4.1.3.

 

FAULT 

Indicates that the system is in the FAULT state (general fault indicator), where at least one device in the 

system is reporting a fault. 

 

Continuous: when a local fault is detected 

 

Blinking slow: when a local device is healthy and at least one remote device is reporting fault state 

4.1.4.

 

POWER SUPPLY 

Indicates a power supply fault of the local C500 unit, where at least one of following faults is reported: 

 

Continuous: mains fault 

 

Blinking slow: battery-related fault: 

o

 

Loss of battery 

o

 

Loss of charger 

o

 

Battery resistance too high 

o

 

Temperature fault 

o

 

Charger communication fault 

4.1.5.

 

SYSTEM FAULT 

Indicates system fault of the C500 main unit, where: 

The CPU or program execution is stopped or malfunctioning, 

Corruption of storage memory containing config settings and audio files (SD card). 

Front panel is not communicating with main board 

Where a system fault is caused by a CPU or memory fault, the C500 remains in “safe state”, where critical 

functions (including audio transmission, reaction on control inputs, etc.)  are stopped until the fault 

is removed.  

 

Continuous: 

o

 

CPU / program fault 

o

 

front panel fault 

 

Blinking slow: 

o

 

SD card fault 

o

 

Config file not compatible 

o

 

Wrong ID setting 

4.1.6.

 

NETWORK 

Indicates when any device or link in the network is missing. 

 

Blinking slow: 

Global ring is broken (any place in the ring) 

 

Summary of Contents for Compact 500

Page 1: ...0 Voice Evacuation System It explains how to operate the Compact 500 and how to interpret indications This operation manual is addressed to end users as well as technical personnel such as service tec...

Page 2: ...system 4 Network system 4 3 2 1 Global network G Net 4 3 2 2 Local network L Net 5 4 Front Panel 6 LED indicators 6 4 1 1 POWER 6 4 1 2 EVAC 6 4 1 3 FAULT 7 4 1 4 POWER SUPPLY 7 4 1 5 SYSTEM FAULT 7 4...

Page 3: ...he Compact 500 is to provide public address functionalities such as background music public announcements or general paging Compact 500 is extremely scalable due to its network capabilities and create...

Page 4: ...NCE and RESET input 8 x GPI 8 x GPO Up to 6 loudspeaker lines with EOL monitoring 100W or 200W maximum power per line 2 analog balanced audio inputs Integrated Fireman Microphone with priority Access...

Page 5: ...500 operation manual Author DD Page 5 of 15 3 2 2 Local network L Net L Net daisy chain topology is dedicated for peripheral devices of the main unit such as remote microphone stations L Net is used t...

Page 6: ...dicates the operating status of the C500 Continuous system is powered and ready Blinking fast system is booting not ready for full operation 4 1 2 EVAC Indicates that the system is in the Voice Alarm...

Page 7: ...charger o Battery resistance too high o Temperature fault o Charger communication fault 4 1 5 SYSTEM FAULT Indicates system fault of the C500 main unit where The CPU or program execution is stopped or...

Page 8: ...d by one of following audio signals Continuous LIVE EVAC Blinking slow EVAC Message 4 1 7 2 Yellow Indicates that the zone is transmitting an ALERT message and or is in fault state Continuous Zone fau...

Page 9: ...ed in the configuration settings 4 2 4 RESET Press to clear your current zone selection 4 2 5 FUNCTION button Press and hold the FUNCTION button to enable Access level 2 In access level 2 you are able...

Page 10: ...nel one by one forcing the backup amplifier to engage and take over the channel where the fault is simulated The sequence will be displayed on the front panel ZONE LEDs NOTE the backup amplifier test...

Page 11: ...essage ALERT message SILENCE RESET fireman mic with PTT button Fireman microphone Integrated Fireman Mic with priority and electrical monitoring Power supply equipment Built in power supply system EN...

Page 12: ...29 kg Housing material Steel ABS IP rating IP 30 Mounting Wall mounted box Network system Max number of devices in the network 255 Max number of zones 255 Max total system output power 102 kW Number...

Page 13: ...Hacousto Holland bv Industrieweg 87 2651BC Berkel Rodenrijs 4EVAC Compact 500 operation manual Author DD Page 13 of 15 8 Marking...

Page 14: ...Hacousto Holland bv Industrieweg 87 2651BC Berkel Rodenrijs 4EVAC Compact 500 operation manual Author DD Page 14 of 15...

Page 15: ...651BC Berkel Rodenrijs 4EVAC Compact 500 operation manual Author DD Page 15 of 15 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berkel Rod...

Reviews: