IMPACT reference system manual (Typical )
Author:
DD
Design revision:
2.0
directly at the triggering output inside of the external device (i.e. fire detection system) to provide reliable
surveillance of the entire link.
EVAC inputs must receive an activation signal of at least 100ms in order to trigger events. Pulses shorter
than 100ms will be ignored.
4.4.9.
Amplifier 100V outputs
Connect 100V outputs of the power amplifier to inputs “chA / chB” of 4E-SW6.
In order to connect multiple 4E-SW6 to the same amplifier, use the parallel 100V connection port “next
SW6” on the 4E-SW6.
More information on different connection modes can be found in the 4E-SW6 manual.