14
PP
2VV.
Creating innovative solutions for you and your business since 1995.
ver.1 07-04-20
A temperature sensor can be selected to control the air tem-
perature. The values from the selected sensor will be used
for temperature control and will be displayed on the main
controller screen.
The Software reset (menu 48) must be performed to save
the changes
Supply duct:
The unit will be controlled by the supply air temperature sensor to the object. Suitable for installations where the same
supply air temperature is required to the rooms and in individual rooms is further adjusted as required. There is no local
overheating. Suitable for multi-zone ventilation. The unit will respond quickly to temperature changes at this setting.
ATTENTION: With this setting, the MAX and MIN channel limit values cannot be defined. The maximum limit in the
channel is the desired temperature. The minimum temperature is set to 15 ° C. (for its adjustment it is possible to go to
the sensor of the outlet channel, adjust the limit and change the sensor to the supply - the MIN value will be respected
according to the settings).
Extract duct:
The unit will be controlled by the extract air temperature sensor from the object. Suitable for installations where it is
necessary to monitor the average exhaust air temperature and adjust the supply air temperature to achieve comfort in
the building. Suitable for mono-zone ventilation where supply air affects one room. The unit will respond more slowly
to the temperature change at this setting. The supply air temperature is between the minimum and maximum supply
air temperature.
Room:
The unit will follow the temperature sensor installed in the room. Suitable for installations where it is necessary to mo-
nitor the local room temperature and adjust the supply air temperature to achieve room comfort. Suitable for monozone
ventilation, where the supply air affects one space. The supply air temperature is between the minimum and maximum
supply air temperature. According to the setting in the menu 10 - SUPPLY DUCT LIMITS.
Room BMS:
Temperature information provided by the building management system
08
Temperature sensor
09