Z1700

INSTALLATION  INSTRUCTIONS  FOR

SHOKTROL  WATER  HAMMER  ARRESTOR

Rev.

D

Date:

4/17/2018

C.N. No.

139910

Form #

WH1

Page 2 of 2

In an effort to arrive at a uniform method of sizing water hammer arrestors, members of the Plumbing and Drainage Institute
sponsored a comprehensive testing program which lasted four years. As a result, there is now an industry-wide standard,
P.D.I.-WH201 and the all-stainless-steel Zurn SHOKTROL conforms with every aspect of this newly-available information.

Standard P.D.I.-WH201 bases its sizing data upon the well-known fixture-unit formula. Since most engineers and specifiers
utilize fixture-units in their daily calculations, it was appropriate to employ this method for quick, concise water hammer
arrestor sizing.

Using Table II (below), determine the “weight in fixture-units” for cold and hot water branch lines serving a group of fixtures,
either for public or private installations. When the “weight in” has been established, the data is then applied to the selection
Table III.

Using the “weight in fixture-units” obtained from Table II, select the properly-sized SHOKTROL from Table III. If the water
pressure in the line exceeds 65 PSIG, select the next larger size SHOKTROL. If the fixture-unit contains “1/2” fraction,
“round it up” to the next larger or whole number. (Example: If total is 11-1/2 fixture units, change it to 12 fixture-units).

HOW TO PROPERLY LOCATE ZURN SHOKTROLS

Multiple Fixture-Branch Line Less Than 20’ Long-(Illus. 2). The
preferred location for a Zurn SHOKTROL is at the end of the branch line
between the last two fixtures served when the branch line does not
exceed 20’ in length, from the start of the horizontal branch line to the
last fixture supply on the line (Use Tables II & III Below).

Multiple Fixtures-Branch Line More Than 20’ Long-(Illus. 3). On
branch lines over 20’ in length, use two SHOKTROLS whose
capacities total the requirements of the branch. Locate one unit
between the last and next to last fixture and the other unit
approximately midway between the fixtures. (Use Tables II & III
Below).

Multiple Fixtures-Extremely Long Branch Line-(Illus. 4). In unusual
instances where a very long branch line is involved, the water supply
is generally fed to some midpoint or other location on the branch line.
(Use Tables II & III Below).

   Illustration 2. Example of P.D.I. Rule 1

   Illustration 3. Example of P.D.I. Rule 2

   Illustration 4. Example of P.D.I. Rule 1 and Rule 2

Table II

Total C.W. H.W. Total C.W. H.W.

Water Closet

Flush Valve

10

10

-

6

6

-

Water Closet

Flush Tank

5

5

-

3

3

-

Pedestal Urinal

Flush Valve

10

10

-

-

-

-

Stall or Wall Urinal

Flush Valve

5

5

-

-

-

-

Stall or Wall Urinal

Flush Tank

3

3

-

-

-

-

Lavatory

Faucet

2

1-1/2 1-1/2

1

1

1

Bathtub

Faucet

4

2

3

2

1-1/2 1-1/2

Shower Head

Mixing Valve

4

2

3

2

1

2

Bathroom Group 
Closet

Flush Valve

-

-

-

8

8

3

Bathroom Group 
Closet

Flush Valve

-

-

-

6

6

3

Separate Shower

Mixing Valve

-

-

-

2

1

2

Service Sink

Faucet

3

3

3

-

-

-

Laundry Tubs (1-3)

Faucet

-

-

-

3

3

3

Combination Fixture Faucet

-

-

-

3

3

3

Weight in Fixture-Units

Public

Private

Fixture

Type of 

Supply 

Control

Table III

Zurn Shoktrol Size 

Z1700 Series

#100

#200

#300

#400

#500

#600

P.D.I. Units

A

B

C

D

E

F

Fixture-Units

1-11

12-32

33-60

61-113

114-154

155-330

Cold Water Branch
2 WC at 10 F.U. . . . . ea. = 20
4 Lav. at 1° F.U. . . . . ea. =   6

   Total  26

Hot Water Branch

4 Lav. at 1° F.U. . . . . ea. =   6

   Total  26

Select Zurn #200 Unit

Select Zurn #100 Unit

Example 1

Example 2

Select Zurn #200 Unit

Cold Water Branch
2 WC at 10 F.U. . . . . ea. = 20
2 Urinal at 5 F.U. . . .  ea. = 10
4 Lav. at 1° F.U. . . . . ea. =   6

   Total  36

Hot Water Branch
4 Lav. at 1° F.U. . . . . ea. =   6

   Total  26

Select Zurn #100 Unit