Carbon Monoxide Detector and Controller 

 

 

           CM-21A

 

 

Low maintenance, no periodic calibration needed 

 

SPDT fan relay switches 5 amps 

 

Automatic ventilation controller 

 

Dual relays: fan (SPDT) & alarm (N.O.) 

 

Lights reflect system status 

 

Micro computer controlled 

 

Long life (7 to 10 years) Solid state sensor 

 

   

••

 CM-21A

 is very specific to carbon monoxide (CO), avoids nuisance alarms. 

   

 

CM-21A

 provides CO detection and automatic exhaust fan control for automotive  

maintenance facilities, enclosed parking garages, warehouses with forklifts, etc.  

   

 

CM-21A

 meets the requirements of the Uniform Building Code for enclosed garages. 

   

 

CM-21A

 Meets or exceeds UL 2034 standard and OSHA standards for CO exposure. 

   

 Fan relay activates at 35 ppm of CO averaged over 5 minutes.  25 ppm is selectable. 

   

 Alarm relay activates at 100 ppm of CO after 30 minutes or 200 ppm after 10 minutes. 

   

 5 amp SPDT fan relay controls starters of exhaust fans.  

   

 1/2 amp N.O. alarm relay connects to warning devices or control panels. 

   

 

CM-21A

 mounts on a standard 4x4 electrical box and becomes cover for the box. 

   

 Supervised system: any internal detector problem will cause the fan relay to activate. 

   

 Optional calibration kit is available.  One screw allows access for calibration. 

 

Specifications:    

 

Power:   3 watts from 12 to 24 VAC or VDC 
Current:   12 V - 0.25 amps, 24 V - 0.12 amps 
Shipping Weight:   1 pound 
Size:   4 1/2 x 4 x 2 1/8 in. 
Color:   gray 
Connections:   7 each #20 wires, 6 inches long 
Mounting box:   (not included) 4x4 electric 
Fan relay:   5 amp, 240 VAC, pilot duty, SPDT 
Fan relay actuation:  35 or 25 ppm CO after 5 min.  
Alarm relay:   0.5 amp 200 V, 10 VA 
Alarm relay actuation:   100 ppm CO after 30 min. 
                                       200 ppm CO after 10 

min. 

Operating Environ:   0 to 125 F, 10 to 90 % RH 
Repeatability: 

±

 10% at 50 ppm calibration point 

Linearity: 

±

 10% 

 

Carbon monoxide exposure: ppm CO vs time

 

 

 

200 ppm 

CO 

100 ppm 

CO 

50 ppm 
    CO 

35 ppm 
    CO

1

 

 

 

 

 

 

CM-21A 

  Fan Relay 

5 min. 

5 min. 

5 min. 

5 min. 

 

 

 

 

 

CM-21A 

  Alarm Relay 

10 min. 

30 min. 

none 

none 

 

 

 

 

 

UL 2034 Std. 

35 min. 

90 min. 

no std. 

no std. 

 

 

 

 

 

OSHA Std. 

no std. 

no std. 

8 hr TWA  no std. 

 

 

 

 

 

UBC Std. 

60 min. 

no std. 

8 hr TWA  no std. 

 

 

 

 

 

1. This response is jumper-selectable at 25 ppm; see         
        CM-21A Operating and Installation Instructions.

 

   Manufactured By:      Distributed By: 

 

 

Summary of Contents for Macurco CM-21A

Page 1: ... CM 21A Carbon Monoxide Detector and Controller User Instructions for 3M Macurco CM 21A Low voltage dual relay Carbon Monoxide CO detector and controller Important Keep these User Instructions for reference 1 ...

Page 2: ...A mounts on a standard 4x4 electrical box and becomes cover for the box Supervised system any internal detector problem will cause the fan relay to activate Optional calibration kit is available One screw allows access for calibration Specifications Power 3 watts from 12 to 24 VAC or VDC Current 12 V 0 25 amps 24 V 0 12 amps Shipping Weight 1 pound Size 4 1 2 x 4 x 2 1 8 in Color gray Connections ...

Page 3: ...ve feet above the floor 3 See applicable building code for fan size vs air changes per periods of time 4 Make sure there are air inlets to provide adequate air flow throughout the building Typical multiple CM 21A installation space sensors equally relay red red yel yel blue brn org POWER 12 24V ALARM RELAY SPDT fan RELAY CM 21A coil MAIN FAN POWER exhaust fan RELAY 12 or 24 vdc coil Alarm Control ...

Page 4: ...20 mA analog output based on a 0 200 ppm sensing range The microprocessor controls the heating of the sensor and subsequent reading of the CO level The micro processor compensates for any drift in the sensor over time The microprocessor system includes self diagnostic self restarting and remote failure reporting The output signal will drop below 4 mA if a fault is discovered If power problems caus...

Page 5: ...pm N O N C Warning Relay Factory setting 50 ppm N O N C T3 T2 L2 KCO A 24 VAC 4 20 mA SIG OUT L1 L2 WIRING 50 ppm 50 100 ppm relay settings KCO R only R Relay output carbon monoxide sensor MODEL KCO DESCRIPTION H Hinged cover enclosure KCO R H 50 ppm Example KCO RH 50 ppm Carbon monoxide sensor with relay output and hinged cover enclosure A Analog output carbon monoxide sensor LT Low temperature o...

Reviews: