INST2018_Model350_65-250  Rev. 11/18

ZURN.COM.AU

ZURN WILKINS BACKFLOW

Double Check Valve Assembly

INSTALLATION & MAINTENANCE 

MODEL 350 65-250mm

TESTING PROCEDURES

TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE

REQUIREMENT: 

    The static pressure drop across check valve #1 shall be at least 

1.0 psid. If test cock #3 is not at the highest point of the check 

valve body, then a vertical tube must be installed on test cock 

#3 so that it rises to the top of the check valve body.

PROCEDURE:

1.

Slowly open all 4 test cocks to remove any foreign material and

attach fittings.

2.

Attach hose from the high side of the test kit to the #2 test

cock.

3.

Open test cock #2 and bleed all air from the hose and gauge

by opening the high side bleed needle valve. Close high side

bleed needle valve. If a tube is attached to test cock #3, open

test cock #3 to fill the tube. Close test cock #3. Close #2

shut-off valve then close the #1 shut-off valve.

4.

Hold gauge at same level as test cock #3 or water level in tube.

Slowly open test cock #3. Record the static pressure drop

across check valve #1 after gauge reading stabilizes and water

stops running out of test cock #3.

5.

Close all test cocks, open shut-off valve #1 and remove test

equipment.

TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE

REQUIREMENT: 

    The static pressure drop across check valve #2 shall be at least 

1.0 psid. If test cock #4 is not at the highest point of the check 

valve body, then a vertical tube must be installed on test cock 

#4 so that it rises to the top of the check valve body.

PROCEDURE:

1.

Attach hose from the high side of the test kit to the #3 test

cock.

2.

Open test cock #3 and bleed all air from the hose and gauge by

opening the high side bleed needle valve. Close high side bleed

needle valve. If a tube is attached to test cock #4, open test

cock #4 to fill the tube. Close test cock #4. Close #1 shut-off

valve.

3.

Hold gauge at same level as test cock #4 or water level in tube.

Slowly open test cock #4. Record the static pressure drop

across check valve #2 after gauge reading stabilizes and water

stops running out of test cock #4.

4.

Close all test cocks, slowly open shut-off valve #1 & #2 and

remove test equipment.

EQUIPMENT REQUIRED: Differential pressure gauge test kit.

VENT HOSE

LOW SIDE HOSE

HIGH SIDE HOSE

LOW SIDE BLEED

NEEDLE VALVE

#1 TEST COCK

#4 TEST COCK

#3 TEST COCK

#2 TEST COCK

#2 SHUT-OFF

VALVE

#1 SHUT-OFF

VALVE

HIGH SIDE BLEED

NEEDLE VALVE

Содержание 350

Страница 1: ...llation methods approvals and guidance 5 Resilient seated shutoff valves are required to be installed on both the inlet and outlet of the device to make field testing possible WARRANTY ZURN WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recommended Please refer to the LWG Zurn Zurn Wilkins Product Warranty Statement for details PERFORMANCE 1200kPa...

Страница 2: ...es and water stops running out of test cock 3 5 Close all test cocks open shut off valve 1 and remove test equipment TEST NO 2 TIGHTNESS OF 2 CHECK VALVE REQUIREMENT The static pressure drop across check valve 2 shall be at least 1 0 psid If test cock 4 is not at the highest point of the check valve body then a vertical tube must be installed on test cock 4 so that it rises to the top of the check ...

Страница 3: ... side of the seal ring is unused it is possible to invert the seal ring This would be considered a temporary solution to fixing a fouled check and should be replaced with a new seal ring as soon as possible 9 Inspect valve cavity and seating areas Remove any debris 10 Reverse the above procedures to reinstall check assemblies Lubricate seat o rings to hold them in place while reinstalling seat Plac...

Страница 4: ...S cont d PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION LEAKING CHECK VALVES 1 Debis on seat or seal ring 1 Clean seat area 2 Damaged seat area 2 Replace check assembly 3 Damaged seat o ring 3 Replace seat o ring 4 Damaged bolt o ring s on check retainer 4 Replace o ring s LOW OR NO FLOW 1 Device installed backwards 1 Verify flow direction arrow 2 Gate valves not fully open 2 Turn handles counter clockw...

Страница 5: ...RFORMANCE CHARACTERISTICS MODEL 350 65 80 100mm 0 0 35 69 104 12 6 25 2 37 9 50 5 FLOW RATES l s PRESSURE LOSS kPa 65mm 80mm 100mm MODEL 350 150 200mm 0 35 69 104 25 2 50 5 75 7 100 9 126 2 151 4 FLOW RATES l s 150mm 200mm 0 0 35 69 104 63 0 126 0 189 0 252 0 MODEL 350 200 250mm PRESSURE LOSS kpa 200mm 250mm 0 PRESSURE LOSS kPa FLOW RATES l s ...

Отзывы: