• All models of the heat recovery unit can be installed in
the following positions:
TECHNICAL INFORMATION
● All the materials within a distance of 100 mm of the unit
must be non-flammable (they don’t burn or flare) or of
low flammability (the don’t burn, disintegrate, like plas
-
terboard). These materials, however, must not cover
the unit’s inlet and exhaust openings.
● The safe distance between combustible materials and
the exhaust is 500 mm.
● The safe distance for combustible materials in all direc
-
tions is 100 mm.
•
The unit must be installed so that the direction of the air
exhaust corresponds to that of the distribution system.
•
The unit should be installed so as to provide access for
maintenance, service or disassembly. This includes, in
particular, access to inspecting the dampers flaps and
their opening, access to the cover of the control unit’s
cabinet, to the cover of the of the air filter.
6.1-2 Safe installation distance
ATTENTION!
6. INSTALLATION
•
Any other position is forbidden.
6.1-3 Hanging the unit
Use the drilling template below to place the anchoring
points.
A
B
Type
Weight of unit (kg)
Without heating
With electric
preheating
With electric
pre-heating and
post-heater
HRDF1-030
62
63
64
HRDF1-050
81
82,5
84
HRDF1-070
100
102
104
Type
A
B
HRDF1-030
652
1160
HRDF1-050
702
1380
HRDF1-070
902
1580
* Installation on the wall possible only for HRDF1-030
* The unit can only be installed in a position where the condensate drain is pointing
downwards.
*