First of all, check if you by any chance didn’t activate the recalculate in liters option.
If you do so without saving any table in the sensor’s memory, it will not be able to either
display the level as is or to recalculate it in liters/gallons.
Fig. 86
Recalculate in liters not activated
Fig. 87
Recalculate in liters is activated but no
table has been uploaded into the sensor’s
memory
Another possible reason could be that the sensor is not properly calibrated and its CNT is
below the Empty calibration value. In such a case, recalibrate the sensor.
Also, if you calibrated the sensor with fuel, it is possible that the drainage hole of the
sensor was left covered and the air trapped inside the tubes doesn’t allow the fuel to go up the
tubes.