2.1.4 Clean or cover cable jacket if necessary, for
c
old
s
hrink parking position. Slide the jacketing tube onto one
cable end. Slide splice body onto opposite cable, loose core end first. For size transitions, park splice on
smaller cable.
*Note:
If space is limited, the jacketing tubes and splice body can be put on the cable stacked inside each other.
Normal installation
loose core end
loose core end
* Stacked for limited space
Aluminum Connector (Al / Cu)
Copper Connector (Cu)
Note:
Jacketing is not optional. Cold
s
hrink jacketing tube must be installed.
Aluminum (Al/Cu) Connector Growth Chart
Conductor Size
Typical growth allowance (per end)
1/0 - 3/0
1/
8
" (
3
mm)
4/0 - 350 1
/4" (6 mm)
Note:
1) Copper connectors do not require a length change allowance.
2) Maximum aluminum connector crimped length allowed is 6.50" (165 mm).