
Page 16
Page 16
Basic description of the Transformer Monitor
LEREF "Verzeichnis Ueberschrift" \* MERGEFORMAT Index
Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift
dem Text zuzuweisen, der hier angezeigt werden soll.
Contents
We take care of it.
4.3
Service life
The 'SERVICE LIFE' menu, which combines all of the service lives (transformer, fan, pumps),
is accessed from the 'MONITOR' main menu by pressing <F2>.
Operating hours (1)
4.3.1
'Operating hours 1' displays the accumulated operating hours for the transformer (trans-
former under voltage), the tap changer and the oil pump. The operating hours for the
transformer and the tap changer are different because only the hours that the motor is in
operation are measured for the tap changer. The 'Operating light time' is used as an indica-
tor of the tap changer's operating hours. This means that the service life counter is only
active for the tap changer if a binary input is configured as 'TC in operation' (07:TC.i.Op).
The counter value does not change if an input is configured but no 'TC in operation' signal
connected. If a binary input is not configured, the program uses the 'Maximum Time TC in
operation' setting in the Controller's SETUP 5 menu (Functions..., F1).
In this case, the tap changer's service life counter is incremented by the preset time when
the controller issues a control command.
The transformer's operating hours are recorded by default if a voltage on the secondary
page is set to 'Transformer in operation'.
This approach can produce incorrect results (see Figure 7) based on the location of the
voltage transducer.
In any case, measuring the primary voltage of the transformer will produce correct results.
The firmware characteristic 'Three winding' can be used to activate a second voltage chan-
nel that measures the primary voltage. The second voltage input is always present and in
principle available for this task when the controller is equipped with hardware Characteris-
tic 'M9'. In all other cases, the regulator – if the primary voltage is to be measured – must
be sent in for modification.
If software feature 'Three winding' is activated (only possible in combination with hardware
Characteristic M9), the operating hour count is derived from the primary voltage.
If the feature 'Three winding' is not activated, the operating hours are derived from the
transformer's secondary voltage, which - as mentioned above - can produce incorrect re-
sults based on the location of the voltage transducer.
Figure 7 shows an application in which two transformers are fed from a bus bar.
Summary of Contents for REG-D
Page 51: ...Notes Page 51 ...