SETUP
Page 21
5.
SETUP
Press < ESC > (alternatively <Menu> and <F4>) to return to the main monitor menu
and
then press < F5 > to enter the setup.
5.1
SETUP 1: Regulation
Use the <F2...F5> keys to access the individual sub-
menus.
Transformer Parameters
5.1.1
A parameter set can be specified for each cooling stage.
The number of menus depends on how many cooling stag-
es/fans the transformer has. The number of cooling stages
can be set via menu.
Press <F1> to access the next set of cooling stage pa-
rameters.
5.1.1.1
Rated current
The winding's rated current can be different for each type of cooling. Please note that pri-
mary values are also used for the rated current when measuring the primary current.
The rated current displayed in this menu must not be confused with the rated value of the
current that is used to measure tasks in the controller (SETUP 5, F2 et sq.).
There, the rated current is configured as 1 A or 5 A. For transformer monitoring, the nomi-
nal value of the current is the maximum current a transformer can be subjected to with a
specific cooling.
The current can be displayed in a range from 0...3000 A.
Press <F2> to enter the corresponding rated current.
Use <F1...F5> to enter the appropriate values.
Press <Enter> to confirm the setting.
5.1.1.2
Thermal time constant of the winding
The thermal time constant is a transformer-specific parameter and can generally be taken
from the transformer's data sheet.
Value range: 0…50000 s
... several sets of parameters