background image

13

VENT ATTENUATION ASSEMBLY

 INSTALLATION INSTRUCTIONS

The Vent Attenuation Assembly (VAA) is designed to provide a
reduction in noise that may be transmitted through the vent pipe.
This installation of this VAA is optional. Review directions
thoroughly prior to installing the new VAA. Please contact the
manufacturer of the water heater as shown in the instruction
manual with any questions or for additional product support.

VENT ATTENUATION ASSEMBLY KIT PARTS LIST

The kit consists of the following items. If a part is missing, use the
contact information in the instruction manual to acquire missing
component(s).

• Vent Attenuation Assembly
• flexible tubing
• hose barb
• hex plug (installed on VAA)
• instruction sheet

VENT ATTENUATION ASSEMBLY INSTALLATION

The VAA is designed for both vertical and horizontal installations.
The vertical installation does not require the additional hose barb
and flexible tubing. However, the horizontal installation will require
the hose barb and flexible tubing to release condensate buildup
from the VAA. See instructions and diagrams that follow for a
more detailed description.

Vertical VAA Installations (Recommended)

1. The VAA is designed to accept two inch PVC pipe into the

adapters on both ends. The VAA can be installed to the piping
from either side (there is no specific inlet or outlet). For optimum
performance, install VAA as close as possible to the blower
assembly.

2. Use standard PVC cement (not included with kit) and glue the

two inch PVC pipe coming from the blower into the VAA.

3. Perform the same sequence on the PVC pipe coming from

the exhaust side (vent terminal side) of the VAA.

4. Make sure the VAA and vent pipe is supported securely to a

permanent fixture (stud or wall). Use standard support straps
(not supplied with kit) that may be found at a local hardware
store. Failure to properly support the VAA and the surrounding
vent pipe could create a hazardous situation. DO NOT puncture
any surface of the VAA.

5. Confirm that the hex plug is securely installed in the 1/2" fitting

found on the center of the VAA pipe. It is imperative that the
plug is secure and air tight to prevent any combustion gases
escaping into the room. If the plug is not securely tightened,
remove and reinstall using Teflon tape on the threads. Once
installed along with the rest of the vent configuration, make
sure to operate the unit through at least one heat up cycle to
ensure there is no leakage around the plug or any joints of the
VAA or vent pipe system.

FIGURE 10: Typical Vertical Installation

Horizontal VAA Installations

1. The VAA is designed to accept two inch PVC pipe into the

adapters on both ends. The VAA can be installed to the piping
from either side (there is no specific inlet or outlet). For optimum
performance, install the VAA as close as possible to the blower
assembly.

2. Use standard PVC cement (not included with kit) and glue

the two inch PVC pipe coming from the blower into the
VAA. 

MAKE SURE THE 1/2" FITTING IS ON THE BOTTOM

SIDE OF THE VAA.

 This will be used to run the condensate

hose to a suitable drain. See typical vent installation in
Figure 11.

3. Perform the same sequence on the PVC pipe coming from

the exhaust side (vent terminal side) of the VAA.

4. Make sure the VAA and vent pipe is supported securely to a

permanent fixture (stud or wall). Use standard support straps
(not supplied with kit) that may be found at a local hardware
store. Failure to properly support the VAA and the surrounding
vent pipe could create a hazardous situation. DO NOT puncture
any surface of the VAA.

5. Remove hex plug from the center pipe of the VAA. Locate

the hose barb and install into the 1/2" fitting on the center of
the VAA. Using Teflon tape on the threads, install hose barb
into 1/2" fitting securely. It is imperative that the hose barb is
secure and tight to prevent any combustion gases escaping
into the room.

6. Locate flexible tubing. Slide one end of tube over the hose

barb located on the center pipe of the VAA. The ridges on the
hose barb should prevent the tube from sliding off, however,
to ensure there are no leaks and possible dislocation from
hose barb, use a wire tie or hose clamp (not supplied with kit)
and secure.

7. Take the other end of the flexible tubing and form an 8 inch

diameter circle approximately 3 feet down from the hose barb
located in the VAA. To ensure that the circle (loop) maintains
its shape, use two wire ties (not supplied with kit) to secure it.

Summary of Contents for BTX-80

Page 1: ...TAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE MODEL BTX 80 COMMERCIAL GAS WATER HEATER Glass Lined Tank Type Water Heater GET TO KNOW YOUR...

Page 2: ...0 50 189 Nat 4 00 0 99 120 60 5 All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load...

Page 3: ...of part numbers and descriptions Standard hardware items may be purchased locally A VENT PIPE B ANODE C HOT WATER OUTLET D OUTLET 120 VAC F GAS SUPPLY G MAIN MANUAL GAS SHUT OFF VALVE H GROUND JOINT...

Page 4: ...suspected do not attempt to find the cause yourself Go to a neighbor s house leaving your doors open to ventilate the house then call your gas supplier or service agent Keep area clear until a servic...

Page 5: ...arance of 24 should be allowed for blower assembly service Adequate clearance for servicing this appliance should be considered before installation such as changing the anodes etc Minimum clearances f...

Page 6: ...or component s previously used with a non potable water heating appliance 4 When the system requires water for space heating at temperatures higher than required for domestic water purposes a temperi...

Page 7: ...er heater With main burner in operation paint pipe joints including flanges and control inlet and outlet with rich soap and water solution Bubbles indicate gas leak To stop leak tighten flange screws...

Page 8: ...pling or other restriction and must terminate near a suitable drain to prevent water damage during valve operation The discharge line shall be installed in a manner to allow complete drainage of both...

Page 9: ...ng PVC Materials should useASTM D 2564 Grade Cement CPVC Materials should use ASTM F 493 Grade Cement and ABS Materials should use ASTM D 2235 Grade Cement If the water heater is being installed as a...

Page 10: ...lued into the end of the elbow that will mount on the discharge boot INSTALLATION OF VENT SYSTEM Before beginning installation of piping system thoroughly read the section of this manual VENT PIPE PRE...

Page 11: ...AUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING POWER VENT WIRING SCHEMATIC FIGUR...

Page 12: ...ION INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed the equivalent feet of pipe as listed...

Page 13: ...ir tight to prevent any combustion gases escaping into the room If the plug is not securely tightened remove and reinstall using Teflon tape on the threads Once installed along with the rest of the ve...

Page 14: ...leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 12 Typical Installation for Vertical Ven...

Page 15: ...0 pipe Never use all purpose cements commercial glues and adhesives or ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE ST...

Page 16: ...after it has hit the bottom of the fitting socket A good joint will have sufficient cement to make a bead all the way around the outside of the fitting hub The fitting will have a tendency to slide b...

Page 17: ...PERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to ligh...

Page 18: ...E ACCESS It is recommended that lower water temperatures be used to avoid the risk of scalding It is further recommended in all cases that the water temperature be set for the lowest temperature which...

Page 19: ...k in operating condition SERVICE SHOULD BE PERFORMED ONLY BY A QUALIFIED SERVICE TECHNICIAN READ THE GENERAL SAFETY INFORMATION SECTION FIRST USERS OF THIS APPLIANCE SHOULD BE AWARE THAT GAS COMPONENT...

Page 20: ...r writing to us at A O Smith Water Products Company Service Department 500 Tennessee Waltz Parkway Ashland City TN 37015 1299 or going to our website at www hotwater com Please click on Contact us the...

Page 21: ...afety water heater service should be performed only by a qualified service technician Read the GENERAL SAFETY INFORMATION section first WARNING DO NOT BY PASS ANY CONTROLS TO MAKE HEATER OPERATE OPERA...

Page 22: ...cuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then bac...

Page 23: ...nless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE...

Page 24: ...24...

Reviews: