burner run time Total Cycle Count Total accumulated count of heating cycles Config CRC A number associated with the configuratio...

Page 45: ...event will replace the oldest Press the Operational Button under VIEW to view details for each Fault or Alert message stored NOTE fault history memory is cleared after 30 days 1 Blocked Air Intake A7...

Page 46: ...m Show Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons select hig...

Page 47: ...itions will cause a reaction between this rod and the water The most common complaint associated with the anode rod is one of a rotten egg smell in the hot water The smell is a result of four factors...

Page 48: ...ciated with the anode rod is a rotten egg smell produced from the presence of hydrogen sulfide gas dissolved in the water IMPORTANT Do not remove this rod permanently as it will void any warranties A...

Page 49: ...ning And Flushing on Page 49 Replace the Temperature Pressure Relief Valve with a properly rated sized new one see Temperature Pressure Relief Valve on Page 22 for instructions on replacement DISCHARG...

Page 50: ...and terminate it to an adequate drain 5 Ensure the drain hose is secured before and during the entire flushing procedure Flushing is performed with system water pressure applied to the water heater 6...

Page 51: ...tting G Leakage from recirculation plug or pipe connection H Leakage from the plug under the cleanout cover I Leakage from the temperature probe connection Not shown in figure J Condensate from the ex...

Page 52: ...cycle to purge the water heater of all combustion gases When the post purge cycle is complete the blower is de energized and will coast to a stop 12 The control system now enters the standby mode whi...

Page 53: ...le is activated Blower Prover switch contacts confirmed closed by control system Igniter is energized 24 V Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control sy...

Page 54: ...e water heater Refer to the parts list for more information or call the parts department or technical support phone number listed on the back cover of this manual for further assistance OPERATIONAL PR...

Page 55: ...ONDITIONS When the control system declares an Alert condition it will display an Alert message on the control system s LCD with a question mark The water heater will continue to operate during an Aler...

Page 56: ...CHANGE BACK ADVANCED Ignition Failure Fault occurred 2 mins ago The water heater has failed to ignite the burner Call a service professional Your Company Name Here press DOWN for more The control syst...

Page 57: ...Blocked Intake Air Switch contacts are open Loose or open wiring to the Blocked Intake Air Switch Excessive equivalent pipe length exceeded the maximum number of 90 elbows or wrong pipe size used in...

Page 58: ...ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING Figure 41 POWER VENT WIRING SCHEMATIC WIR...

Page 59: ...is also installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the li...

Page 60: ...60 www hotwater com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2013 A O Smith Corporation All rights reserved...

Reviews: