Page 7

    

For further assistance with troubleshooting visit http://www.zurn.com

Problem

Possible Cause

Corrective Action

Faucet is non-responsive Battery voltage low or no power.

Verify power is provided by ACA

Sensor and electronic connector 

cable has bent or broken pins.

Check to see if pins are missing, bent, or broken. If yes, then the 

electronic box needs to be replaced

Sensor lens could have surface 

damage, scratches, or deposit 

build ups.

Inspect the sensor lens underneath the spout tip. May require

 

cleaning with a damp cloth or sensor replacement

Sensor lens could be obstructed 

by environmental factors such 

as highly reflective surfaces or 

bright lighting conditions.

If this is the case, then adjust the dip switch settings for sensor 

sensitivity per the diagram on previous page (switches 7 and 8). 

Direct sunlight into sink may make the unit inoperable. Do not 

allow direct sunlight into sink. 

 

 

If one mode does not help try one of the following:

 

-switching 7 to Off to set the sensor to the lowest sensitivity level 

(detection range may be less for all hand types).

 

-switching to alternate mode using switch 8; mode A or B depend-

ing on current configuration

 

 

Reset sensor after dip switch changes.

Faucet does not activate 

after initial installation

Sensor may not have had enough 

time to calibrate prior to a user 

or target trying to initiate activa-

tion.

Disconnect the sensor and electronic box cables and wait for 30 

seconds. Reconnect the cables, but allow for another 30 seconds 

before placing hands or a target within the sensor range. You 

should hear a click of the solenoid once calibration is complete.

Check if protective film was 

removed from lens.

Water does not stop

Electronics box cable connector 

has bent pins that are shorted

Check to see if pins are missing, bent, or broken. If yes, then the 

electronic box needs to be replaced.

Ghost Activation

Sensor lens could be obstructed 

or environmental factors such as 

highly reflective surfaces and/or 

bright sunlight conditions.

Check/clean sensor lens of any debris or buildup If sunlight or IR 

interference is a factor, refer to page 7 “Sensor Sensitivity” and 

adjust faucet for Mode B operation.  Also, decreasing the sensitiv-

ity setting (switch 7) may help.

 

 

Reset sensor after dip switch changes.

Sensor faucet is leaking

 

underneath the sink or

 

counter

Mounting hardware is not tight-

ened sufficiently (faucet shank, 

electronic box, supply hoses, etc)

Check and ensure the nuts and joints are tight and secure from 

the supply stop all the way to the faucet shank.

Missing the washer located in the 

solenoid box nut where it assem-

bles to the faucet shank.

Make sure the water supply stops are shut off. Check to ensure 

the washer is installed or damaged. If not, install washer. If a 

washer is damaged, replace with new.

Trouble Shooting:  Faucet

Содержание plumbSMART AquaSense Z6913-XL-W1

Страница 1: ... the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the products sold hereunder are consumer products the implied warranty of merchantability is limited to a period of three years and shall be limited solely to the replacement of the defective good...

Страница 2: ...This Page Intentionally Left Blank ...

Страница 3: ...tional Smooth Jawed Wrench Phillips Head Screwdriver 3 32 M3 Allen Wrenches Endpoint Y Cable CWB DC Adapter Aerator and Key Electronics Box with Ceramic Valve Filter Base Gasket Spout Assembly Shank Mounting Kit Spout Assembly Aerator and Key Electronics Box with Ceramic Valve Shank Mounting Kit Base Gasket Filter ...

Страница 4: ...0 HW6 with CWB or P6900 ACA BA with CWB for endpoint Sensor Range Self calibrated dependent upon sink depth and finish Operating Water Pressure 10 125 psi Operational Water Temperature 33 F to 140 F 1 C to 60 C Aerator 1 5 GPM Vandal Resistant Standard Important Safety Information Installer is responsible for ensuring the product is installed and conforms to all plumbing codes and ordinances Do no...

Страница 5: ...ult in debris clogging the inlets and or internal control and mixing valve 1 Carefully screw aerator into spout using included tool Take care to not pinch blue o ring 3 Ensure that slot in plastic washer is facing forward Sensor cable should not pass through plastic mounting washer Spout Installation Instructions Z6913 XL W1 Z6915 XL W1 Cover Plate Installation Instructions 1 For faucets with CP4 ...

Страница 6: ...able Endpoint Electronic Module Installation Instructions 4 Connect Y cable to electronics module assembly Ceramic Valve 2 Tighten electronics module assembly to shank and connect water line s 5 a ACA version Connect supplied inline connector and AC adapter 5 b Optional HW6 Hardwired 6V version Connect supplied inline connector and hardwire adapter When securing the CWB wires to the screw terminal...

Страница 7: ...lead to dulling of luster attacking of chrome plating or decorative finishes ONLY use mildly warm soapy water and then wipe the device dry with a clean soft towel or cloth Upon cleaning other areas of the restroom be sure the sensor lenses are protected from other cleaning chemicals solvents to prevent potential damages to the sensor and or electronics Care and Cleaning Instructions 5 c MJ unit so...

Страница 8: ...ctions Thick walls and reflective surfaces such as metal weaken the signal between the gateway and other devices The LoRa antenna is an omni directional antenna but for best results mount the device so the LoRa antenna is in a vertical position near the top of a wall We recommend conducting a site survey to test the signal strength in different locations before you mount the device Step 4 Mounting...

Страница 9: ...me to calibrate prior to a user or target trying to initiate activa tion Disconnect the sensor and electronic box cables and wait for 30 seconds Reconnect the cables but allow for another 30 seconds before placing hands or a target within the sensor range You should hear a click of the solenoid once calibration is complete Check if protective film was removed from lens Water does not stop Electron...

Страница 10: ...ronics Restore proper electrical connection as needed Step 2 Test activate the faucet If problem persists see Faucet Troubleshooting section in this guide for other steps Status Good posted in plumbSMART and faucet actuates but usage event data not appearing in plumbSMART Charts Step 1 Verify gateway is powered and LoRa Status LED is ON If not apply power per Zurn Gateway Installation Guide or see...

Страница 11: ...cility IT administrator to modify port rules to allow Zurn gateway to access the internet via local router If gateway model is ETH LTE visually verify SIM card is installed in designated slot on the side of gateway If unit has a SIM card then disconnect ethernet cable and power cycle the gateway and wait for unit to initialize and connect LORA LED should turn ON solid after initialization Step 4 I...

Страница 12: ...ect fixture model Verify product image and model number from plumbSMART product page Details tab against model number cited on product literature and packaging If incorrect contact Zurn Custom Service at 1 855 ONE ZURN 1 855 663 9876 for assistance High Daily Faucet Activate Rate posted in plumbSMART Step 1 Verify faucet is not falsely triggering See Faucet Troubleshooting section for appropriate ...

Страница 13: ...ard faucet installation Control Box Attach adapter here with MV P6900 12BC Filter P6900 MV ADAP Supplied Adapter with MV Option To Control Box Supplied Adapter 3 8 Copper Tube By Others For use with MV Option Mixing Valve Filter and Mixing Valve Installation ...

Страница 14: ...te Gasket Item 2B P6913 42 WEDGE Mounting Kit Item 3 P6900 43 Ceramic Valve Item 4 P6900 XL CV B L Smart Connected Faucet Retrofit Kit Items 5 8 P6900 RK W1 Description Product No Filter Kit Item 9 P6900 120BC Filter Screen Item 10 P6900 MV 7 Mixing Valve with Filter Item 11 P6900 XL MV Composite Mixing Valve Adapter Item 12 P6900 MV ADAP 4 Cast Cover Plate w Gasket Item 13 P6900 CP4 8 Cast Cover ...

Страница 15: ...This Page Intentionally Left Blank ...

Страница 16: ...TRIES LLC 511 W Freshwater Way Milwaukee WI U S A 53204 Ph 1 855 ONE ZURN Fax 919 775 3541 In Canada ZURN INDUSTRIES LIMITED 7900 Goreway Drive Unit 10 Brampton Ontario L6T 5W6 Ph 905 405 8272 Fax 905 405 1292 Rev C Date 04 06 21 C N No 143637 Prod Dwg No FV740 ...

Отзывы: